 Operation

E EKSRDS1A

Control and pump unit for solar systems

4PW56033-1

Operating and installation instructions

23

5.2.2 Contact for Solar Priority (BSK)

System considerations mean that hot water cannot be heated simultaneously with the solar system and the air-water heat pump.

For this reason, the contact for solar priority (BSK) is closed by the control system EKSR3PA when the solar panel circulation 
pump P

S

 is switched on. This transfers the signal that the solar system is active to the air-water heat pump via the cable 

connected to the printed circuit board A4P of the solar module EKRP1HBAA. The LED for the BSK contact (Item 7, Fig 5-1) lights 
up.

If the control system of the air-water heat pump is set to hot water generation with solar priority, the storage tank circuit pump 
in the solar connection kit EKSOLHWAV1 is switched on by this control system. At the same time, the hot water generation is 
blocked by the air-water heat pump.

5.2.3 Switch-on lock-out function

The switch-on lock-out function prevents:
– reactivation if the solar system has been automatically shutdown because the set maximum storage tank temperature 

"T

S

max" has been reached.

– pump operation if the solar panel temperature exceeds the value set by the heating expert with the parameter "T

K

zul". 

Under sustained solar radiation temperatures markedly in excess of 100 °C may occur at the solar panels after switching off the 
solar circuit pump. If the storage tank temperature falls below the release temperature ("T

S

max" – 2 K) in this situation (e.g. by 

removal of hot water), the solar circuit pump is switched on again when the cut-in switch protection temperature at the solar 
panels set with parameter "T

K

zul"  falls by 2 K. The T

K

 indicator flashes.

The function blocking time "Time SP" makes it possible, that, in the event of a switch-off condition caused by the flow sensor 
(FlowSensor), only after the blocking time (0 – 600 s) set in the solar control system has expired can the pumps be released again.

Therefore:
– cycling of the system can be minimised.
– the solar panels can reach a higher temperature.
– the feed temperature during filling the system does not fall below the cut-out condition and the system regulates itself faster.

5.2.4 Manual operation

The system can started manually with the time set in the parameter "H/A" for start-up and testing only. All control functions are 
disabled and the solar circuit pump runs continuously at the specified output independently of the system temperatures.

Pressing (>1 s) both arrow keys simultaneously activates or deactivates manual operation.

5.2.5 Solar FlowSensor EKSFLP12A

The optional FlowSensor is used to measure the flow "V" and the feed temperature "T

V

".

If a sensor is connected and activated:
– the measurement values "V" and "T

V

" are displayed.

– the control systems operate after the filling process with the actual system temperature difference of feed and return tem-

perature.

– if the speed of the solar circuit pump is regulated.
If the system has detected the FlowSensor once, a fault signal is shown if the sensor is faulty or disconnected (see section 6.1)
The system now operates in emergency mode without a FlowSensor.

The storage tank circulation pump is in the solar connection set EKSOLHWAV1. It is switched on with the air-
water heat pump when the contact BSK is closed and the solar priority is present (see Installation and Operat-
ing Instructions EKSOLHWAV1).

CAUTION!

Uncontrolled manual operation can lead to vapour pressure pulses, heat losses and excessively high storage 
tank temperatures.

To prevent vapour pressure pulses:

the solar panel temperature must be T

K

 < T

K

zul. Manual operation is blocked if T

K

 > T

K

zul and can 

only be started after sufficient cooling of the solar panels.

Содержание EKSR3PA

Страница 1: ...Control and pump unit for solar systems Control and pump unit for solar systems Operating and installation instructions English EKSR3PA EKSRDS1A Operating and installation instructions...

Страница 2: ......

Страница 3: ...on 10 3 1 System concepts 10 3 1 1 Parallel connection 10 3 1 2 Serial connection 10 3 2 Preparatory installation work 10 3 3 Pump unit EKSRDS1A 11 3 4 Controller EKSR3PA 12 3 4 1 Wall mounting 12 3 4...

Страница 4: ...st protection function 26 5 2 10 Leak protection function 26 5 3 Setting and menu operation 27 5 3 1 Start display 27 5 3 2 Operating display 28 5 3 3 Settings menu 28 5 3 4 Password input 30 5 3 5 La...

Страница 5: ...uctions Solar add on for air water heat pump system EKSOLHWAV1 Installation and operating instruction manual Process water for air water heat pump EKHWE EKHWS Installation instructions 1 2 Warning sig...

Страница 6: ...acturer This is the case for example with original spare parts 1 5 Instructions for operating safety Working on the roof Installation work on the roof may only be carried out by authorised and trained...

Страница 7: ...4 3 way diverter valve with drive motor 5 Heat distribution 6 Check valve I Double sided connection for 2 to 5 solar panels II Same side connection for max 3 solar panels not for in roof installation...

Страница 8: ...high degree of pre assembly ensure fast and simple installation Storage tank Only the hot water storage tanks EKHWE EKHWS can be used for the Daikin solar system Electronic control The fully electroni...

Страница 9: ...cessories Fig 2 3 Pump unit EKSRDS1A To connect the pump unit EKSRDS1A with the hot water storage tank EKHWE EKHWS Consists of Plate heat exchanger Circulation pump Fitting material Fig 2 4 Solar conn...

Страница 10: ...h both connections at one end max 3 solar panels 1 Solar panel connector 2 Mounting profile rail 3 Solar panel securing clip 4 Solar panel 5 Return connection solar panel 6 Flow connection solar panel...

Страница 11: ...formed and may damage the diaphragm expansion vessel MAG Always install the EKSRDS1A pump unit and the diaphragm expansion vessel MAG lower than the solar panels CAUTION Danger of scalding if incorrec...

Страница 12: ...accordance with EN 12828 The blow off line should be routed so that solar liquid can flow freely into a collection vessel when the safety valve is tripped The blow off line should be able to be block...

Страница 13: ...lug and connect the plug on the edge of the board of the control system to position TK 2 pole see Fig 3 10 6 Optional Connect the FlowSensor EKSFLP12A plug see Chapter 3 7 7 All the cables are routed...

Страница 14: ...F Programming socket for software updates FLS FlowSensor EKSFLP12A accessory TS Storage temperature sensor tS2 TR Return flow temperature sensor TK Solar panel temperature sensor BSK Connection cable...

Страница 15: ...tall cover on switch casing of solar panel circulation pump 4 Lay control line in casing of EKSRDS1A pump unit 5 Replace the external cover 1 on the pump unit EKSRDS1A 3 6 Storage temperature sensor F...

Страница 16: ...measurement range of the FlowSensor EKSFLP12A is between 0 and 12 l min flow volume and 0 to 120 C feed temperature The measured values are shown on the control unit EKSR3PA display The control system...

Страница 17: ...unlight or only if the solar panels are covered up WARNING If the heat transfer medium is mixed with other substances frost and corrosion protection may be reduced This may damage system components Co...

Страница 18: ...l circuit pressure to at least 0 3 bar above the pressure set at the diaphragm expansion vessel MAG see system fill pressure Tab 4 1 12 Close the upper KFE cock 13 Vent the system as follows Direct th...

Страница 19: ...Instructing the user owner 4 1 3 Filling the storage tank and heating circuit Filling the hot water storage tank see the associated installation and operating instructions Filling the heating system...

Страница 20: ...in the heating system that is shut down if there is danger of frost If there is a danger of frost for just a few days the unit s excellent heat insulation means that the insulated tank does not have t...

Страница 21: ...at pump that solar heat is available 8 Operating status indicator for PS solar panel circulation pump lights when pump is operating 9 Push arrow key up to switch the temperature or parameter display i...

Страница 22: ...put is regulated in dependence of the temperature difference between the solar feed and return flow temperature With a short delay Time PsE after switching on the solar circulation pump PS the contact...

Страница 23: ...me Time SP makes it possible that in the event of a switch off condition caused by the flow sensor FlowSensor only after the blocking time 0 600 s set in the solar control system has expired can the p...

Страница 24: ...ented after a safety time t2 Fig 5 4 If the pump output is too small the flow in the solar circuit can fall below the threshold value required to provide reliable data evaluation If the flow falls bel...

Страница 25: ...tart phase B Operating phase modulation C Flow stall D Low pump output stages are automatically blocked after flow stall V Flow in solar panel circuit V1 Minimum flow in start phase VS min V2 Minimum...

Страница 26: ...s or vapour formation in the solar circuit or a leak in the solar circuit To prevent the solar fluid from being pumped out of the system if there is a leak the pump PS is shutdown for 2 h and the faul...

Страница 27: ...ure sensor TV Flow temperature 0 to 100 C 1 K FlowSensor with voltage output 0 5 to 3 5 V V Flow 0 0 to 12 0 l min 0 1 l min FlowSensor 12 with voltage output 0 5 to 3 5 V Individual Designation Value...

Страница 28: ...briefly to confirm a selection open the next menu display or Saved is shown for approx 1 s if a value is changed In the required parameter display press OK to open parameter change mode In the menu F...

Страница 29: ...4PW56033 1 Operating and installation instructions 29 Fig 5 9 Settings menu ok ok ok ok Level 1 ok ok ok ok ok ok ok ok ok ok ok ok ok ok All incidents are deleted Correction values Flow l min 0 0 flo...

Страница 30: ...is entered in the menu path Selection 1 2 at Password 0000 It activates all important systems parameters in the settings menu for technicians see Fig 5 9 5 3 5 Language selection At initial start up...

Страница 31: ...1 K Flow correction 2 to 2 0 l min 1 l min Parameter Designation Access level Setting range Recommended setting range Factory setting Increment BE FA Delta T on Cut in temperature difference x x 1 80...

Страница 32: ...e tank circulation pump Time PsE so hot water is at the plate heat exchanger of the solar connection kit EKSOLHWAV1 until the tank circulation pump starts The maximum storage tank temperature TS max i...

Страница 33: ...ng instructions in the installation and operating instructions of the connection kit EKSOLHWAV1 5 4 3 Domestic water hygiene If no hot water is drawn off for several days and if the storage tank tempe...

Страница 34: ...the system All other sensor values can still be reached using the arrow keys Event code Plain text display Description Status display flashing Lamp flashing Consequence 0 Solar panel Solar panel senso...

Страница 35: ...of the solar connection kit EKSOLHWAV1 2 The fault signal W is shown in the left column of the solar control system display During the start procedure after expiry of time PsE and time UB the minimum...

Страница 36: ...In doing so observe the instructions in Chapter 4 Inbetriebnahme und Au erbetriebnahme Check the safety valve of the affected circuit for leaks c Increase the capacity of the pumps at the selector swi...

Страница 37: ...or PTC Feed temperature and flow sensor optional EKSFLP12A Pump unit EKSRDS1A Dimensions W x T x H 240 x 410 x 130 cm Operating voltage 230 V 50 Hz Solar panel circulation pump Grundfos Solar 25 65 13...

Страница 38: ...1116 1155 1194 1232 1270 1308 1347 1385 1423 1461 FlowSensor Sensor voltage in V according to manufacturer data TV 0 50 3 50 V 0 50 0 80 1 10 1 40 1 70 2 00 2 30 2 60 2 90 3 20 3 50 Flow rate Solar se...

Страница 39: ...circuit 11 13 Malfunction 34 35 Set values 19 38 Setting solar panel circuit 19 FlowSensor 9 16 19 23 27 31 34 37 38 Frost protection function 26 I Installation Connection pipes 11 Control unit 12 Flo...

Страница 40: ...4PW56033 1 Copyright Daikin...

Отзывы: