Electric heater kit
4PW17553-3
Installation manual
2
Notes on installation
Each unit requires a switch (IL) on the power supply line with a distance
of at least 3 mm between the opening contacts, and a suitable safety
fuse (F).
The minimum wire section of the power cables are specified in the
table below:
Model
FW01
FW02~06
FW08~10
Gauge of power cables (mm
2
)
1.5
2.5
4
To guarantee the efficiency of a unit equipped with a supplementary
EEH heating element, comply with the following directions:
n
On completing installation, make sure that the minimum airflow is
guaranteed.
Model
Minimum air flow rate
(m
3
/h)
FW01
196
FW02+15
232
FW03+25
265
FW04+35
397
FW06
517
FW08
627
FW10
706
The maximum temperature of air intake into the unit is 25°C.
n
Check the airflow rate periodically.
n
Do not obstruct the air outlet or inlet of the unit in any way.
n
Do not place damp or wet clothing on the air outlet grille of the unit
n
Do not turn off the unit using switch IL or by cutting off power to
the entire electric system. This would disable the post-ventilation
function and thus the air and components in the vicinity of the
heating element would risk overheating. Always use the
controllers to switch off the unit.
n
Keep the air filter clean.
n
Do not pour liquids inside the equipment.
O
pEraTiON
Refer to the manual of the controller.