73
• Control systems
• intelligent Touch Manager • ED721208
<Front face of iTM plus adaptor>
A
F
I
J
K
L
M
N
G
H
B
C
D
POWER
100-240V
~
50/60H
z
L
N
E
A [plus ADP IF]
The terminals for connecting an intelligent Touch Manager or iTM plus adaptor installed in parallel.
B [DIII]
The communication line connection terminals for “DIII-NET”, which enables communications with DAIKIN’s air conditioning
equipment.
C [Di]
The terminals for connecting an external signal input device for stopping air conditioners in an emergency, or for connecting
electric energy meters for calculating the electricity usage of individual indoor air conditioning units.
D [RESERVE]
No Use.
E [POWER]
The power line connection terminals. These terminals are covered with a protective cover. A power supply voltage of
100 to 240 VAC (at 50/60 Hz) is required. Near this terminal block, there is a blue resin cable mount used for securing the power
supply cables with cable ties.
F [plus ADP ADDRESS]
The switch for selecting the address of the iTM plus adaptor. For each iTM plus adaptor, set a unique number
between 2 to 8.
G [TERM]
The switch used when multiple iTM plus adaptors are connected in parallel for enabling the termination resistor on the
furthest iTM plus adaptor from the intelligent Touch Manager.
H [DIII MASTER]
The switch used when there are two or more DIII-NET centralized controllers, such as intelligent Touch Managers,
are connected for distinguishing between the “MASTER” or the “SLAVE” controllers.
I [RESET//]
The switch for restarting the iTM plus adaptor.
J [Tx]
(Green) The indicator that indicates when on that data is being sent to the intelligent Touch Manager.
K [Rx]
(Orange) The indicator that indicates when on that data is being received from the intelligent Touch Manager.
L [DIII MONITOR]
(Yellow) The indicator that indicates when on that data is being communicated with DIII-NET.
M [CPU ALIVE]
(Green) The LED that indicates that the CPU is operating normally. For the relationship between the LED status and
the unit’s operating condition, refer to the “LED status and operation” table below.
N [ALARM]
(Red) The LED that turns on or blinks in the event of an error. For the relationship between the LED status and the unit’s
operating condition, refer to the “LED status and operation” table below.