5 Configuration
Installation manual
16
EGSQH10S18AA9W
Daikin Altherma ground source heat pump
4P351747-1F – 2016.06
#
Code
Description
[A.2.2.A]
[D-02]
DHW pump:
▪ 0 (No)(default): NOT installed
▪ 1 (Secondary rtrn): Installed for instant
hot water
▪ 2
(Disinf.
shunt):
Installed
for
disinfection
See also illustrations below.
Domestic hot water pump installed for…
Instant hot water
Disinfection
c
f
b
a
g
c
b
a
d f
e g
a
Indoor unit
b
Tank
c
Domestic hot water pump
d
Heater element
e
Non‑return valve
f
Shower
g
Cold water
Thermostats and external sensors
NOTICE
If an external room thermostat is used, the external room
thermostat will control the room frost protection. However,
the room frost protection is only possible if the leaving
water temperature control on the unit's user interface is
turned ON.
#
Code
Description
[A.2.2.4]
[C-05]
External room thermostat for the
main
zone:
▪ 1 (Thermo ON/OFF): When the used
external
room
thermostat
or
heat pump convector can only send a
thermo ON/OFF condition.
▪ 2 (H/C request): Because only heating
is possible, the used external room
thermostat can only send a thermo
ON/OFF condition.
[A.2.2.5]
[C-06]
External room thermostat for the
additional
zone:
▪ 0: N/A
▪ 1 (Thermo ON/OFF): When the used
external
room
thermostat
or
heat pump convector can only send a
thermo ON/OFF condition.
▪ 2 (H/C request): Because only heating
is possible, the used external room
thermostat can only send a thermo
ON/OFF condition.
[A.2.2.B]
[C-08]
External sensor:
▪ 0 (No)(default): NOT installed.
▪ 2 (Room sensor): Connected to PCB
measuring the indoor temperature.
Digital I/O PCB
#
Code
Description
[A.2.2.6.1]
[C-02]
External backup heater source:
▪ 0 (No)(default): None
▪ 1 (Bivalent): Gas, oil boiler
#
Code
Description
[A.2.2.6.3]
[C-09]
Alarm output on optional EKRP1HB
PCB:
▪ 0 (Normally open)(default): The
alarm output will be powered when
an alarm occurs.
▪ 1 (Normally closed): The alarm
output will NOT be powered when an
alarm occurs. This installer setting
allows distinction between detection
of an alarm and detection of a power
failure to the unit.
See also table below (Alarm output
logic).
Alarm output logic
[C-09]
Alarm
No alarm
No power
supply to unit
0 (default)
Closed output
Open output
Open output
1
Open output
Closed output
Demand PCB
#
Code
Description
[A.2.2.7]
[D-04]
Demand PCB
Indicates if the optional demand PCB is
installed.
▪ 0 (No)
▪ 1 (Pwr consmp ctrl)
Energy metering
#
Code
Description
[A.2.2.8]
[D‑08]
Optional external kWh meter 1:
▪ 0 (No): NOT installed
▪ 1: Installed (0.1 pulse/kWh)
▪ 2: Installed (1 pulse/kWh)
▪ 3: Installed (10 pulse/kWh)
▪ 4: Installed (100 pulse/kWh)
▪ 5: Installed (1000 pulse/kWh)
[A.2.2.9]
[D‑09]
Optional external kWh meter 2:
▪ 0 (No): NOT installed
▪ 1: Installed (0.1 pulse/kWh)
▪ 2: Installed (1 pulse/kWh)
▪ 3: Installed (10 pulse/kWh)
▪ 4: Installed (100 pulse/kWh)
▪ 5: Installed (1000 pulse/kWh)
5.2.4
Quick wizard: Capacities (energy
metering)
#
Code
Description
[A.2.3.2]
[6‑03]
Capacity of the first step of the backup
heater at nominal voltage [kW]
[A.2.3.3]
[6‑04]
Capacity difference between the second
and first step of the backup heater [kW]