10
|
Configuration
Installer reference guide
122
ERLA EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1B – 2021.10
Demand PCB
The demand PCB is used to enable the power consumption control by digital
inputs. See
31].
#
Code
Description
N/A
[D-04]
Demand PCB
Indicates if the optional demand PCB is installed.
▪
0 (
No
)
▪
1 (
Pwr consmp ctrl
)
Energy metering
When energy metering is performed by the use of external power meters,
configure the settings as described below. Select the pulse frequency output of
each power meter in accordance with the power meter specifications. It is possible
to connect (up to 2) power meters with different pulse frequencies. When only 1
or no power meter is used, select
No
to indicate the corresponding pulse input is
NOT used.
#
Code
Description
N/A
[D‑08]
Optional external kWh meter 1:
▪
0 (
No
): NOT installed
▪
1: Installed (0.1
pulse/kWh
)
▪
2: Installed (1
pulse/kWh
)
▪
3: Installed (10
pulse/kWh
)
▪
4: Installed (100
pulse/kWh
)
▪
5: Installed (1000
pulse/kWh
)
N/A
[D‑09]
Optional external kWh meter 2:
▪
0 (
No
): NOT installed
▪
1: Installed (0.1
pulse/kWh
)
▪
2: Installed (1
pulse/kWh
)
▪
3: Installed (10
pulse/kWh
)
▪
4: Installed (100
pulse/kWh
)
▪
5: Installed (1000
pulse/kWh
)