ERLQ006~008BBV39

Outdoor unit for air to water heat pump

4PW68003-1A – 03.2011

Installation manual

9

10. R

EFRIGERANT

 

PIPING

10.1. Flaring the pipe end

To flare each pipe end, follow the procedure below:

1

Cut the pipe end with a pipe cutter.

2

Remove burrs with the cut surface facing downward so that the
chips do not enter the pipe.

Cut exactly at right angles.
Remove burrs

3

Remove the flare nut from the stop valve and put the flare nut on
the pipe.

4

Flare the pipe. Set exactly at the position shown below.

5

Check that the flaring is properly made.

Flare's inner surface must be flaw-

free.

The pipe end must be evenly flared in 

a perfect circle.

Make sure that the flare nut is fitted.

10.2. Connecting the refrigerant piping to the outdoor 

unit

1

When connecting the flare nut, coat the flare inner surface with
ether oil or with ester oil and initially tighten 3 or 4 turns by hand
before tightening firmly.

2

When loosening a flare nut, always use two wrenches together.

When connecting the piping, always use a spanner and torque
wrench together to tighten the flare nut to prevent nut cracking
and leaks.

Torque wrench
Spanner
Piping union
Flare nut

10.3. Refrigerant piping work

Pipe handling guidelines

All pipe bends should be as gentle as possible. Use a pipe bender for
bending.

Bending radius should be 30 to 40 mm or larger.

Selection of copper and heat insulation materials

When using commercial copper pipes and fittings, observe the
following:

Insulation material: polyethylene foam
Heat transfer rate: 0.041 to 0.052 W/mK (0.035 to 0.045 kcal/
mh°C)
Refrigerant gas pipe's surface temperature reaches 110°C max.
Choose heat insulation materials that will withstand this
temperature.

Be sure to insulate both the gas and liquid piping and to provide
insulation dimensions as below.

Gas pipe
Inter-unit wiring
Liquid pipe
Liquid pipe insulation
Finishing tape
Gas pipe insulation

Use separate thermal insulation pipes for gas and liquid
refrigerant pipes.

Flare tool for R410A 

(clutch type)

Conventional flare tool

Clutch type 

(Ridgid-type)

Wing nut type 

(Imperial-type)

A

0~0.5 mm

1.0~1.5 mm

1.5~2.0 mm

DANGER

Installation shall be done by an installer, the choice of
materials and installation shall comply with applicable
legislation. In Europe the EN378 is the application
standard that shall be used.

CAUTION

Do not use mineral oil on flared part.
Mineral oil getting into the system would reduce the
lifetime of the units.

Never use piping which has been used for previous
installations. Only use parts which are delivered with
the unit.

Do never install a drier to this R410A unit in order to
guarantee its lifetime. The drying material may
dissolve and damage the system.

Incomplete flaring may cause refrigerant gas leakage.

1

2

A

1

2

3

Flare nut

Flare nut tightening torque

Ø6.4 mm (1/4")

15~17 N•m

Ø15.9 mm (5/8")

63~75 N•m

Valve cap tightening torque

Valve cap

Gas pipe

Ø6.4 mm (1/4")

21.6~27.4 N•m

Ø15.9 mm (5/8")

44.1~53.9 N•m

Service port cap tightening torque

10.8~14.7 N•m

Pipe size

Pipe insulation

Outer diameter

Thickness

Inner diameter

Thickness

6.4 mm (1/4")

0.8 mm

8-10 mm

10 mm

15.9 mm (5/8")

1.0 mm

16-20 mm

13 mm

1

2

3

4

5

6

1

2

4

3

Содержание ERLQ006BBV39

Страница 1: ...INSTALLATION MANUAL ERLQ006BBV39 ERLQ007BBV39 ERLQ008BBV39 Outdoor unit for air to water heat pump...

Страница 2: ...stig de bepalingen van 05 siguiendo las disposiciones de 06 secondo le prescrizioni per 07 v v v 08 de acordo com o previsto em 09 10 under iagttagelse af bestemmelserne i 11 enligt villkoren i 12 git...

Страница 3: ...13 2 Forced cooling operation 12 14 Electrical wiring work 12 14 1 Precautions on electrical wiring work 12 14 2 Internal wiring Parts table 13 14 3 Connecting power supply and interunit wiring 13 No...

Страница 4: ...s described in this manual shall be carried out by an installer Be sure to wear adequate personal protection equipment protection gloves safety glasses when performing installation maintenance or serv...

Страница 5: ...lectrical shock and fire Electrical work must be carried out in accordance with the installation manual and the national electrical wiring rules or code of practice Insufficient capacity or incomplete...

Страница 6: ...X008 unit designed exclusively for R410A 3 3 Installation For installation of the indoor unit refer to the indoor unit installation manual Never operate the unit without the thermistors burning of th...

Страница 7: ...the unit or the operation noise will not cause a nuisance to the neighbours of the user Avoid places near a bedroom and the like so that the operation noise will cause no trouble There must be suffici...

Страница 8: ...peration Disruption of operation due to rise of high pressure When a strong wind blows continuously on the face of the unit the fan can start rotating very fast until it breaks Refer to the figures fo...

Страница 9: ...owing over the footpath so that in case of ambient freezing temperatures the footpath does not become slippery 7 INSTALLATION SERVICING SPACE Where a wall or other obstacle is in the path of the outdo...

Страница 10: ...e system Vacuum pump Use a 2 stage vacuum pump with a non return valve Make sure the pump oil does not flow oppositely into the system while the pump is not working Use a vacuum pump which can evacuat...

Страница 11: ...material polyethylene foam Heat transfer rate 0 041 to 0 052 W mK 0 035 to 0 045 kcal mh C Refrigerant gas pipe s surface temperature reaches 110 C max Choose heat insulation materials that will withs...

Страница 12: ...Check that the compound pressure gauge reads 0 1 MPa 760 mm Hg 4 Close the gauge manifold s low pressure valve Lo and stop the vacuum pump Leave as is for 4 5 minutes and make sure that the coupling m...

Страница 13: ...to charge additionally if the piping length is under 10 m If the piping length is over 10 m please determine the additional amount of refrigerant to be charged using the formula below R total length m...

Страница 14: ...h the inverter resistant to high frequency electrical noise to avoid unnecessary opening of the earth leakage circuit breaker The power supply cable and circuit breaker must be selected in accordance...

Страница 15: ...enoid valve coil Z1C Z7C Ferrite core 14 3 Connecting power supply and interunit wiring 1 Strip the insulation from the wire 20 mm 2 Connect the connection wires between the indoor and outdoor units s...

Страница 16: ...e at terminal block L N 1 2 3 C A 3 1 4 5 4 2 B 2 1 1 Stranded conductor wire 2 Round crimp style terminal 1 Strip wire end to this point 2 Excessive strip length may cause electrical shock or leakage...

Страница 17: ...chnical specifications 18 2 Electrical specifications INFORMATION If the circuit breaker trips to shut off the power to the outdoor unit the system will restore the original operation mode when the po...

Страница 18: ......

Страница 19: ......

Страница 20: ...4PW68003 1A 03 2011 Copyright 2011 Daikin...

Отзывы: