ERLQ006~008BBV39

Outdoor unit for air to water heat pump

4PW68003-1A – 03.2011

Installation manual

15

15.2. Trial operation and testing

1

Measure the voltage at the primary side of the safety breaker.
Check that it is 230 V.

2

Carry out the test operation in accordance with the indoor
installation manual and operation manual to ensure that all
functions and parts are working properly.

16. M

AINTENANCE

 

AND

 

SERVICING

16.1. Service precautions

In order to ensure optimal operation of the unit, a number of checks
and inspections should be carried out on the unit at regular intervals,
preferably yearly. 

This maintenance shall be carried out by the installer or service
agent.

Please note that some sections of the electric component box
are extremely hot.

Make sure you do not touch a conductive section.

After measuring the residual voltage, pull out the outdoor fan
connector.

The outdoor fan may rotate due to strong backblow wind,
causing the capacitor to charge. This may result in an electric
shock.

After maintenance, make sure the outdoor fan connector is
connected again. Otherwise, the unit may break down.

16.2. Service mode operation

Refer to the service manual to carry out any service mode operation.

17. D

ISPOSAL

 

REQUIREMENTS

Dismantling of the unit, treatment of the refrigerant, of oil and of other
parts must be done in accordance with applicable legislation.

18. U

NIT

 

SPECIFICATIONS

18.1. Technical specifications

18.2. Electrical specifications

INFORMATION

If the circuit breaker trips to shut off the power to the
outdoor unit, the system will restore the original
operation mode when the power supply is restored.
See installation manual, chapter "Field settings" of the
indoor unit for more details.

INFORMATION

Instruct the customer how to operate the unit correctly.

NOTICE

For applications with benefit kWh rate power supply

The outdoor unit power supply (L, N) interruption may not
be longer than 2 hours to guarantee optimized startup
condition for compressor. See installation manual of the
indoor unit for more details.

DANGER: ELECTRICAL SHOCK

See 

"2. General safety precautions" on page 2

.

DANGER: DO NOT TOUCH PIPING AND INTERNAL
PARTS

See 

"2. General safety precautions" on page 2

.

Do not touch live parts for 10 minutes after the power
supply is turned off because of high voltage risk.

Make sure that the power supply is turned off before
performing the maintenance work. The heater of the
compressor may operate even in stop mode.

CAUTION

Do not rinse the outdoor unit. This may cause electric
shocks or fire.

NOTICE

Touch a metal part by hand (such as the stop valve) in
order to eliminate static electricity and to protect the PCB
before performing service.

Casing material

Painted galvanised steel

Dimensions hxwxd

(mm)

735x825x300

Weight 

(kg)

57

Operation range

• cooling (min./max.)

(°C)

10/43

• heating (min./max.)

(°C)

–15/25

• domestic hot water 

(min./max.)

(°C)

–15/35

Refrigerant oil

Daphne FVC68D

Piping connection

• liquid

(mm)

6.4

• gas

(mm)

15.9

Phase

1~

Frequency

(Hz)

50

Voltage range

• minimum

(V)

207

• maximum

(V)

253

Содержание ERLQ006BBV39

Страница 1: ...INSTALLATION MANUAL ERLQ006BBV39 ERLQ007BBV39 ERLQ008BBV39 Outdoor unit for air to water heat pump...

Страница 2: ...stig de bepalingen van 05 siguiendo las disposiciones de 06 secondo le prescrizioni per 07 v v v 08 de acordo com o previsto em 09 10 under iagttagelse af bestemmelserne i 11 enligt villkoren i 12 git...

Страница 3: ...13 2 Forced cooling operation 12 14 Electrical wiring work 12 14 1 Precautions on electrical wiring work 12 14 2 Internal wiring Parts table 13 14 3 Connecting power supply and interunit wiring 13 No...

Страница 4: ...s described in this manual shall be carried out by an installer Be sure to wear adequate personal protection equipment protection gloves safety glasses when performing installation maintenance or serv...

Страница 5: ...lectrical shock and fire Electrical work must be carried out in accordance with the installation manual and the national electrical wiring rules or code of practice Insufficient capacity or incomplete...

Страница 6: ...X008 unit designed exclusively for R410A 3 3 Installation For installation of the indoor unit refer to the indoor unit installation manual Never operate the unit without the thermistors burning of th...

Страница 7: ...the unit or the operation noise will not cause a nuisance to the neighbours of the user Avoid places near a bedroom and the like so that the operation noise will cause no trouble There must be suffici...

Страница 8: ...peration Disruption of operation due to rise of high pressure When a strong wind blows continuously on the face of the unit the fan can start rotating very fast until it breaks Refer to the figures fo...

Страница 9: ...owing over the footpath so that in case of ambient freezing temperatures the footpath does not become slippery 7 INSTALLATION SERVICING SPACE Where a wall or other obstacle is in the path of the outdo...

Страница 10: ...e system Vacuum pump Use a 2 stage vacuum pump with a non return valve Make sure the pump oil does not flow oppositely into the system while the pump is not working Use a vacuum pump which can evacuat...

Страница 11: ...material polyethylene foam Heat transfer rate 0 041 to 0 052 W mK 0 035 to 0 045 kcal mh C Refrigerant gas pipe s surface temperature reaches 110 C max Choose heat insulation materials that will withs...

Страница 12: ...Check that the compound pressure gauge reads 0 1 MPa 760 mm Hg 4 Close the gauge manifold s low pressure valve Lo and stop the vacuum pump Leave as is for 4 5 minutes and make sure that the coupling m...

Страница 13: ...to charge additionally if the piping length is under 10 m If the piping length is over 10 m please determine the additional amount of refrigerant to be charged using the formula below R total length m...

Страница 14: ...h the inverter resistant to high frequency electrical noise to avoid unnecessary opening of the earth leakage circuit breaker The power supply cable and circuit breaker must be selected in accordance...

Страница 15: ...enoid valve coil Z1C Z7C Ferrite core 14 3 Connecting power supply and interunit wiring 1 Strip the insulation from the wire 20 mm 2 Connect the connection wires between the indoor and outdoor units s...

Страница 16: ...e at terminal block L N 1 2 3 C A 3 1 4 5 4 2 B 2 1 1 Stranded conductor wire 2 Round crimp style terminal 1 Strip wire end to this point 2 Excessive strip length may cause electrical shock or leakage...

Страница 17: ...chnical specifications 18 2 Electrical specifications INFORMATION If the circuit breaker trips to shut off the power to the outdoor unit the system will restore the original operation mode when the po...

Страница 18: ......

Страница 19: ......

Страница 20: ...4PW68003 1A 03 2011 Copyright 2011 Daikin...

Отзывы: