 Operation

Operating and installation instructions

30

E EKSRDS1A

Control and pump unit for solar systems

4PW56033-1

5.3.4 Password input

The technician area of the settings menu is protected by a password, which is entered when opening the settings menu. The user 
level can also be password-protected. The user level and the technician level are shown in different colours in the settings menu. 
In addition to the path described in Fig 5-9 the user can press and hold the up arrow key (+) to open the settings menu during the 
control systems start display.

Password input is not required while the unit is under manual operation. A password remains valid for approx. 10 min after the 
last pushbutton press. After entering the password, the desired level is available for 2 s:
– "User OK",
– "Technician OK" or
– "Password incorrect".

User password

This password is not activated in the factory setting of the solar control system. A 4-digit numerical code can be entered to 
protect all adjustable parameters in the user level from unauthorised access (child protection or concierge function). The param-
eters of the user level can only be modified with a deactivated user password or with a valid user password.

A user password can be activated and changed or reassigned in the following menu path: "Selection 1/2" -> "Functions" -> 
"Change passw." (see Fig 5-9):

Enter old password into "current 0000” and new into "new 0000”. Confirm every digit of the password with OK.

For a new password, enter the new password in "current 0000” and also in "new 0000”.

If the user password is activated, the menu path "Selection 1/2" only shows "Password 0000". The user password only becomes 
active after 10 min or after the solar control system is restarted.

Technician password

The password is entered in the menu path: "Selection 1/2" at "Password 0000". It activates all important systems parameters 
in the settings menu for technicians (see Fig 5-9).

5.3.5 Language selection

At initial start-up or after a global reset the display (Fig 5-7) stops during start-up and the user is prompted to select the language. 

Select a language with arrow keys and confirm with OK. 

Open the settings menu in the menu path: "Selection 1/2" -> "Functions" -> "Change language" to select a different language 
(see Fig 5-9):

5.3.6 Setting and resetting parameters

Setting the parameters is in accordance with Fig 5-9. All adjustable parameters are shown with access level, adjustment range 
and factory setting in the Tab. 5-5. In the menu path: "Selection 1/2" -> "Parameter selection" -> "Reset" the maximum values 
and calculated values (see Tab. 5-5) can be reset. The selected maximum value is immediately set to "0" using the OK button.0 
Cancel the action with the down arrow key and the cursor returns to the left. Press OK to confirm the selection. Press the down 
arrow key repeatedly to open "Selection 2/2". Confirm "back" to return to the operating display. In the menu path: 
"Selection 2/2" -> "System" -> "Reset" all system parameters can be reset to the factory settings. The system is then 
restarted (see also section 5.2.8).

5.3.7 Manual setting of the pump speed regulation (only with connected FlowSensor EKSFLP12A)

At some output stages of the speed-controlled pump P

S

noise problems may be encountered occasionally The actual output of the 

selected stage is displayed as a percentage in the bottom line "Flow" in the operating display (see Fig 5-8). 

Note the output of the problematic stage. 

In the menu path: "Selection 2/2" -> "System" -> "Modulation" go to "Stage" (see Fig 5-9).

Up to 10 speed stages can be disabled here. The percentage output for the various stages is displayed under "Output" as well as 
the allocation number of the output stage (starting with 01 for the lowest output) and the activity status.

Содержание EKSR3PA

Страница 1: ...Control and pump unit for solar systems Control and pump unit for solar systems Operating and installation instructions English EKSR3PA EKSRDS1A Operating and installation instructions...

Страница 2: ......

Страница 3: ...on 10 3 1 System concepts 10 3 1 1 Parallel connection 10 3 1 2 Serial connection 10 3 2 Preparatory installation work 10 3 3 Pump unit EKSRDS1A 11 3 4 Controller EKSR3PA 12 3 4 1 Wall mounting 12 3 4...

Страница 4: ...st protection function 26 5 2 10 Leak protection function 26 5 3 Setting and menu operation 27 5 3 1 Start display 27 5 3 2 Operating display 28 5 3 3 Settings menu 28 5 3 4 Password input 30 5 3 5 La...

Страница 5: ...uctions Solar add on for air water heat pump system EKSOLHWAV1 Installation and operating instruction manual Process water for air water heat pump EKHWE EKHWS Installation instructions 1 2 Warning sig...

Страница 6: ...acturer This is the case for example with original spare parts 1 5 Instructions for operating safety Working on the roof Installation work on the roof may only be carried out by authorised and trained...

Страница 7: ...4 3 way diverter valve with drive motor 5 Heat distribution 6 Check valve I Double sided connection for 2 to 5 solar panels II Same side connection for max 3 solar panels not for in roof installation...

Страница 8: ...high degree of pre assembly ensure fast and simple installation Storage tank Only the hot water storage tanks EKHWE EKHWS can be used for the Daikin solar system Electronic control The fully electroni...

Страница 9: ...cessories Fig 2 3 Pump unit EKSRDS1A To connect the pump unit EKSRDS1A with the hot water storage tank EKHWE EKHWS Consists of Plate heat exchanger Circulation pump Fitting material Fig 2 4 Solar conn...

Страница 10: ...h both connections at one end max 3 solar panels 1 Solar panel connector 2 Mounting profile rail 3 Solar panel securing clip 4 Solar panel 5 Return connection solar panel 6 Flow connection solar panel...

Страница 11: ...formed and may damage the diaphragm expansion vessel MAG Always install the EKSRDS1A pump unit and the diaphragm expansion vessel MAG lower than the solar panels CAUTION Danger of scalding if incorrec...

Страница 12: ...accordance with EN 12828 The blow off line should be routed so that solar liquid can flow freely into a collection vessel when the safety valve is tripped The blow off line should be able to be block...

Страница 13: ...lug and connect the plug on the edge of the board of the control system to position TK 2 pole see Fig 3 10 6 Optional Connect the FlowSensor EKSFLP12A plug see Chapter 3 7 7 All the cables are routed...

Страница 14: ...F Programming socket for software updates FLS FlowSensor EKSFLP12A accessory TS Storage temperature sensor tS2 TR Return flow temperature sensor TK Solar panel temperature sensor BSK Connection cable...

Страница 15: ...tall cover on switch casing of solar panel circulation pump 4 Lay control line in casing of EKSRDS1A pump unit 5 Replace the external cover 1 on the pump unit EKSRDS1A 3 6 Storage temperature sensor F...

Страница 16: ...measurement range of the FlowSensor EKSFLP12A is between 0 and 12 l min flow volume and 0 to 120 C feed temperature The measured values are shown on the control unit EKSR3PA display The control system...

Страница 17: ...unlight or only if the solar panels are covered up WARNING If the heat transfer medium is mixed with other substances frost and corrosion protection may be reduced This may damage system components Co...

Страница 18: ...l circuit pressure to at least 0 3 bar above the pressure set at the diaphragm expansion vessel MAG see system fill pressure Tab 4 1 12 Close the upper KFE cock 13 Vent the system as follows Direct th...

Страница 19: ...Instructing the user owner 4 1 3 Filling the storage tank and heating circuit Filling the hot water storage tank see the associated installation and operating instructions Filling the heating system...

Страница 20: ...in the heating system that is shut down if there is danger of frost If there is a danger of frost for just a few days the unit s excellent heat insulation means that the insulated tank does not have t...

Страница 21: ...at pump that solar heat is available 8 Operating status indicator for PS solar panel circulation pump lights when pump is operating 9 Push arrow key up to switch the temperature or parameter display i...

Страница 22: ...put is regulated in dependence of the temperature difference between the solar feed and return flow temperature With a short delay Time PsE after switching on the solar circulation pump PS the contact...

Страница 23: ...me Time SP makes it possible that in the event of a switch off condition caused by the flow sensor FlowSensor only after the blocking time 0 600 s set in the solar control system has expired can the p...

Страница 24: ...ented after a safety time t2 Fig 5 4 If the pump output is too small the flow in the solar circuit can fall below the threshold value required to provide reliable data evaluation If the flow falls bel...

Страница 25: ...tart phase B Operating phase modulation C Flow stall D Low pump output stages are automatically blocked after flow stall V Flow in solar panel circuit V1 Minimum flow in start phase VS min V2 Minimum...

Страница 26: ...s or vapour formation in the solar circuit or a leak in the solar circuit To prevent the solar fluid from being pumped out of the system if there is a leak the pump PS is shutdown for 2 h and the faul...

Страница 27: ...ure sensor TV Flow temperature 0 to 100 C 1 K FlowSensor with voltage output 0 5 to 3 5 V V Flow 0 0 to 12 0 l min 0 1 l min FlowSensor 12 with voltage output 0 5 to 3 5 V Individual Designation Value...

Страница 28: ...briefly to confirm a selection open the next menu display or Saved is shown for approx 1 s if a value is changed In the required parameter display press OK to open parameter change mode In the menu F...

Страница 29: ...4PW56033 1 Operating and installation instructions 29 Fig 5 9 Settings menu ok ok ok ok Level 1 ok ok ok ok ok ok ok ok ok ok ok ok ok ok All incidents are deleted Correction values Flow l min 0 0 flo...

Страница 30: ...is entered in the menu path Selection 1 2 at Password 0000 It activates all important systems parameters in the settings menu for technicians see Fig 5 9 5 3 5 Language selection At initial start up...

Страница 31: ...1 K Flow correction 2 to 2 0 l min 1 l min Parameter Designation Access level Setting range Recommended setting range Factory setting Increment BE FA Delta T on Cut in temperature difference x x 1 80...

Страница 32: ...e tank circulation pump Time PsE so hot water is at the plate heat exchanger of the solar connection kit EKSOLHWAV1 until the tank circulation pump starts The maximum storage tank temperature TS max i...

Страница 33: ...ng instructions in the installation and operating instructions of the connection kit EKSOLHWAV1 5 4 3 Domestic water hygiene If no hot water is drawn off for several days and if the storage tank tempe...

Страница 34: ...the system All other sensor values can still be reached using the arrow keys Event code Plain text display Description Status display flashing Lamp flashing Consequence 0 Solar panel Solar panel senso...

Страница 35: ...of the solar connection kit EKSOLHWAV1 2 The fault signal W is shown in the left column of the solar control system display During the start procedure after expiry of time PsE and time UB the minimum...

Страница 36: ...In doing so observe the instructions in Chapter 4 Inbetriebnahme und Au erbetriebnahme Check the safety valve of the affected circuit for leaks c Increase the capacity of the pumps at the selector swi...

Страница 37: ...or PTC Feed temperature and flow sensor optional EKSFLP12A Pump unit EKSRDS1A Dimensions W x T x H 240 x 410 x 130 cm Operating voltage 230 V 50 Hz Solar panel circulation pump Grundfos Solar 25 65 13...

Страница 38: ...1116 1155 1194 1232 1270 1308 1347 1385 1423 1461 FlowSensor Sensor voltage in V according to manufacturer data TV 0 50 3 50 V 0 50 0 80 1 10 1 40 1 70 2 00 2 30 2 60 2 90 3 20 3 50 Flow rate Solar se...

Страница 39: ...circuit 11 13 Malfunction 34 35 Set values 19 38 Setting solar panel circuit 19 FlowSensor 9 16 19 23 27 31 34 37 38 Frost protection function 26 I Installation Connection pipes 11 Control unit 12 Flo...

Страница 40: ...4PW56033 1 Copyright Daikin...

Отзывы: