66
• Control systems
• intelligent Touch Manager • ED721208
<DIII MASTER>
To set the intelligent Touch Manager to SLAVE, use the DIII
MASTER switch located under the front slide cover. Placing the
DIII MASTER switch in the upper position (labeled as “SLAVE”)
changes it to a SLAVE.
To install multiple centralized controllers, set only the highest priority controller to MASTER and all other controllers to SLAVE according
to the following order of priority:
High
(1) Interface for use in BACnet
(2) Interface for use in LONWORKS
(3) intelligent Touch Manager (Main),
iTM plus adaptor (Main)
(4) Central Remote Controller (Main)
(5) intelligent Touch Manager (Sub),
iTM plus adaptor (Sub)
(6) Central Remote Controller (Sub)
(7) ON/OFF Controller (Main)
(8) ON/OFF Controller (Sub)
Priority
Low
Centralized
controllers that
cannot be installed in
parallel with
intelligent Touch
Manager
• CALCULATE UNIT
• intelligent Processing Unit
• Parallel Interface
• Intelligent Touch Controller
• DIII-NET Plus Adapter
• Residential Central Remote Controller
• Schedule Timer
• Wiring Adaptor for Electrical Appendices (1) (KRP2)
Connecting a LAN cable
Connecting your intelligent Touch Manager with a PC network enables you to set up the operation of air conditioning system or perform
maintenance work on it from a remote location.
WARNING
Do not clamp the cables with high-current lines such as a power cable.
NOTE
For how to connect the intelligent Touch Manager to a PC network, contact your network administrator.