10
|
Configuration
Installer reference guide
143
ERLA EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1B – 2021.10
#
Code
Description
N/A
[8-02]
Anti-recycling time.
Minimum time between two cycles for domestic
hot water.
Range: 0~10 hours
Remark:
The minimum time is 0.5 hours even
when the selected value is 0.
[8-02]: Anti-recycling time
t
1
0
1
0
[8-01]
[8-02]
[8-00]
1
Heat pump domestic hot water heating mode (1=active, 0=not active)
2
Hot water request for heat pump (1=request, 0=no request)
t
Time
Disinfection
Applies only to installations with a domestic hot water tank.
The disinfection function disinfects the domestic hot water tank by periodically
heating the domestic hot water to a specific temperature.
CAUTION
The disinfection function settings MUST be configured by the installer according to
the applicable legislation.
#
Code
Description
[A.4.4.1]
[2‑01]
Disinfection
▪
0:
No
▪
1:
Yes
[A.4.4.2]
[2‑00]
Operation day
:
▪
0:
Each day
▪
1:
Monday
▪
2:
Tuesday
▪
3:
Wednesday
▪
4:
Thursday
▪
5:
Friday
▪
6:
Saturday
▪
7:
Sunday
[A.4.4.3]
[2‑02]
Start time
: 00~23:00, step: 1:00.
[A.4.4.4]
[2‑03]
Temperature target
: fixed value
[A.4.4.5]
[2‑04]
Duration
Range: 40~60 minutes