4 Installation
Installation manual
11
EGSQH10S18AA9W
Daikin Altherma ground source heat pump
4P351747-1F – 2016.06
2
Fix the cable with cable ties to the cable tie mountings.
INFORMATION
In case of preferential kWh rate power supply, connect
X6Y to X6YB. The necessity of separate normal kWh rate
power supply to indoor unit (b) X2M30/31 depends on the
type of preferential kWh rate power supply.
Separate connection to the indoor unit is required:
▪ if preferential kWh rate power supply is interrupted
when active, OR
▪ if no power consumption of the indoor unit is allowed at
the preferential kWh rate power supply when active.
INFORMATION
The preferential kWh rate power supply contact is
connected to the same terminals (X5M/3+4) as the safety
thermostat. It is only possible for the system to have
EITHER preferential kWh rate power supply OR a safety
thermostat.
4.5.4
To connect the remote outdoor sensor
The remote outdoor sensor (delivered as accessory) measures the
outdoor ambient temperature.
INFORMATION
If the desired leaving water temperature is weather
dependent, the full time outdoor temperature measurement
is important.
1
Connect the external temperature sensor cable to the indoor
unit.
X2M
X5M
11
10
12
2
Fix the cable with cable ties to the cable tie mountings.
3
Install the remote outdoor sensor outside as described in the
installation manual of the sensor (delivered as accessory).
4.5.5
To connect the user interface
▪ If you use 1 user interface, you can install it at the indoor unit (for
control close to the indoor unit), or in the room (when used as
room thermostat).
▪ If you use 2 user interfaces, you can install 1 user interface at the
indoor unit (for control close to the indoor unit) + 1 user interface
in the room (used as room thermostat).
The procedure differs slightly depending on where you install the
user interface.
#
At the indoor unit
In the room
1
Connect the user interface cable to the indoor unit.
Fix the cable with cable ties to the cable tie mountings.
X2M
X5M
a
b
1 2
a
Main user interface
(a)
b
Optional user interface
2
Insert a screwdriver into the slots underneath the user
interface and carefully separate the faceplate from the
wallplate.
The PCB is mounted in the faceplate of the user interface.
Be careful NOT to damage it.
3
Use the 2 screws in the accessory
bag to fix the wallplate of the user
interface to the sheet metal of the
unit.
Be careful NOT to distort the shape
of the backside of the user interface
by overtightening the mounting
screws.
Fix the wallplate of
the user interface to
the wall.
4
Connect as shown in 4A.
Connect as shown
in 4A, 4B, 4C or 4D.
5
Reinstall the faceplate onto the wallplate.
Be careful NOT to pinch the wiring when attaching the
frontplate to the unit.
(a)
The main user interface is required for operation, but has to
be ordered separately (mandatory option).
4A From the rear
b
a
PCB
1×
4B From the left
a
PCB
b
1×