106
• Control systems
• intelligent Touch Manager • ED721208
Electric Wiring Work and Initial Setting
Electric Wiring Work
1
7
6
3
2
5
4
8
1
7
6
3
2
5
4
1
3
2
4
8
DS6
SS1
DS5
DS4
0
DS2
DS3
D4
D2 D3
D1
CD
H11P H12P
2
H3P
1
H10P
3
H9P
4
H2P
H4P
H1P
M4
A1
M3
A3
CA
M2
A2
M1
A4
CM
L
N
F1
F2
X4M
TNc4
TNa2
AC200V
~240V
TNb3
TNc1
X1M
X3M
LED10
RED
TNc3
TNa1
TNb4
TNb2
HAP
HAP
GRN
TNc2
TP1
H10P
X2M
TNa4
TNa3
TNb1
X2A
X1A
YE
RED
1
2
3 4
Initial setting
• DEC102A51 Switch Settings
Name
Operation
OFF
ON
SS1
Output switching
Switching control output
Always
output “1”
Always
output “2”
DS2
Abnormal input detection
Open/Close
Failure detection
Open: Close (Normal) Æ Open (Abnormal)
Close: Open (Normal) Æ Close (Abnormal)
Open
Close
DS3
Buzzer output ON/OFF
ON/OFF switching of buzzer output of buzzer
unit upon detection of failure.
ON
OFF
DS4-1
Instantaneous automatic
recovery
Recover control output after power failure to
status before the power failure.
No
Yes
DS4-2
Transmission failure
Shut off control output upon detecting transfer
failure.
Yes
No
DS4-3
Last command priority
Allowing start/stop control from facility.
Yes
No
DS4-4
Start/stop failure
Detecting start/stop failure. (*1)
No
Yes
DS5
Abnormal output shutoff/retain Shut off control output upon detecting failure.
Yes
No
DS6-1
Startup failure
Masking time after detecting operation input.
10
seconds
30
seconds
DS6-2
Failure detection
Operation upon recovery from failure.
Automatic
reset
Retained
DS6-3
Monitor input
Detecting failure under halting status.
Yes
No
DS6-4
Forced termination
Ignoring forced stop signal.
No
Yes
Note:
1. All are set to “OFF” upon shipment from factory.
2. *1 If operating feedback input is not detected within 10 seconds after 1 operation input is received, it results in start/stop failure.
No simultaneous clamping is allowed for high-voltage wiring <power
supply wiring (L/N), earth wiring, relay output wiring (CD, D1 to 4)>,
low-voltage wiring <communication wiring (F1/F2), operation input
wiring (CM, M1 to 4) and abnormal input wiring (CA, A1 to 4)> since
malfunctioning may result. Also, in case where the wirings described
above are routed in parallel, be sure to connect the wirings at least
50mm apart from the other.
➀
To 1~200-240V and earth
➁
To facility equipment
➂
To facility equipment
➃
To terminals F1, F2 of the centralized control equipment or terminals
F1, F2 of other equipment
(outdoor unit, DEC101A51, 102A51)
Alarm
Monitor
(RED)
ON
ON
ON
INPUT
Group No. Set
DS1 High
RS1 Low
Operation
Monitor
(GRN)
Contact switch
Con.
Ins.