Commissioning
Installer reference guide
160
ERLA EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1B – 2021.10
There is NO
water leak
inside the indoor unit.
The
shut-off valves
are properly installed and fully open.
The
stop valves
(gas and liquid) on the outdoor unit are fully open.
The
air purge
valve is open (at least 2 turns).
The
pressure relief valve
purges water when opened. Clean water MUST come out.
The
minimum water volume
is guaranteed in all conditions. See "To check the water
The
domestic hot water tank
is filled completely.
11.4 Checklist during commissioning
The
minimum flow rate
during backup heater/defrost operation is guaranteed in all
conditions. See "To check the water volume and flow rate" in
To perform an
air purge
.
To perform a
test run
.
To perform an
actuator test run
.
Underfloor screed dryout function
The underfloor screed dryout function is started (if necessary).
11.4.1 To check the minimum flow rate
Mandatory procedure for the additional zone
1
Confirm according to the hydraulic configuration which space heating loops
can be closed due to mechanical, electronic, or other valves.
2
Close all space heating loops that can be closed (see previous step).
3
Start the pump test run operation (see
"11.4.4 To perform an actuator test
4
Go to [6.1.8]: >
Information
>
Sensor information
>
Flow rate
to
check the flow rate. During pump test run operation, the unit can operate
below this minimum required flow rate that is needed during defrost/backup
heater operation.
Recommended procedure for the main zone
5
Confirm according to the hydraulic configuration which space heating loops
can be closed due to mechanical, electronic, or other valves.
6
Close all space heating loops that can be closed (see previous step).
7
Create a thermo request on the main zone only.
8
Wait 1 minute until the unit is stabilized.
9
If the additional pump is still assisting (the green LED on the right hand sided
pump is ON), increase the flow until the additional pump is NOT assisting
anymore (LED is OFF).
10
Go to [6.1.8]: >
Information
>
Sensor information
>
Flow rate
to
check the flow rate.