Fig. 1 

– Operating principle 

 

 

The operating principle of the equipment (Fig. 1): 

I-II: 

The coolant fluid sucked in by the compressor flows 

inside the evaporator and while it evaporates, it 
absorbs the “ecological” heat given by the air. 

At the same time, the ambient air is sucked into the 

equipment by a fan; the air loses its heat by 
passing over the finned-tube battery of the 
evaporator; 

II-III: 

The coolant gas passes through the compressor 

and it undergoes an increase in pressure that 
causes the temperature to rise; transforming the 
gas into superheated steam; 

III-IV: 

Inside the condenser, the coolant gas releases its 

heat to the water inside the tank (boiler). This 
exchange process enables the coolant to transform 
from superheated steam into a liquid by 
condensing at a constant pressure and undergoing 
a lowering in temperature; 

IV-I: 

The liquid coolant passes through the lamination 

valve, it undergoes a sudden drop in both pressure 
and temperature and it partially evaporates 
bringing pressure and temperature back to its initial 
conditions. The thermodynamic cycle can begin. 

2.5 

Available versions and 
configurations 

The heat pump is available as a 1.9 kW, which can be 

set up in different configurations, depending on the 
possible integrations with other heating sources 
(e.g. solar thermal, biomass power, etc.).  

Version 

Configuration description 

EKHH2E200AAV3(3) 

EKHH2E260AAV3(3) 

 

Air source heat pump for 

the production of 
domestic hot water 

EKHH2E260PAAV3(3) 

 

Air source heat pump for 

the production of 
domestic hot water 
suitable for use with 
the solar power 
system.  

Handling and transport 

The equipment is supplied in a cardboard box. It is 

fastened to a pallet with three screws. 

 

Use a fork-lift truck or a pallet truck in order to unload 

the equipment: it is opportune for these to have a 
load capacity of at least 250 Kg. 

In order to loosen the 

fixing screws more 
easily, you can put 
the packaged 
equipment on a 
horizontal position 
on its back side. 

The unpacking 

operations must be 
carried out carefully 
to not damage the 
equipment 
enclosure, if the 
unpacking is 
carried out with 
knives or cutters to 
open the cardboard 
packaging. 

After having removed the packaging, check whether the 

unit is intact. If in doubt, do not use the equipment 
and seek help from authorised technical staff. 

In conformity with the environmental protection 

regulations, you should make sure that all 
accessories supplied have been removed before 
discarding the packaging. 

 

WARNING!

 

 

Packaging items (staples, cardboard boxed, etc.) 

should not be left within reach of children, as 
this can lead to dangerous situations. 

(*) Note: at Daikin’s discretion, the type of packaging 

may be subject to change. 

It is opportune to protect the equipment from 

atmospheric agents as long as it remains idle, 
waiting to be used. 

Ecological heat 

Condenser 

 

Air

 

Evaporator 

 

Compressor 

 

Lamination 

valve 

 

Tank 

 

Cold water  

 

Hot water 

 

Electric heat  

Содержание EKHH2E200AAV3

Страница 1: ...nstallation manual Domestic Hot Water Heat Pump Monobloc type English Language Language Language Language Language Installation manual Domestic Hot Water Heat Pump Monobloc type EKHH2E200AAV3 3 EKHH2E...

Страница 2: ...ental safety rules 16 5 6 Information on coolant used 16 6 Installation and connections 17 6 1 Preparation of the installation site 17 6 2 Ventilation connection 17 6 2 1 Particular installation condi...

Страница 3: ...Version Log Version code Description Date 4P509215 1 Document release 20 12 2017...

Страница 4: ...Page 4 20 12 2017 Version 1 0...

Страница 5: ...tion see the installer and user reference guide 1 2 For the user If you are not sure how to operate the unit contact yourinstaller This appliance can be used by children aged 8 years or older and by p...

Страница 6: ...r equipment on top of the unit Do NOT sit climb or stand on the unit NOTICE Works executed on the outdoor unit are preferably carried out under dry weather conditions to avoid water ingress In accorda...

Страница 7: ...he specified amount of refrigerant When the refrigerant system needs to be opened refrigerant must be treated according to the applicable legislation WARNING Make sure there is no oxygen in the system...

Страница 8: ...orber or telephone earth Incomplete earth may cause electrical shock Make sure to use a dedicated power circuit NEVER use a power supply shared by another appliance Make sure to install the required f...

Страница 9: ...ction manual designed for a certain unit or application explaining how to install configure and maintain it Operation manual Instruction manual designed for a certain unit or application explaining ho...

Страница 10: ...ures drawings or descriptions without prejudice to errors of any kind The Supplier shall not be held responsible for damages attributable to misuse improper use or as a consequence of unauthorised rep...

Страница 11: ...on EKHH2E200AAV3 3 EKHH2E260AAV3 3 Air source heat pump for the production of domestic hot water EKHH2E260PAAV3 3 Air source heat pump for the production of domestic hot water suitable for use with th...

Страница 12: ...WARNING The equipment can be transported horizontally only during the last km following the instructions in the section Positions permitted for transporting and handling above and taking care of posit...

Страница 13: ...pressor 14 Replaceable magnesium anode 15 1 5 kW 230 W Electric heating element 16 Condenser pump discharge line 17 Condenser return 18 Replaceable magnesium anode 19 Hot water outlet connection joint...

Страница 14: ...5 1 5 Maximum current in HP A 2 4 2 4 2 4 Required overload protections A 16A T fuse 16A automatic switch characteristic C to be expected during installation on power supply systems Internal protectio...

Страница 15: ...0 mm 1 x Mg anode 26x400 mm Insulation 50 mm high density polyurethane foam Defrosting Active with Hot Gas valve Dimensions mm H1714xD600xDmax650 H2000xD600xDmax650 H2000xD600xDmax650 Transport weight...

Страница 16: ...g system with alarm functions in order to avoid such damage being caused Moreover it is necessary to arrange for a back up service in case of failure 5 4 Operating limits The above mentioned device is...

Страница 17: ...ailable and ready with adequate discharge pipes in case of damage caused to the boiler or actuation of the safety valve or breakage of pipes connections Have containment systems in case of serious wat...

Страница 18: ...discharge pipe conveying air to the outside with the goal of preventing foreign bodies from entering the equipment In order to guarantee maximum device performance the grid must ensure low pressure l...

Страница 19: ...arge pipe directs the air flow either towards the inside Fig 5a or the outside of the home Fig 5b Fig 5a Example of installation in summer Fig 5b Example of installation in winter 6 3 Device mounting...

Страница 20: ...water supply connection Fig 8 Example of the water supply system Fig 8a Example of heavy series safety valve N B It is compulsory to install a dirt filter on the cold water inlet pipe The equipment do...

Страница 21: ...ce Fig 8a WARNING In case an expansion vessel is not being installed make sure that there s no non return valve installed in the cold water intake WARNING The heat pump for the production of domestic...

Страница 22: ...41 Fig 11 A Schuko socket Fig 12 Equipment plug 6 6 1 Remote links The equipment is designed in such a way that it can be connected to other remote energy systems photovoltaic and solar thermal power...

Страница 23: ...re an example of a remote link Fig 13 Example of a remote link Fig 13a Detailed example of a remote link The upper cover of the boiler needs to be removed in order to access the 4 core cable for remot...

Страница 24: ...er inlet tap and check for any leaks from gaskets and connections Tighten the bolts or connections if necessary Do not exceed the maximum permitted pressure indicated in the general technical data sec...

Страница 25: ...instrument can automatically switch on at certain time slots and independently enables the anti Legionella and defrosting functions When the equipment is switched on it shows the status it was previou...

Страница 26: ...s automatically disabled and the equipment is automatically restored to the Automatic or Economy mode depending on which one was previously set by the user ANTI LEGIONELLA operating mode This function...

Страница 27: ...ure that no other advanced procedures are in progress Press and hold the and the keys until Loc will appear on the display for 1 second If the keyboard is locked it will be impossible to carry out any...

Страница 28: ...malfunctions caused by users 8 1 3 7 Display of the operating status Make sure that the keyboard is not locked paragraph 8 1 3 3 and that no other advanced procedures are in progress Press and releas...

Страница 29: ...f the equipment and restart it or disconnect the equipment from the mains power supply Main consequences Compressor will be switched off Defrosting will be never activated FiL Ventilation filter check...

Страница 30: ...oard is not locked paragraph 8 1 3 3 and that no other advanced procedures are in progress Press and release the key the first available code will appear on the display Press and release either the or...

Страница 31: ...he and keys for 4 seconds PA password will appear on the screen Press and release the key Press and release either the or the key within the next 15 seconds to set 149 Press and release the key or do...

Страница 32: ...equently lead to breakdown of the equipment At every Start up the fan is activated for an amount of time set by parameter C12 1 minute After this amount of time the system measures the incoming air te...

Страница 33: ...3 C F 25 0 25 0 0 0 Thermistor type P0 0 1 1 0 PTC 1 NTC 2 PT1000 Decimal point P1 0 1 1 1 Display decimal point per temperature Unit of measurement P2 0 1 0 0 C 1 F Function associated with the evapo...

Страница 34: ...osting procedure d3 min 0 99 8 Automatic defrosting start threshold evaporator temperature d17 C F 50 0 50 0 2 0 Minimum compressor start up time to start defrosting procedure d18 min 0 240 60 Minimum...

Страница 35: ...1 Buzzer enabled Switching on time for Monday Hd1 1 2 1 1 HOn1 HOF1 2 HOn2 HOF2 Switching on time for Tuesday Hd2 1 2 1 1 HOn1 HOF1 2 HOn2 HOF2 Switching on time for Wednesday Hd3 1 2 1 1 HOn1 HOF1 2...

Страница 36: ...Page 36 20 12 2017 Version 1 0 Parameter description Code U M Min Max Default Notes RESERVED E9 0 2 0...

Страница 37: ...the mains power supply Remove any air ducts see paragraph 6 2 Remove the upper cover by undoing the appropriate locking screws Fig 18 Manually reset the tripped safety thermostat from the top Fig 19 I...

Страница 38: ...n comparison to the material that coates the inside of the boiler It therefore attracts the negative charges that are formed during the heating of the water and would cause the boiler to corrode The a...

Страница 39: ...ins greenhouse fluorinated gas included in the Kyoto protocol The maintenance and disposal operations must only be carried out by qualified personnel INFORMATION TO USERS Pursuant to Directives 2011 6...

Страница 40: ...he water heater C 55 Sound power level Lwa indoors in dB dB 53 The water heater is able to work only during off peak hours NO Any specific precautions that shall be taken when the water heater is asse...

Страница 41: ......

Страница 42: ...Page 42 20 12 2017 Version 1 0 Nov 17...

Отзывы: