NOTE) For Patterns 1 and 2
• Wall height for front side no higher than 1500 mm.
• Wall height on the suction side no higher than 500 mm.
• Wall height for sides – no limit
• If the height is exceeded the above, calculate h1 and h2 shown
in the figure on next page, and add h1/2 to the service space
of front side and h2/2 to the service space of suction side.
CAUTION
1.
An inverter CONVENI-PACK may cause electronic noise gener-
ated from AM broadcasting. Examine where to install the main
CONVENI-PACK and electric wires, keeping proper distances
away from stereo equipment, personal computers, etc.
Particularly for locations with weak reception, ensure there is a
distance of at least 3 meters for indoor remote controllers, place
power wiring and transmission wiring in conduits, and ground the
conduits.
2.
When installing in a locations where there is heavy snowfall,
implement the following snow measures.
• Ensure the base is high enough that intakes are not clogged
by snow.
• Mount a snow protection hood (optional accessory)
• Remove the rear intake grille to prevent snow from accumulat-
ing on the fins.
3.
If condensate may drip on downstairs (or walkway) depending on
the floor condition, take a measure such as the installation of cen-
tral drain pan kit (sold separately).
4.
The refrigerant R410A itself is nontoxic, nonflammable and is
safe. If the refrigerant should leak however, its concentration may
exceed the allowable limit depending on room size. Due to this it
could be necessary to take measures against leakage.
See “Engineering Data” for details.
4.
HANDLING THE UNIT
1.
Decide on the transportation route.
2.
If a forklift is to be used, pass the forklift arms through the large
openings on the bottom of the unit.
1
Opening (large)
2
Fork
3
Fixed screws of transportation clasp
4
Transportation clasp (yellow)
If hanging the unit, use a cloth sling to prevent damaging the unit.
Keeping the following points in mind, hang the unit following the
procedure shown in the following figure.
• Use a sling sufficiently strong to hold the mass of the unit.
• Use 2 belts of at least 8m long.
• Place extra cloth in the locations where the casing comes in
contact with the sling to prevent damage.
• Hoist the unit making sure it is being lifted at its center of gravity.
1
Belt sling
2
Patch cloth
3
Belt sling
4
Patch cloth
5
Opening
3.
After installation, remove the transportation clasp (yellow)
attached to the large openings.
Note
Apply a filler cloth on a fork to prevent coating of the bottom frame
from coming off and rust from occurring when bringing in the unit with
anti-corrosion treatment type using a forklift.
≥
10
≥
10
≥
10
≥
20
≥
10
≥
20
≥
50
≥
100
≥
50
≥
100
≥
200
≥
400
≥
400
≥
50
≥
50
≥
200
≥
300
≥
300
≥
300
≥
500
≥
100
≥
500
≥
300
≥
500
≥
100
≥
500
<
When
installed as a sin
g
le unit
>
(Pattern 1) NOTE)
(Pattern 2) NOTE)
(Pattern 2) NOTE)
(Pattern 3)
(Pattern 3)
(Pattern 1) NOTE)
<
When
installed in serial
>
Front
side
Front side
Front side
Front side
Front
side
Front side
No limit to
wall hei
g
ht
No limit to
wall hei
g
ht
Service space
of suction side
Service space
of front side
Service space
of suction side
Service space
of front side
Service space
of suction side
Service space
of front side
Service space
of suction side
Service space
of front side
A
B
1500
500
h2
Front side
Service space
Service space
Suction side
h1
h1 = A (Actual hei
g
ht) – 1500
h2 = B (Actual hei
g
ht) – 500
X = 500 + h1/2 or over
Y = 300 + h2/2 or over
(Y = 100 + h2/2 or over)
[Values in parentheses are for pattern 2]
≥
1500
≥
1500
≥
1500
≥
1500
≥
1500
Branch switch,
overcurrent breaker
(Earth leaka
g
e breaker)
Branch switch,
overcurrent breaker
(Earth leaka
g
e breaker)
Control panel
Warnin
g
panel
Showcase
(mm)
1
2
4
3
1
2
3
4
5
Содержание CONVENI-PACK
Страница 2: ......