Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
A.2.1.8
[7-02]
R/W
0: 1 LWT zone
1: 2 LWT zones
A.2.1.9
[F-0D]
R/W
0: Continuous
1: Sample
2: Request
A.2.1.A
[E-04]
R/O
0~1
0: No
A.2.1.B
R/W
0: At unit
1: In room
A.2.1.C
[E-0D]
R/W
0: No
1: Yes
└─ Options
A.2.2.A
[D-02]
R/W
0: No
1: Secondary rtrn
2: Disinf. Shunt
3: Circul. Pump
4: CP & disinf. Sh
A.2.2.B
[C-08]
R/W
0: No
1: Outdoor sensor
2: Room sensor
└────────────────── Control box
A.2.2.E.1
[E-03]
R/W
0: No BUH
1: 1 step
2: 2 steps
A.2.2.E.2
[5-0D]
R/W
0~5
1: 1P,(1/1+2)
4: 3PN,(1/2)
5: 3PN,(1/1+2)
A.2.2.E.3
[D-01]
R/W
0: No
1: Open tariff
2: Closed tariff
A.2.2.E.4
[E-05]
R/W
0: No
1: Yes
A.2.2.E.5
[C-05]
R/W
1: Thermo ON/OFF
2: C/H request
A.2.2.E.6
[C-06]
R/W
0~2
1: Thermo ON/OFF
└────────────────── Option box
A.2.2.F.1
[C-02]
R/W
0: No
1: Bivalent
2: -
3: -
A.2.2.F.2
[C-09]
R/W
0: Normally open
1: Normally closed
A.2.2.F.3
[D-08]
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
A.2.2.F.4
[D-09]
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
A.2.2.F.5
[C-08]
R/W
0: No
1: Outdoor sensor
2: Room sensor
A.2.2.F.6
[D-04]
R/O
0: No
1: Yes
└─ Capacities
A.2.3.1
[6-02]
R/W
0~10kW, step: 0,2kW
3kW
A.2.3.2
[6-03]
R/W
0~10kW, step: 0,2kW
3kW
A.2.3.3
[6-04]
R/W
0~10kW, step: 0,2kW
0kW
└─ Space operation
└─ LWT settings
└────────────────── Main
A.3.1.1.1
R/W
0: Fixed
1: Weather dep.
2: Fixed + scheduled
3: WD + scheduled
A.3.1.1.2.1
[9-01]
Temperature range
Minimum temp (heating)
R/W
15~37°C, step: 1°C
25°C
A.3.1.1.2.2
[9-00]
Temperature range
Maximum temp (heating)
R/W
37~55°C, step: 1°C
55°C
A.3.1.1.2.3
[9-03]
Temperature range
Minimum temp (cooling)
R/W
5~18°C, step: 1°C
5°C
A.3.1.1.2.4
[9-02]
Temperature range
Maximum temp (cooling)
R/W
18~22°C, step: 1°C
22°C
A.3.1.1.5
[8-05]
R/W
0: No
1: Yes
A.3.1.1.7
[9-0B]
R/W
0: Quick
1: Slow
└────────────────── Additional
A.3.1.2.1
R/W
0: Fixed
1: Weather dep.
2: Fixed + scheduled
3: WD + scheduled
A.3.1.2.2.1
[9-05]
Temperature range
Minimum temp (heating)
R/W
15~37°C, step: 1°C
25°C
A.3.1.2.2.2
[9-06]
Temperature range
Maximum temp (heating)
R/W
37~55°C, step: 1°C
55°C
A.3.1.2.2.3
[9-07]
Temperature range
Minimum temp (cooling)
R/W
5~18°C, step: 1°C
5°C
A.3.1.2.2.4
[9-08]
Temperature range
Maximum temp (cooling)
R/W
18~22°C, step: 1°C
22°C
Number of LWT zones
Pump operation mode
Power saving possible
User interface location
External sensor
Backup heater steps
BUH type
DHW pump
Glycol present
Preferential kWh rate
Contact type main
Ext. backup heat src
Alarm output
External kWh meter 1
External kWh meter 2
DHW operation
Contact type add.
External sensor
PCC by digital inputs
BUH: step 1
BUH: step 2
LWT setpoint mode
Modulated LWT
Booster heater
Emitter type
LWT setpoint mode
(*1) *B*_(*2) *D*
4P522033-1 - 2018.01