
5 Application guidelines
Installer reference guide
13
ERHQ+ERLQ011~016 + EHBH/X11+16CB
Daikin Altherma – Low temperature split
4P384974-1 – 2015.01
▪ A shut-off valve (field supply) is installed before the under floor
heating to prevent condensation on the floor during cooling
operation.
▪ The desired room temperature is set via the remote controller of
the heat pump convectors.
▪ The space heating/cooling demand signal is sent to one digital
input on the indoor unit (X2M/1 and X2M/4)
▪ The space operation mode is sent by one digital output (X2M/32
and X2M/33) on the indoor unit to:
▪ The heat pump convectors
▪ The shut-off valve
Configuration
Setting
Value
Unit temperature control:
▪ #: [A.2.1.7]
▪ Code: [C-07]
1 (Ext RT control): Unit operation
is decided by the external
thermostat.
Number of water temperature
zones:
▪ #: [A.2.1.8]
▪ Code: [7-02]
0 (1 LWT zone): Main
External room thermostat for the
main
zone:
▪ #: [A.2.2.4]
▪ Code: [C-05]
1 (Thermo ON/OFF): When the
used external room thermostat or
heat pump convector can only
send a thermo ON/OFF
condition. No separation between
heating or cooling demand.
Benefits
▪
Cooling
.
Heat pump convectors provide, besides heating
capacity, also excellent cooling capacity.
▪
Efficiency
. Under floor heating has the best performance with
Altherma LT.
▪
Comfort
.
The combination of the two heat emitter types provides:
▪ The excellent heating comfort of the under floor heating
▪ The excellent cooling comfort of the heat pump convectors
5.2.2
Multiple rooms – One LWT zone
If only one leaving water temperature zone is needed because the
design leaving water temperature of all heat emitters is the same,
you do NOT need a mixing valve station (cost effective).
Example:
If the heat pump system is used to heat up one floor
where all the rooms have the same heat emitters.
Under floor heating or radiators – Thermostatic
valves
If you are heating up rooms with under floor heating or radiators, a
very common way is to control the temperature of the main room by
using a thermostat (this can either be the user interface or an
external room thermostat), while the other rooms are controlled by
so-called thermostatic valves, which open or close depending on the
room temperature.
Setup
T
B
C
A
a
A
Main leaving water temperature zone
B
Room 1
C
Room 2
a
User interface
▪ The under floor heating of the main room is directly connected to
the indoor unit.
▪ The room temperature of the main room is controlled by the user
interface used as thermostat.
▪ A thermostatic valve is installed before the under floor heating in
each of the other rooms.
INFORMATION
Mind situations where the main room can be heated by
another heating source. Example: Fireplaces.
Configuration
Setting
Value
Unit temperature control:
▪ #: [A.2.1.7]
▪ Code: [C-07]
2 (RT control): Unit operation is
decided based on the ambient
temperature of the user interface.
Number of water temperature
zones:
▪ #: [A.2.1.8]
▪ Code: [7-02]
0 (1 LWT zone): Main
Benefits
▪
Cost effective
.
▪
Easy
. Same installation as for one room, but with thermostatic
valves.
Under floor heating or radiators – Multiple external
room thermostats
Setup
M2
M1
B
C
A
a
a
b
A
Main leaving water temperature zone
B
Room 1
C
Room 2
a
External room thermostat
b
Bypass valve
▪ For each room, a shut-off valve (field supplied) is installed to avoid
leaving water supply when there is no heating or cooling demand.
Содержание Altherma ERLQ011-014-016CA
Страница 144: ...4P384974 1 2015 01 Copyright 2015 Daikin ...