6 Preparation
Installer reference guide
28
ERHQ+ERLQ011~016 + EHBH/X11+16CB
Daikin Altherma – Low temperature split
4P384974-1 – 2015.01
6.5.2
About preferential kWh rate power supply
NOTICE
For applications with preferential kWh rate power supply:
The interruption of the outdoor unit power supply may not
be more than 2 hours to guarantee optimised startup
conditions for the compressor.
Electricity companies throughout the world work hard to provide
reliable electric service at competitive prices and are often
authorized to bill clients at benefit rates. E.g. time-of-use rates,
seasonal rates, Wärmepumpentarif in Germany and Austria, ...
This equipment allows for connection to such preferential kWh rate
power supply delivery systems.
Consult with the electricity company acting as provider at the site
where this equipment is to be installed to know whether it is
appropriate to connect the equipment in one of the preferential kWh
rate power supply delivery systems available, if any.
When the equipment is connected to such preferential kWh rate
power supply, the electricity company is allowed to:
▪ interrupt power supply to the equipment for certain periods of time;
▪ demand that the equipment only consumes a limited amount of
electricity during certain periods of time.
The indoor unit is designed to receive an input signal by which the
unit switches into forced off mode. At that moment, the outdoor unit
compressor will not operate.
Whether the power supply is interrupted or not, the wiring to the unit
is different.
Overview of electrical connections except external actuators
Normal power
supply
Preferential kWh rate power supply
Power supply is
NOT interrupted
Power supply is
interrupted
1
580
1 50
0
0
2
a
3
1
4
580
1 50
0
0
2
b
3
During preferential
kWh rate power
supply activation,
power supply is NOT
interrupted. The
outdoor unit is turned
off by the control.
Remark:
The
electricity company
must always allow the
power consumption
of the indoor unit.
5 3
a
b
1
4
580
1 50
0
0
580
1 50
0
0
2
During preferential
kWh rate power
supply activation,
power supply is
interrupted
immediately or after
some time by the
electricity company.
In this case, the
indoor unit must be
powered by a
separate normal
power supply.
a
Normal power supply
b
Preferential kWh rate power supply
1
Power supply for outdoor unit
2
Power supply and interconnection cable to indoor unit
3
Power supply for backup heater
4
Preferential kWh rate power supply (voltage free contact)
5
Normal kWh rate power supply (to power the indoor unit
PCB in the event of power supply interruption of the
preferential kWh rate power supply)
6.5.3
Overview of electrical connections for
external and internal actuators
The following illustration shows the required field wiring.
INFORMATION
The following illustration is an example and might NOT
match your system layout.
M
M
6
7
c
16
21
d
e
8 10
a
9 19
12
14
b
20
15
13
14
17
18
a
Single power supply for outdoor unit, backup heater and
booster heater
b
Backup heater
c
Indoor unit
d
Domestic hot water tank
e
Booster heater
Item
Description
Wires
Maximum
running
current
Outdoor unit and indoor unit power supply
1
Power supply for
outdoor unit
2+GND or
3+GND
(a)
2
Power supply and
interconnection cable to
indoor unit
3
(c)
3
Power supply for
backup heater
See table below. —
4
Preferential kWh rate
power supply (voltage
free contact)
2
(e)
5
Normal kWh rate power
supply
2
6.3 A
User interface
6
User interface
2
(f)
Optional equipment
7
3‑way valve
3
100 mA
(b)
8
Power supply for
booster heater and
thermal protection
(from indoor unit)
4+GND
(c)
9
Power supply for
booster heater (to
indoor unit)
2+GND
13 A
10
Domestic hot water
tank thermistor
2
(d)
11
Power supply for
bottom plate heater
2
(b)
12
Room thermostat
3 or 4
100 mA
(b)
13
Outdoor ambient
temperature sensor
2
(b)
14
Indoor ambient
temperature sensor
2
(b)