Installation manual

8

ERLQ006~008BBV39

Outdoor unit for air to water heat pump

4PW68003-1A – 03.2011

8.

R

EFRIGERANT

 

PIPE

 

SIZE

 

AND

 

ALLOWABLE

 

PIPE

 

LENGTH

8.1.

Selection of piping material

Construction material: phosphoric acid deoxidised seamless
copper for refrigerant.

Temper grade: use piping with temper grade in function of the
pipe diameter as listed in table below.

The pipe thickness of the refrigerant piping should comply with
applicable legislation. The minimal pipe thickness for R410A
piping must be in accordance with the table below.

O=Annealed

8.2.

Refrigerant pipe size

The pipes between outdoor unit and indoor unit should have the
same size as the outdoor connections.

8.3.

Allowable pipe length and height difference

See the figure and table below concerning allowable lengths and
heights. Assume that the longest line in the figure corresponds with
the actual longest pipe, and the highest unit in the figure corresponds
with the actual highest unit.

 

Height

 

Length

9.

P

RECAUTIONS

 

ON

 

REFRIGERANT

 

PIPING

Do not allow anything other than the designated refrigerant to
get mixed into the freezing cycle, such as air, etc. If any
refrigerant gas leaks while working on the unit, ventilate the
room thoroughly right away.

Use R410A only when adding refrigerant
Installation tools:
Make sure to use installation tools (gauge manifold charge hose,
etc.) that are exclusively used for R410A installations to
withstand the pressure and to prevent foreign materials (e.g.
mineral oils and moisture) from mixing into the system.
Vacuum pump:
Use a 2-stage vacuum pump with a non-return valve
Make sure the pump oil does not flow oppositely into the system
while the pump is not working.
Use a vacuum pump which can evacuate to –100.7 kPa (5 Torr,
–755 mm Hg).

In order to prevent dirt, liquid or dust from entering the piping,
cure the piping with a pinch or taping.
Great caution is needed when passing copper tubes through
walls.

Piping should be mounted so that the flare is not subjected to
mechanical stress.

DANGER

Piping and other pressure containing parts shall
comply with the applicable legislation and shall be
suitable for refrigerant. Use phosphoric acid
deoxidised seamless copper for refrigerant.

Installation shall be done by an installer, the choice of
materials and installation shall comply with applicable
legislation. In Europe the EN378 is the application
standard that shall be used.

NOTICE

To persons in charge of piping work:

Be sure to open the stop valve after piping installing and
vacuming is complete. (Running the system with the valve
closed may break the compressor.)

INFORMATION

It is forbidden to discharge refrigerant into the atmosphere.
Collect the refrigerant in accordance with the freon
collection and destruction law.

Pipe Ø

Temper grade 

of piping material 

Minimal thickness t (mm)

6.4

O

0.80

15.9

O

1.00

Refrigerant pipe size (mm)

Gas pipe

Ø15.9

Liquid pipe

Ø6.4

Allowable pipe length

Maximum total one-way piping length

L

30 m

Minimum one-way piping length

L

3  m

Maximum height between indoor and outdoor

H

20 m

Chargeless length

L

10 m

Place

Installation period

Protection method

Outdoor unit

More than a month

Pinch the pipe

Less than a month

Pinch or tape the pipe

Indoor unit

Regardless of the 

period

H

L

Содержание ERLQ006BBV39

Страница 1: ...INSTALLATION MANUAL ERLQ006BBV39 ERLQ007BBV39 ERLQ008BBV39 Outdoor unit for air to water heat pump...

Страница 2: ...stig de bepalingen van 05 siguiendo las disposiciones de 06 secondo le prescrizioni per 07 v v v 08 de acordo com o previsto em 09 10 under iagttagelse af bestemmelserne i 11 enligt villkoren i 12 git...

Страница 3: ...13 2 Forced cooling operation 12 14 Electrical wiring work 12 14 1 Precautions on electrical wiring work 12 14 2 Internal wiring Parts table 13 14 3 Connecting power supply and interunit wiring 13 No...

Страница 4: ...s described in this manual shall be carried out by an installer Be sure to wear adequate personal protection equipment protection gloves safety glasses when performing installation maintenance or serv...

Страница 5: ...lectrical shock and fire Electrical work must be carried out in accordance with the installation manual and the national electrical wiring rules or code of practice Insufficient capacity or incomplete...

Страница 6: ...X008 unit designed exclusively for R410A 3 3 Installation For installation of the indoor unit refer to the indoor unit installation manual Never operate the unit without the thermistors burning of th...

Страница 7: ...the unit or the operation noise will not cause a nuisance to the neighbours of the user Avoid places near a bedroom and the like so that the operation noise will cause no trouble There must be suffici...

Страница 8: ...peration Disruption of operation due to rise of high pressure When a strong wind blows continuously on the face of the unit the fan can start rotating very fast until it breaks Refer to the figures fo...

Страница 9: ...owing over the footpath so that in case of ambient freezing temperatures the footpath does not become slippery 7 INSTALLATION SERVICING SPACE Where a wall or other obstacle is in the path of the outdo...

Страница 10: ...e system Vacuum pump Use a 2 stage vacuum pump with a non return valve Make sure the pump oil does not flow oppositely into the system while the pump is not working Use a vacuum pump which can evacuat...

Страница 11: ...material polyethylene foam Heat transfer rate 0 041 to 0 052 W mK 0 035 to 0 045 kcal mh C Refrigerant gas pipe s surface temperature reaches 110 C max Choose heat insulation materials that will withs...

Страница 12: ...Check that the compound pressure gauge reads 0 1 MPa 760 mm Hg 4 Close the gauge manifold s low pressure valve Lo and stop the vacuum pump Leave as is for 4 5 minutes and make sure that the coupling m...

Страница 13: ...to charge additionally if the piping length is under 10 m If the piping length is over 10 m please determine the additional amount of refrigerant to be charged using the formula below R total length m...

Страница 14: ...h the inverter resistant to high frequency electrical noise to avoid unnecessary opening of the earth leakage circuit breaker The power supply cable and circuit breaker must be selected in accordance...

Страница 15: ...enoid valve coil Z1C Z7C Ferrite core 14 3 Connecting power supply and interunit wiring 1 Strip the insulation from the wire 20 mm 2 Connect the connection wires between the indoor and outdoor units s...

Страница 16: ...e at terminal block L N 1 2 3 C A 3 1 4 5 4 2 B 2 1 1 Stranded conductor wire 2 Round crimp style terminal 1 Strip wire end to this point 2 Excessive strip length may cause electrical shock or leakage...

Страница 17: ...chnical specifications 18 2 Electrical specifications INFORMATION If the circuit breaker trips to shut off the power to the outdoor unit the system will restore the original operation mode when the po...

Страница 18: ......

Страница 19: ......

Страница 20: ...4PW68003 1A 03 2011 Copyright 2011 Daikin...

Отзывы: