Page 34 

 

20/12/2017 - Version 1.0 

 

Parameter description 

Code 

U.M. 

Min 

Max 

Default 

Notes 

Delay in equipment start-up 

C0 

min 

240 

Compressor protections  

Delay as from last ON 

C1 

min 

240 

Delay as from last OFF 

C2 

min 

240 

Minimum ON time 

C3 

sec 

240 

Number of compressor operating hours 

required for maintenance  

C10 

9999 

1000 

0 = Function excluded 

Delay air temperature sample taking for cold 

evaporator test  

C11 

min 

999 

120 

 

Minimum delay between fan start-up and 

compressor activation for incoming air 
temperature check  

C12 

min 

240 

 

Timeout solar thermal cycle 

C13 

min 

240 

20 

 

Delay for damaged fan check 

C14 

min 

-1 

240 

20 

-1 = disabled function 

 

Type of defrosting 

d1 

---- 

0 = With heating element 

1 = With hot gas  

2 = With compressor 

stopped 

Evaporator temperature to conclude 

defrosting procedure (only if P4=1) 

d2 

°C/°F 

-50.0 

50.0 

3.0 

 

Maximum duration of defrosting procedure 

d3 

min 

99 

 

Automatic defrosting start threshold 

(evaporator temperature) 

d17 

°C/°F 

-50.0 

50.0 

-2.0 

 

Minimum compressor start up time to start 

defrosting procedure 

d18 

min 

240 

60 

 

 

Minimum level thermistor alarm (only AL1 

warning) 

A0 

---- 

0 = Upper thermistor 

1 = Lower thermistor 

2 = Evaporator thermistor 

Minimum alarm set (only AL1 warning) 

A1 

°C/°F 

0.0 

50.0 

10.0 

 

Type of minimum level alarm delay (only AL1 

warning) 

A2 

---- 

0 = Disabled 

1 = Absolute 

Maximum level thermistor alarm (only AH 

warning) 

A3 

---- 

0 = Upper thermistor 

1 = Lower thermistor 

2 = Evaporator thermistor 

Maximum alarm set(only AH warning) 

A4 

°C/°F 

0.0 

199.0 

90.0 

 

Type of maximum level alarm delay (only AH 

warning) 

A5 

---- 

0 = Disabled 

1 = Absolute 

Minimum level AL1 alarm delay due to 

equipment start-up (only warning) 

A6 

min 

240 

120 

 

AL1 and AH temperature alarm delays (only 

warning) 

A7 

min 

240 

15 

 

Alarm hysteresis 

A11 

min 

0.1 

30.0 

2.0 

 

 

Heating element start-up interval (Anti-

Legionella) 

H0 

days 

99 

30 

 

Anti-Legionella function set 

H1 

°C/°F 

10.0 

199.0 

60.0 

 

Duration of Anti-Legionella function  

H3 

min 

240 

 

Содержание EKHH2E200AAV3

Страница 1: ...nstallation manual Domestic Hot Water Heat Pump Monobloc type English Language Language Language Language Language Installation manual Domestic Hot Water Heat Pump Monobloc type EKHH2E200AAV3 3 EKHH2E...

Страница 2: ...ental safety rules 16 5 6 Information on coolant used 16 6 Installation and connections 17 6 1 Preparation of the installation site 17 6 2 Ventilation connection 17 6 2 1 Particular installation condi...

Страница 3: ...Version Log Version code Description Date 4P509215 1 Document release 20 12 2017...

Страница 4: ...Page 4 20 12 2017 Version 1 0...

Страница 5: ...tion see the installer and user reference guide 1 2 For the user If you are not sure how to operate the unit contact yourinstaller This appliance can be used by children aged 8 years or older and by p...

Страница 6: ...r equipment on top of the unit Do NOT sit climb or stand on the unit NOTICE Works executed on the outdoor unit are preferably carried out under dry weather conditions to avoid water ingress In accorda...

Страница 7: ...he specified amount of refrigerant When the refrigerant system needs to be opened refrigerant must be treated according to the applicable legislation WARNING Make sure there is no oxygen in the system...

Страница 8: ...orber or telephone earth Incomplete earth may cause electrical shock Make sure to use a dedicated power circuit NEVER use a power supply shared by another appliance Make sure to install the required f...

Страница 9: ...ction manual designed for a certain unit or application explaining how to install configure and maintain it Operation manual Instruction manual designed for a certain unit or application explaining ho...

Страница 10: ...ures drawings or descriptions without prejudice to errors of any kind The Supplier shall not be held responsible for damages attributable to misuse improper use or as a consequence of unauthorised rep...

Страница 11: ...on EKHH2E200AAV3 3 EKHH2E260AAV3 3 Air source heat pump for the production of domestic hot water EKHH2E260PAAV3 3 Air source heat pump for the production of domestic hot water suitable for use with th...

Страница 12: ...WARNING The equipment can be transported horizontally only during the last km following the instructions in the section Positions permitted for transporting and handling above and taking care of posit...

Страница 13: ...pressor 14 Replaceable magnesium anode 15 1 5 kW 230 W Electric heating element 16 Condenser pump discharge line 17 Condenser return 18 Replaceable magnesium anode 19 Hot water outlet connection joint...

Страница 14: ...5 1 5 Maximum current in HP A 2 4 2 4 2 4 Required overload protections A 16A T fuse 16A automatic switch characteristic C to be expected during installation on power supply systems Internal protectio...

Страница 15: ...0 mm 1 x Mg anode 26x400 mm Insulation 50 mm high density polyurethane foam Defrosting Active with Hot Gas valve Dimensions mm H1714xD600xDmax650 H2000xD600xDmax650 H2000xD600xDmax650 Transport weight...

Страница 16: ...g system with alarm functions in order to avoid such damage being caused Moreover it is necessary to arrange for a back up service in case of failure 5 4 Operating limits The above mentioned device is...

Страница 17: ...ailable and ready with adequate discharge pipes in case of damage caused to the boiler or actuation of the safety valve or breakage of pipes connections Have containment systems in case of serious wat...

Страница 18: ...discharge pipe conveying air to the outside with the goal of preventing foreign bodies from entering the equipment In order to guarantee maximum device performance the grid must ensure low pressure l...

Страница 19: ...arge pipe directs the air flow either towards the inside Fig 5a or the outside of the home Fig 5b Fig 5a Example of installation in summer Fig 5b Example of installation in winter 6 3 Device mounting...

Страница 20: ...water supply connection Fig 8 Example of the water supply system Fig 8a Example of heavy series safety valve N B It is compulsory to install a dirt filter on the cold water inlet pipe The equipment do...

Страница 21: ...ce Fig 8a WARNING In case an expansion vessel is not being installed make sure that there s no non return valve installed in the cold water intake WARNING The heat pump for the production of domestic...

Страница 22: ...41 Fig 11 A Schuko socket Fig 12 Equipment plug 6 6 1 Remote links The equipment is designed in such a way that it can be connected to other remote energy systems photovoltaic and solar thermal power...

Страница 23: ...re an example of a remote link Fig 13 Example of a remote link Fig 13a Detailed example of a remote link The upper cover of the boiler needs to be removed in order to access the 4 core cable for remot...

Страница 24: ...er inlet tap and check for any leaks from gaskets and connections Tighten the bolts or connections if necessary Do not exceed the maximum permitted pressure indicated in the general technical data sec...

Страница 25: ...instrument can automatically switch on at certain time slots and independently enables the anti Legionella and defrosting functions When the equipment is switched on it shows the status it was previou...

Страница 26: ...s automatically disabled and the equipment is automatically restored to the Automatic or Economy mode depending on which one was previously set by the user ANTI LEGIONELLA operating mode This function...

Страница 27: ...ure that no other advanced procedures are in progress Press and hold the and the keys until Loc will appear on the display for 1 second If the keyboard is locked it will be impossible to carry out any...

Страница 28: ...malfunctions caused by users 8 1 3 7 Display of the operating status Make sure that the keyboard is not locked paragraph 8 1 3 3 and that no other advanced procedures are in progress Press and releas...

Страница 29: ...f the equipment and restart it or disconnect the equipment from the mains power supply Main consequences Compressor will be switched off Defrosting will be never activated FiL Ventilation filter check...

Страница 30: ...oard is not locked paragraph 8 1 3 3 and that no other advanced procedures are in progress Press and release the key the first available code will appear on the display Press and release either the or...

Страница 31: ...he and keys for 4 seconds PA password will appear on the screen Press and release the key Press and release either the or the key within the next 15 seconds to set 149 Press and release the key or do...

Страница 32: ...equently lead to breakdown of the equipment At every Start up the fan is activated for an amount of time set by parameter C12 1 minute After this amount of time the system measures the incoming air te...

Страница 33: ...3 C F 25 0 25 0 0 0 Thermistor type P0 0 1 1 0 PTC 1 NTC 2 PT1000 Decimal point P1 0 1 1 1 Display decimal point per temperature Unit of measurement P2 0 1 0 0 C 1 F Function associated with the evapo...

Страница 34: ...osting procedure d3 min 0 99 8 Automatic defrosting start threshold evaporator temperature d17 C F 50 0 50 0 2 0 Minimum compressor start up time to start defrosting procedure d18 min 0 240 60 Minimum...

Страница 35: ...1 Buzzer enabled Switching on time for Monday Hd1 1 2 1 1 HOn1 HOF1 2 HOn2 HOF2 Switching on time for Tuesday Hd2 1 2 1 1 HOn1 HOF1 2 HOn2 HOF2 Switching on time for Wednesday Hd3 1 2 1 1 HOn1 HOF1 2...

Страница 36: ...Page 36 20 12 2017 Version 1 0 Parameter description Code U M Min Max Default Notes RESERVED E9 0 2 0...

Страница 37: ...the mains power supply Remove any air ducts see paragraph 6 2 Remove the upper cover by undoing the appropriate locking screws Fig 18 Manually reset the tripped safety thermostat from the top Fig 19 I...

Страница 38: ...n comparison to the material that coates the inside of the boiler It therefore attracts the negative charges that are formed during the heating of the water and would cause the boiler to corrode The a...

Страница 39: ...ins greenhouse fluorinated gas included in the Kyoto protocol The maintenance and disposal operations must only be carried out by qualified personnel INFORMATION TO USERS Pursuant to Directives 2011 6...

Страница 40: ...he water heater C 55 Sound power level Lwa indoors in dB dB 53 The water heater is able to work only during off peak hours NO Any specific precautions that shall be taken when the water heater is asse...

Страница 41: ......

Страница 42: ...Page 42 20 12 2017 Version 1 0 Nov 17...

Отзывы: