Outdoor Unit Functional Concept
ESIE06-03
2–22
Part 2 – Functional Description
3
1
2
4
5
3.10
Low Hz High Pressure Limit
Outline
Heat Pump Only
Set the upper limit of high pressure in a low Hz zone. Set the upper limit of the indoor heat exchanger
temperature by its operating frequency of Hz. Separate into three zones, reset zone, unchanged zone
and drooping zone and the frequency control must be carried out in such zones.
Separate into zones
Note
Drooping: The system stops after staying in the drooping zone for 2 minutes.
Highest heat
exchanger
temperature
among the
operating rooms
Reset zone
60˚C
59˚C
56˚C
Unchanged
zone
Drooping zone
Содержание Altherma EKHBH Series
Страница 2: ...ESIE06 03 1 2 Part 1 System Outline 3 1 1 5 ...
Страница 26: ...Functional Diagrams ESIE06 03 1 26 Part 1 System Outline 3 1 1 4 5 ...
Страница 32: ...Piping Diagrams ESIE06 03 1 32 Part 1 System Outline 3 1 1 4 5 ...
Страница 38: ...Switch Box Layout ESIE06 03 1 38 Part 1 System Outline 3 1 1 4 5 ...
Страница 58: ...PCB Layout ESIE06 03 1 58 Part 1 System Outline 3 1 1 4 5 ...
Страница 60: ...ESIE06 03 2 2 Part 2 Functional Description 3 1 2 5 ...
Страница 68: ...Hydro box Functional Concept ESIE06 03 2 10 Part 2 Functional Description 3 1 2 4 5 ...
Страница 88: ...ESIE06 03 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Страница 134: ...Error Codes System Malfunctions ESIE06 03 3 48 Part 3 Troubleshooting 3 1 3 4 5 ...
Страница 152: ...Additional Checks for Troubleshooting ESIE06 03 3 66 Part 3 Troubleshooting 3 1 3 4 5 ...
Страница 154: ...ESIE06 03 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Страница 180: ...Removal procedure outdoor unit ERYQ005 007AAV3 ESIE06 03 5 28 Part 5 Disassembly and Maintenance 3 1 5 5 ...