5
x
Operation
E EKSRDS1A
Control and pump unit for solar systems
4PW56033-1
Operating and installation instructions
27
5.3
Setting and menu operation
Tab. 5-2 shows an overview of the available measuring points and the associated display formats. Tab. 5-3 summarises the views
of the calculated parameters.
Tab. 5-2
Overview of measuring points
Tab. 5-3
Maximum values and calculated values -
1)
only with connected FlowSensor EKSFLP12A
5.3.1 Start display
After switching on, the solar control system carries out a self test where the display elements are switched on individually and
the setting parameters of the user level are displayed. The following test steps are run and displayed in succession for approx.
2 s (Fig 5-7):
– Immediately after switch-on the start screen appears showing the installed software version and the serial number of the
unit.
– At the initial start-up the user is prompted to select the display language.
– The function of the pump and the status indicator can only be checked manually for security reasons (see chapter 5.2.4).
Measuring
point
Designation
Measurement
range
Resolution
Sensor
Display
T
K
Solar panel temperature
-30 to 250 °C
1 K
PT 1000 temperature sensor
T
R
Return flow temperature
0 to 100 °C
1 K
PTC temperature sensor
T
S
Storage tank temperature
0 to 100 °C
1 K
PTC temperature sensor
T
V
Flow temperature
0 to 100 °C
1 K
FlowSensor with voltage output 0.5 to 3.5 V
V
Flow
0.0 to 12.0 l/min
0.1 l/min
FlowSensor 12 with voltage output
0.5 to 3.5 V
Individual
Designation
Value range
Resolution
Comment
TK max
Maximum measured solar
panel temperature
-30 to 250 °C
1 K
Maximum measured solar panel temperature
since reset
TK min
Minimum measured solar panel
temperature
-30 to 250 °C
1 K
Maximum measured solar panel temperature
since reset
V max
Maximum flow
0.0 to 12.0 l/min
0.1 l/min
Maximum flow rate achieved during filling
1)
PS
Peak output
0.0 to 99.9 kW
0.1 kW
Maximum value from 5 min output average
1)
HP (15h)
Daily peak output
0.0 to 99.9 kW
0.1 kW
Maximum value of the peak power within the
last 15 h
1)
W (15h)
Daily heat yield
0.0 to 999.9 kW
0.1 kWh
Heat yield obtained from the momentary
output within the last 15 h
1)
W
Total heat yield
0.0 to 9999.9 kWh
or 10.000 to 99.999
kWh
0.1 kWh
0.0001 MWh
Total solar heat yield obtained from the
momentary output
1)
P
Instantaneous output
0.0 to 99.9 kW
0.1 kW
Average of the last minute
1)
DT
Nominal spread
1 to 15 K
1 K
Nominal temperature difference T
V
–T
R
at
modulation operation (calculated)
1)
PS
Current output stage of the
solar panel circuit pump
0 to 100%
1%
1)
Stage min
Smallest released output stage
of the solar panel circuit pump
0 to 10;
0 to 100%
1; 1%
Only available with technician access (see
1)
P1 on
Running time of the solar panel
circuit pump
0 to 99999h
1 h
Only available with technician access (see
1)