11
|
Commissioning
Installer reference guide
162
ERLA EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1B – 2021.10
2
Set the air purge mode: go to [A.7.3.1]
>
Installer settings
>
Commissioning
>
Air purge
>
Type
.
3
Select
Manual
and press .
4
Go to [A.7.3.4]
>
Installer settings
>
Commissioning
>
Air
purge
>
Start air purge
and press to start the air purge function.
Result:
The manual air purge starts and the following screen appears.
5
Use the and buttons to set the desired pump speed.
Result:
Low
Result:
High
To perform an automatic air purge
INFORMATION
When purging the main zone, make sure the setpoint for the main zone is at least
5°C higher than the actual water temperature inside the unit.
Prerequisite:
Make sure that the leaving water temperature home page, room
temperature home page, and domestic hot water home page are turned OFF.
1
Set the user permission level to Installer. See
"To set the user permission level
111].
2
Set the air purge mode: go to [A.7.3.1]
>
Installer settings
>
Commissioning
>
Air purge
>
Type
.
3
Select
Automatic
and press .
4
Go to [A.7.3.4]
>
Installer settings
>
Commissioning
>
Air
purge
>
Start air purge
and press to start the air purge function.
Result:
Air purging will start and the following screen will be shown.
11.4.3 To perform a test run
INFORMATION
The test run only applies to the additional temperature zone.
Prerequisite:
Make sure that the leaving water temperature home page, room
temperature home page, and domestic hot water home page are turned OFF.
1
Set the user permission level to Installer. See
"To set the user permission level
111].
2
Go to [A.7.1]: >
Installer settings
>
Commissioning
>
Test run
.
3
Select a test and press .
Example:
Heating
.
4
Select
OK
and press .
Result:
The test run starts. It stops automatically when done (±30 min). To stop it
manually, press , select
OK
and press .
INFORMATION
If 2 user interfaces are present, you can start a test run from both user interfaces.
▪
The user interface used to start the test run displays a status screen.
▪
The other user interface displays a "busy" screen. You cannot use the user
interface as long as the "busy" screen is shown.