14 Technical data
Installer reference guide
97
EBLQ+EDLQ011~W1 + EK(2)CB
EKMB9W1
Daikin Altherma low temperature monobloc
4P522034-1 – 2018.01
14.5
ESP curve: Outdoor unit
Note:
A flow error will occur when the minimum water flow rate is not
reached.
0
10
20
30
40
50
60
70
80
90
0
5
10
15
20
25
30
35
40
45
50
A (kPa)
B (l/min)
4D115246
C
E
D
F
A
External static pressure
B
Water flow rate
C
Operation range
D
Minimum flow during normal operation.
E
Minimum flow during defrost operation in case the system
contains a backup heater / DHW tank with recirculation
pump / glycol.
F
Minimum flow during defrost operation in case does NOT
contain a backup heater / DHW tank with recirculation
pump
(a)
/ glycol
(a)
If an EKHWP tank is installed, no recirculation pump is
required.
Notes:
▪ About the dashed lines: The operation area is extended to lower
flow rates only in case the unit operates with heat pump only, and
the temperature of the flow medium is sufficiently high. (This does
not apply to start-up operation, defrost operation, and backup
heater operation in case a backup heater is installed.)
▪ The upper operation range is only valid if the flow medium is
water. If glycol is added to the system, the operation range limit is
lower.
▪ Selecting a flow outside the operating area can damage the unit or
cause the unit to malfunction.