ESIE06-03
Outdoor Unit Functional Concept
Part 2 – Functional Description
2–25
3
2
4
5
1
3.11.2 Pressure Equalization Control
When the compressor is stopped, open and close the electronic expansion valve and develop
pressure equalization.
3.11.3 Opening Limit
Outline
Limit a maximum and minimum opening of the electronic expansion valve.
Detail
P
A maximum electronic expansion valve opening: 480 pulses
P
A minimum electronic expansion valve opening: 54 pulses
The electronic expansion valve is opened with fixed opening during defrosting.
3.11.4 Starting Operation Control
Control the electronic expansion valve opening when the system is starting, and prevent the system
to be super heated or moistened.
3.11.5 High Temperature of the Discharge Pipe
When the compressor is operating, if the discharge pipe temperature exceeds a certain value, open
the electronic expansion valve and remove the refrigerant to the low pressure side and lower
discharge temperature.
3.11.6 Disconnection of the Discharge Pipe Thermistor
Outline
Disconnection of the discharge pipe thermistor is detected by comparing the discharge pipe
temperature with the heat exchanger temperature. If any is disconnected, open the electronic
expansion valve according to the outdoor air temperature and the operating frequency, and operate
for 9 minutes, and then stop.
After 3 minutes of waiting, the compressor restarts and the same process is carried out again. If the
disconnection is detected 4 times in succession, then the system will be down.
When the compressor runs for 60 minutes without any error, the error counter will reset itself.
Содержание Altherma EKHBH Series
Страница 2: ...ESIE06 03 1 2 Part 1 System Outline 3 1 1 5 ...
Страница 26: ...Functional Diagrams ESIE06 03 1 26 Part 1 System Outline 3 1 1 4 5 ...
Страница 32: ...Piping Diagrams ESIE06 03 1 32 Part 1 System Outline 3 1 1 4 5 ...
Страница 38: ...Switch Box Layout ESIE06 03 1 38 Part 1 System Outline 3 1 1 4 5 ...
Страница 58: ...PCB Layout ESIE06 03 1 58 Part 1 System Outline 3 1 1 4 5 ...
Страница 60: ...ESIE06 03 2 2 Part 2 Functional Description 3 1 2 5 ...
Страница 68: ...Hydro box Functional Concept ESIE06 03 2 10 Part 2 Functional Description 3 1 2 4 5 ...
Страница 88: ...ESIE06 03 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Страница 134: ...Error Codes System Malfunctions ESIE06 03 3 48 Part 3 Troubleshooting 3 1 3 4 5 ...
Страница 152: ...Additional Checks for Troubleshooting ESIE06 03 3 66 Part 3 Troubleshooting 3 1 3 4 5 ...
Страница 154: ...ESIE06 03 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...
Страница 180: ...Removal procedure outdoor unit ERYQ005 007AAV3 ESIE06 03 5 28 Part 5 Disassembly and Maintenance 3 1 5 5 ...