• Control systems
• intelligent Touch Manager • ED721208
By short-circuiting the quantity change TP1 in the normal operating condition, the setting status
can be confirmed.
Operation
monitor
This indicates LED lighting.
1 unit
2 units
3 units
4 units
5 units
6 units
7 units
8 units
L
F1, F2
N
DEC101A51
...
Centralized
control
equipment
Switch Fuse (10A)
Facility equipment
(8 numbers max.)
Power Supply
(1 ~ 200-240V)
Electric wiring connection
Wiring Procedure
➀
<F1/F2> wiring between this equipment and centralized control equipment is
required.
➁
The connection to the facility equipment and setting of various switches are
required.
See the "
Wiring with Facility Equipment
" paragraph.
➂
Connect the power supply and earth.
See the “
Power Supply & Earth Wiring
” paragraph.
➃
For the wiring connection and clamping method, refer to the “Wiring Lead-in”
paragraph.
Wiring with Facility Equipment
<CAUTION> The length of wiring between this
equipment and facility equipment is
100m max.
Power Supply & Earth Wiring
• For power supply, 1 ~ 20 0-240V is used. the wiring to the power terminal block
(L/N) is required. The electric wire used should be 1.25 to 2.0mm
2
. After
checking the power supply specifications, make correct connections.
• Connect the earth wiring to the “ “ terminal. Use a 2.0mm
2
wire.