ERLQ006~008BBV39

Outdoor unit for air to water heat pump

4PW68003-1A – 03.2011

Installation manual

13

As this unit is equipped with an inverter, installing a phase
advancing capacitor not only will deteriorate power factor
improvement effect, but also may cause capacitor abnormal
heating accident due to high-frequency waves. Therefore, never
install a phase advancing capacitor.

This equipment complies with EN/IEC 61000-3-11

(1)

  provided

that the system impedance Z

sys

 is less than or equal to Z

max

 at

the interface point between the user's supply and the public
system. It is the responsibility of the installer or user of the
equipment to ensure, by consultation with the distribution
network operator if necessary, that the equipment is connected
only to a supply with a system impedance Z

sys

  less than or

equal to Z

max

. Z

max

=0.42 

Equipment complying with EN/IEC 61000-3-12

(2)

14.2. Internal wiring – Parts table

AC1,AC2............................Connector

E1,E2.................................Connector

E1H....................................Bottom plate heater

FU1....................................Fuse 30 A

FU2,FU3 ............................Fuse 3.15 A

FU4,FU5 ............................Fuse 1 A 250 V

HR1,HR2 ...........................Connector

L.........................................Live

L1R ....................................Reactor

LED A ................................Pilot lamp

M1C ...................................Compressor motor

M1F ...................................Fan motor

MRM10,MRM20,MRC/W...Magnetic relay

N ........................................Neutral

PCB1,PCB2.......................Printed circuit board

PM1 ...................................Power module

Q1L....................................Overload protector

R1T~R3T ...........................Thermistor

S2~S102............................Connector

SA2....................................Surge arrester

Sheet metal .......................Terminal strip fixed plate

SW1...................................Forced operation ON/OFF switch

SW4...................................Local setting switch

U ........................................Connector

V ........................................Connector

V2,V3,V5,V9,V100.............Varistor

W .......................................Connector

X11A,X12A ........................Connector

X1M,X2M...........................Terminal strip

Y1E....................................Electronic expansion valve voil

Y1R....................................Reversing solenoid valve coil

Z1C~Z7C ...........................Ferrite core

14.3. Connecting power supply and interunit wiring

1

Strip the insulation from the wire (20 mm).

2

Connect the connection wires between the indoor and outdoor
units so that the terminal numbers match (see wiring diagram
below). Tighten the terminal screws securely. We recommend a
flathead screwdriver to tighten the screws.
See also caution 2 under 

"Notes to observe" on page 14

  for

wiring guidelines.

Interconnection between indoor unit and outdoor unit: 

when wire length exceeds 10 m, use Ø2.5 mm wires 
instead of Ø1.5 mm wires.

Power supply cable 

(refer to the unit nameplate for maximum running current)

Earth
Safety breaker
Earth leakage circuit breaker

3

Earth terminal installation

Use the following method when installing single core wires.

Single core wire
Screw
Flat washer

Use the following method when using round crimp-style
terminals.

Round crimp-style terminal
Screw
Flat washer

4

Pull the connected wire and make sure that it does not
disconnect. Then fix the wires in place in the wire clamp. See
also 

"Notes to observe" on page 14

.

CAUTION

Be sure to install the required fuses or circuit breakers.

(1) European/International Technical Standard setting the limits for voltage 

changes, voltage fluctuations and flicker in public low-voltage supply 
systems for equipment with rated current 

75 A.

(2) European/International Technical Standard setting the limits for harmonic 

currents produced by equipment connected to public low-voltage systems 
with input current >16 A and 

75 A per phase.

WARNING

This unit must be earthed.

For earthing, follow the applicable local standard for
electrical installations.

1

2

3

1 2 3

L N

H05VV

2

1

4

5

3

50 Hz

230 V

1 2 3

1 2 3

A'

A

AA'

2

3

1

1

3

3

2

1

B

2

3

1

B

Содержание ERLQ006BBV39

Страница 1: ...INSTALLATION MANUAL ERLQ006BBV39 ERLQ007BBV39 ERLQ008BBV39 Outdoor unit for air to water heat pump...

Страница 2: ...stig de bepalingen van 05 siguiendo las disposiciones de 06 secondo le prescrizioni per 07 v v v 08 de acordo com o previsto em 09 10 under iagttagelse af bestemmelserne i 11 enligt villkoren i 12 git...

Страница 3: ...13 2 Forced cooling operation 12 14 Electrical wiring work 12 14 1 Precautions on electrical wiring work 12 14 2 Internal wiring Parts table 13 14 3 Connecting power supply and interunit wiring 13 No...

Страница 4: ...s described in this manual shall be carried out by an installer Be sure to wear adequate personal protection equipment protection gloves safety glasses when performing installation maintenance or serv...

Страница 5: ...lectrical shock and fire Electrical work must be carried out in accordance with the installation manual and the national electrical wiring rules or code of practice Insufficient capacity or incomplete...

Страница 6: ...X008 unit designed exclusively for R410A 3 3 Installation For installation of the indoor unit refer to the indoor unit installation manual Never operate the unit without the thermistors burning of th...

Страница 7: ...the unit or the operation noise will not cause a nuisance to the neighbours of the user Avoid places near a bedroom and the like so that the operation noise will cause no trouble There must be suffici...

Страница 8: ...peration Disruption of operation due to rise of high pressure When a strong wind blows continuously on the face of the unit the fan can start rotating very fast until it breaks Refer to the figures fo...

Страница 9: ...owing over the footpath so that in case of ambient freezing temperatures the footpath does not become slippery 7 INSTALLATION SERVICING SPACE Where a wall or other obstacle is in the path of the outdo...

Страница 10: ...e system Vacuum pump Use a 2 stage vacuum pump with a non return valve Make sure the pump oil does not flow oppositely into the system while the pump is not working Use a vacuum pump which can evacuat...

Страница 11: ...material polyethylene foam Heat transfer rate 0 041 to 0 052 W mK 0 035 to 0 045 kcal mh C Refrigerant gas pipe s surface temperature reaches 110 C max Choose heat insulation materials that will withs...

Страница 12: ...Check that the compound pressure gauge reads 0 1 MPa 760 mm Hg 4 Close the gauge manifold s low pressure valve Lo and stop the vacuum pump Leave as is for 4 5 minutes and make sure that the coupling m...

Страница 13: ...to charge additionally if the piping length is under 10 m If the piping length is over 10 m please determine the additional amount of refrigerant to be charged using the formula below R total length m...

Страница 14: ...h the inverter resistant to high frequency electrical noise to avoid unnecessary opening of the earth leakage circuit breaker The power supply cable and circuit breaker must be selected in accordance...

Страница 15: ...enoid valve coil Z1C Z7C Ferrite core 14 3 Connecting power supply and interunit wiring 1 Strip the insulation from the wire 20 mm 2 Connect the connection wires between the indoor and outdoor units s...

Страница 16: ...e at terminal block L N 1 2 3 C A 3 1 4 5 4 2 B 2 1 1 Stranded conductor wire 2 Round crimp style terminal 1 Strip wire end to this point 2 Excessive strip length may cause electrical shock or leakage...

Страница 17: ...chnical specifications 18 2 Electrical specifications INFORMATION If the circuit breaker trips to shut off the power to the outdoor unit the system will restore the original operation mode when the po...

Страница 18: ......

Страница 19: ......

Страница 20: ...4PW68003 1A 03 2011 Copyright 2011 Daikin...

Отзывы: