4 About the units and options
Installer reference guide
9
ERHQ+ERLQ011~016 + EHBH/X11+16CB
Daikin Altherma – Low temperature split
4P384974-1 – 2015.01
4.2.1
Identification label: Outdoor unit
Location
Model identification
▪ ERLQ: Contains components (insulation, bottom plate heater, …)
to prevent freeze-up in areas with low ambient temperature and
high humidity.
▪ ERHQ: Does NOT contain these components.
Example:
ER L Q 011 CA W1
Code
Explanation
ER
European split outdoor pair heat pump
L
H=Low water temperature – ambient zone:
0~−10°C
L=Low water temperature – ambient zone:
−10~−20°C
Q
Refrigerant R410A
011
Capacity class
CA
Model series
W1
Power supply
4.2.2
Identification label: Indoor unit
Location
Model identification
Example:
E HB H 04 CB 3V
Code
Description
E
European model
HB
Wall-mounted indoor unit
H
H=Heating only
X=Heating/cooling
04
Capacity class
CB
Model series
3V
Backup heater model
4.3
Combining units and options
4.3.1
Possible options for the outdoor unit
Demand PCB (KRP58M51) (only for ERLQ)
▪ Limits the maximum current. However, this also decreases the
heating/cooling capacity of the system.
▪ Only the "Setting of demand running" function of the demand PCB
is applicable.
▪ For installation instructions, see the installation manual of the
demand PCB.
Snow cover (EK016SNC) (only for ERLQ)
▪ Prevents the outdoor unit from being snowed up.
▪ Recommended in areas with low ambient temperatures or heavy
snowfall.
▪ For installation instructions, see the installation manual of the
snow cover.
Drain plug kit (EKDK04) (only for ERHQ)
▪ Gathers the condensate from the outdoor unit and guides it away
through 1 plug in the bottom plate.
▪ For ERLQ: Drain plug kit is not applicable.
▪ For ERHQ: Drain plug kit is option.
▪ Cannot be combined with bottom plate heater.
▪ For installation instructions, see the installation manual of the
drain plug kit.
Bottom plate heater (EKBPHTH16A) (only for ERHQ in
combination with C* indoor unit)
▪ Prevents freeze-up of the bottom plate.
▪ Recommended in areas with low ambient temperature and high
humidity.
▪ For ERLQ: Bottom plate heater is standard (factory-mounted).
▪ For ERHQ: Bottom plate heater is option.
▪ Cannot be combined with drain plug kit.
▪ If you install EKBPHTH16A, you also have to install the digital I/O
PCB (EKRP1HB).
▪ For installation instructions, see the installation manual of the
bottom plate heater and addendum book for optional equipment.
4.3.2
Possible options for the indoor unit
User interface (EKRUCBL*)
The user interface and a possible additional user interface are
available as an option.
The additional user interface can be connected:
▪ To have both:
▪ control close to the indoor unit,
▪ room thermostat functionality in the principal space to be
heated.
▪ To have an interface containing other languages.
Following user interfaces are available:
▪ EKRUCBL1 contains following languages: German, French,
Dutch, Italian.
▪ EKRUCBL2 contains following languages: English, Swedish,
Norwegian, Finnish.
▪ EKRUCBL3 contains following languages: English, Spanish,
Greek, Portuguese.
▪ EKRUCBL4 contains following languages: English, Turkish,
Polish, Romanian.
▪ EKRUCBL5 contains following languages: German, Czech,
Slovenian, Slovakian.
▪ EKRUCBL6 contains following languages: English, Croatian,
Hungarian, Estonian.
▪ EKRUCBL7 contains following languages: English, German,
Russian, Danish.