8 Configuration
Installer reference guide
59
EBLQ+EDLQ011~W1 + EK(2)CB
EKMB9W1
Daikin Altherma low temperature monobloc
4P522034-1 – 2018.01
#
Code
Description
[A.3.1.2.1]
N/A
LWT setpoint mode:
▪ Fixed: The desired leaving water
temperature is:
▪ NOT weather-dependent (i.e. does
NOT depend on the outdoor
ambient temperature)
▪ fixed in time (i.e., NOT scheduled)
▪ Weather dep. (default): The desired
leaving water temperature is:
▪ weather-dependent (i.e. depends
on
the
outdoor
ambient
temperature)
▪ fixed in time (i.e., NOT scheduled)
▪ Fixed/scheduled: The desired leaving
water temperature is:
▪ NOT
weather-dependent
(i.e.,
does NOT depend on the outdoor
ambient temperature)
▪ according
a
schedule.
The
scheduled actions are On or OFF.
Remark:
This value can only be
set in leaving water temperature
control.
▪ WD/scheduled: The desired leaving
water temperature is:
▪ weather-dependent
(i.e.,
does
depend on the outdoor ambient
temperature)
▪ according
a
schedule.
The
scheduled actions are On or OFF.
Remark:
This value can only be
set in leaving water temperature
control.
#
Code
Description
[7.7.2.1]
[0-00]
[0-01]
[0-02]
[0-03]
Set weather-dependent heating:
[0-00]
[0-01]
Ta
Tt
[0-03]
[0-02]
▪ T
t
: Target leaving water temperature
(additional)
▪ T
a
: Outdoor temperature
continued >>
#
Code
Description
[7.7.2.1]
[0-00]
[0-01]
[0-02]
[0-03]
<< continuation
▪ [0-03]:
Low
outdoor
ambient
temperature. –40°C~+5°C (default: –
10°C)
▪ [0-02]:
High
outdoor
ambient
temperature. 10°C~25°C (default:
15°C)
▪ [0-01]:
Desired
leaving
water
temperature
when
the
outdoor
temperature equals or drops below
the
low
ambient
temperature.
[9‑05]°C~[9‑06]°C (default: 45°C).
Note:
This value should be higher
than [0-00] as for low outdoor
temperatures
warmer
water
is
required.
▪ [0-00]:
Desired
leaving
water
temperature
when
the
outdoor
temperature equals or rises above
the
high
ambient
temperature.
[9‑05]°C~min(45, [9‑06])°C (default:
35°C).
Note:
This value should be lower
than [0-01] as for high outdoor
temperatures less warm water is
required.
#
Code
Description
[7.7.2.2]
[0-04]
[0-05]
[0-06]
[0-07]
Set weather-dependent cooling:
[0-04]
[0-05]
Ta
Tt
[0-07]
[0-06]
▪ T
t
: Target leaving water temperature
(additional)
▪ T
a
: Outdoor temperature
continued >>