92
• Control systems
• intelligent Touch Manager • ED721208
Installation
(Installation Place)
• Install the unit indoors where it is not exposed to water and dust or dirt.
• Install the unit where both temperature and humidity do not become high.
(Operating (available) temperature: -10 ~ +40°C)
(Operating (available) humidity: 10 ~ 85%)
• Connect the wiring to be connected in the field from the lower surface side.
It is, therefore, necessary to make arrangements so as not to attach other equipment within 80mm from the lower surface
ot this equipment.
• Install this equipment in a place in wich only the authorized personnel can touch it.
(Installation Direction)
• Install this equipment vertically to the floor surface. It should be noted that if it is installed in the horizontal direction, a
malfunction or failure may result.
(Installation Method)
• Ensure that this equipment is installed with 4 screws (screw size M4 min.).
32
5
(198)
70
(309)
33
5
70
DEC101A51
Mounting hole
UP
Mounting hole
Front panel screw
Unit (mm)
Содержание brp069a42