9 Operation

Installation and operation manual

30

EHYKOMB33A

Daikin Altherma hybrid heat pump – gas boiler module

4P353067-1K – 2020.10

12

Switch  off  the  appliance  by  pressing  the    button  and  put  the
sampling point back in its place. Make sure it is gastight.

13

Put the front panel back in its place.

CAUTION

Work  on  gas  carrying  parts  may  only  be  carried  out  by  a
qualified competent person.

To adjust the CO

 setting

INFORMATION

Only adjust the CO

2

 setting when you have checked it first

and  are  sure  adjustment  is  necessary.  In  Belgium,  any
modifications  to  the  gas  valve  MUST  be  performed  by  a
certified  representative  of  the  manufacturer.  For  more
information, contact your dealer.

1

Remove  the  cap  that  covers  the  adjustment  screw.  In  the
illustration, the cover cap is already removed.

2

Turn  the  screw  (a)  to  increase  (clockwise)  or  decrease
(counterclockwise) the CO

2

 percentage. See the table below for

the desired value.

a

a

Adjusting screw with cover

Measured value at
maximum power

Adjustment values CO

2

 (%) at

minimum power (front cover opened)

Natural gas 2H/2E
(G20, 20 mbar)

Propane 3P (G31,
30/50/37 mbar)

10.8

10.5±0.1

10.6

10.3±0.1

10.4

10.1±0.1

10.2

9.9±0.1

10.0

9.8±0.1

9.8

9.6±0.1

9.6

9.0±0.1

9.4

8.9±0.1

9.2

8.8±0.1

9.0

8.7±0.1

8.8

8.6±0.1

8.6

8.5±0.1

3

After  measuring  the  CO

2

  percentage  and  adjusting  the  setting,

put  the  cover  cap  and  the  sampling  point  back  in  their  place.
Make sure they are gastight.

4

Select High setting by simultaneously pressing 

 and   twice.

Capital   will appear on the service display.

5

Measure  the  CO

2

  percentage.  If  the  CO

2

  percentage  still

deviates  from  the  values  in  the  table  indicating  the  CO

2

percentage at maximum power, contact your local dealer.

6

Press   and   simultaneously to exit the test program.

7

Put the front panel back in its place.

9

Operation

9.1

Overview: Operation

The  gas  boiler  is  a  modulating,  high-efficiency  boiler.  This  means
that the power is adjusted in line with the desired heat requirement.
The aluminium heat exchanger has 2 separate copper circuits. As a
result  of  the  separately  constructed  circuits  for  space  heating  and
domestic  hot  water,  the  heating  and  the  hot  water  supply  can
operate independently, but not simultaneously.

The  gas  boiler  has  an  electronic  boiler  controller  which  does  the
following when heating or hot water supply is required:

▪ starting the fan,

▪ opening the gas valve,

▪ igniting the burner,

▪ constantly monitoring and controlling the flame.

It  is  possible  to  use  the  domestic  hot  water  circuit  of  the  gas  boiler
without connecting and filling the space heating system.

9.2

Heating

Heating  is  controlled  by  the  indoor  unit.  The  boiler  will  start-up  the
heating process when there is a request from the indoor unit.

INFORMATION

For  third-party  gas  boilers,  prolonged  boiler  operation  at
low outdoor temperatures might be temporarily interrupted
to protect the outdoor unit and water piping from freezing.
During  this  temporary  interruption  the  boiler  might  appear
to be off.

9.3

Domestic hot water

Not applicable for Switzerland

Instant  domestic  hot  water  is  supplied  by  the  boiler.  Because
supplying  domestic  hot  water  has  priority  over  space  heating,  the
boiler will switch to domestic hot water mode whenever there is a hot
water  demand.  When  a  simultaneous  space  heating  and  domestic
hot water demand occurs:

▪ during  heat  pump  only  operation  (space  heating  mode),  the  heat

pump will provide heat while the boiler is bypassed and switches
to domestic hot water mode to provide domestic hot water.

▪ during  boiler  only  operation,  and  with  the  boiler  in  domestic  hot

water  mode,  space  heating  will  NOT  be  provided,  but  domestic
hot water will.

▪ during  simultaneous  heat  pump  and  boiler  operation,  the  heat

pump will provide heat and the boiler will be bypassed and switch
to domestic hot water mode to provide domestic hot water.

This  manual  only  explains  the  domestic  hot  water  making  without
having a domestic hot water tank combined with the system. For the
operation and needed settings of domestic hot water in combination
with  a  domestic  hot  water  tank  needed  for  Switzerland,  please  see
the manual of the heat pump module.

INFORMATION

For  EHY32AA,  prolonged  instant  domestic  hot
water  operation  at  low  outdoor  temperatures  might  be
temporarily  interrupted  to  protect  the  outdoor  unit  and
water piping from freezing.

9.4

Operation modes

The  following  codes  on  the  service  display  indicate  the  following
operating modes.

Содержание Altherma EHYKOMB33AA

Страница 1: ...Installation and operation manual Daikin Altherma hybrid heat pump gas boiler module English Installation and operation manual Daikin Altherma hybrid heat pump gas boiler module EHYKOMB33AA...

Страница 2: ...u e jsou vyu v ny v souladu s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni kor...

Страница 3: ...management kit 22 7 7 11 Flues in voids 22 7 7 12 Flue gas materials C63 available on the market 22 7 7 13 About securing the flue system 23 7 8 Finishing the gas boiler installation 24 7 8 1 To clos...

Страница 4: ...http www daikineurope com support and manuals product information Addendum book for optional equipment Additional info about how to install optional equipment Format Paper in the box of the indoor un...

Страница 5: ...the system WARNING Tear apart and throw away plastic packaging bags so that nobody especially children can play with them Possible risk suffocation WARNING Provide adequate measures to prevent that t...

Страница 6: ...e wiring diagram Do NOT touch electrical components with wet hands Do NOT leave the unit unattended when the service cover is removed WARNING If NOT factory installed a main switch or other means for...

Страница 7: ...or unauthorized modifications to the appliance flue or associated components and systems could invalidate the warranty The manufacturer accepts no liability arising from any such actions excluding sta...

Страница 8: ...ler Before unpacking move the gas boiler as close as possible to its installation position 1 2 WARNING Tear apart and throw away plastic packaging bags so that nobody especially children can play with...

Страница 9: ...rotect the piping and valves of the gas boiler For installation instructions see the installation manual of the cover plate Gas conversion kit G25 EKPS076227 Kit for the conversion of the gas boiler f...

Страница 10: ...EKFGP4810 Elbow PP ALU 80 125 90 EKFGP4820 Inspection elbow Plus PP ALU 80 125 90 EPDM EKFGP6864 Roof Terminal PP GLV 80 125 AR300 RAL 9011 EKFGT6300 Weather slate steep Pb GLV 80 125 18 22 EKFGT6301...

Страница 11: ...1 Chimney connection 60 10 air intake Dn 80 C83 EKFGV1102 Connection set 60 10 60 Flue Air intake Dn 80 C53 EKFGW4001 Extension P BM Air 80 500 EKFGW4002 Extension P BM Air 80 1000 EKFGW4004 Extension...

Страница 12: ...ting the gas boiler INFORMATION Removing the top plate of the indoor unit makes it easier to install the gas boiler 7 2 1 To install the gas boiler 1 Lift the unit from the package 36kg 2 Remove the t...

Страница 13: ...e powering up the boiler See illustration below NOT placing or filling up the condensate trap may cause flue gases to come into the installation room and can lead to dangerous situations In order to p...

Страница 14: ...ade to prevent freezing The pipe should be run internally as far as possible before going to the outside The pipe diameter should be increased to a minimum inner diameter of 30 mm typically outer diam...

Страница 15: ...let space heating NOTICE Make sure that the straight brass fitting connections are tightened thoroughly to prevent leakage Maximum torque is 30 N m To fill the domestic water circuit of the gas boiler...

Страница 16: ...noid coil is outside the gas boiler switch box 6 Route the communication cable from the gas boiler to the indoor unit as in figure below 7 Open the switch box cover of the indoor unit 8 Plug the indoo...

Страница 17: ...take take into account the serviceability of the indoor unit When the gas exhaust air intake goes backwards over the indoor unit the expansion vessel cannot be accessed and if necessary will have to b...

Страница 18: ...Equivalent length for concentric installation 60 100 Length m Bend 90 1 5 Bend 45 1 Equivalent length for dual pipe installation Length m R D 1 Bend 90 2 m Bend 45 1 m R D 0 5 Elbow 90 4 m Elbow 45 2...

Страница 19: ...CE approval Do NOT mix flue materials from different suppliers C83 Joint air supply and flue gas discharge duct CLV system Discharging into different pressure zones Only as twin pipe system C93 Air su...

Страница 20: ...units Minimum 2 130 3 150 4 180 5 200 6 220 7 230 8 250 9 270 10 280 11 290 12 300 Special remark regarding C43 See the table below for the minimum diameters of the combined gas exhaust air intake sy...

Страница 21: ...g a boundary it is recommended that an anti plume kit be fitted T T1 T2 Terminals adjacent to windows or openings on pitched and flat roofs The flue should NOT penetrate this area 2000 600 NOTICE The...

Страница 22: ...the manufacturer s instructions regarding maximum length of the flue system the appropriate flue material correct jointing methods and the maximum distance between flue support Make sure that all join...

Страница 23: ...be secured to a solid structure The flue system should have a continuous fall back to the boiler 1 5 3 Wall terminals MUST be installed levelled Only use accompanying brackets Every elbow MUST be sec...

Страница 24: ...067 1K 2020 10 1000 m m 2000 mm 1000 mm 250 mm 250 mm 250 m m 250 mm 3 50 mm m 1000 m m 1000 m m 500 mm a b a Second clamp after the second elbow b First clamp after the second elbow 7 8 Finishing the...

Страница 25: ...cate that the power is ON In this mode the pressure in the space heating installation will also be displayed on the main display bar Domestic hot water comfort function Not applicable for Switzerland...

Страница 26: ...meters 1 Press simultaneously on and until appears on the main and the service display 2 Use the and buttons to set service code on the main display 3 Press the button to set the parameter on the serv...

Страница 27: ...nging this setting has no effect on the operation of the unit Step modulation 0 1 1 0 OFF during space heating operation 1 ON during space heating operation It is recommended not to modify this settin...

Страница 28: ...rning is increased slowly and is reduced as soon as the supply temperature is reached Frost protection function The boiler is equipped with an internal frost protection function that automatically ope...

Страница 29: ...correct readings It is recommended to wait at least 30 minutes 5 Switch on the gas boiler with the button and create a space heating demand 6 Select High setting by simultaneously pressing and twice C...

Страница 30: ...he heating and the hot water supply can operate independently but not simultaneously The gas boiler has an electronic boiler controller which does the following when heating or hot water supply is req...

Страница 31: ...are controlled by the gas boiler controller so that the domestic hot water temperature reaches the domestic hot water temperature setting The domestic hot water supply temperature must be set on the...

Страница 32: ...r ON at minimum power and Burner ON maximum space heating power setting and 1 Burner ON maximum domestic hot water setting and 2 Stop test program and Actual situation NOTICE If an 81 04 error occurs...

Страница 33: ...emove the pipe downwards by turning the pipe alternately clockwise and counterclockwise 9 Lift the condensate drain pan on the left hand side from the connection to the condensate trap 10 Turn it to t...

Страница 34: ...ews plus serrated lock washers 3 Tighten the socket head screws equally hand tight by turning the hex key clockwise 4 Fit the gas connection below the gas valve 5 Fit the connector to the fan and the...

Страница 35: ...ulty Check the cabling Check the spark plug cap Replace the ignition unit Gas air adjustment NOT correctly set Check the adjustment See To check the CO setting 429 Fan faulty Check the wiring Check th...

Страница 36: ...l min is recommended Increase the domestic hot water setpoint on the domestic hot water homepage of the user interface 12 4 Solving problems based on error codes If the unit runs into a problem the us...

Страница 37: ...xplaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Maintenance instructions Instruction...

Страница 38: ...ponents 14 1 1 Components Gas boiler i j c q d o g h n m p s e a f t b r l k a Gas valve b Boiler control panel c Sensor S1 d Sensor S2 e Fan f Flow sensor g Space heating pressure sensor h Mains lead...

Страница 39: ...Main power supply 2 L BRN 4 N BLU X3 Power supply fan 230 V X5 Boiler communication cable X7 Sensor connection 14 3 Technical specifications 14 3 1 Technical specifications Gas boiler General EHYKOMB3...

Страница 40: ...cuit 3 bar Maximum space heating water temperature 90 bar Nominal load upper value Qn Hs 8 4 36 3 kW Nominal load lower value Qn Hi 7 6 32 7 kW Output at 80 60 C Pn 7 4 32 0 kW Nominal output 8 3 32 0...

Страница 41: ...G25 20 25 mbar G31 37 mbar United Kingdom GB II2H3P G20 20 mbar G31 37 mbar Greece GR II2H3P G20 20 mbar G31 37 mbar Croatia HR II2H3P G20 20 mbar G31 37 mbar Hungary HU I2H G20 25 mbar Ireland IE II2...

Страница 42: ...ned the boiler as a means of demonstrating compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference GAS BOILER SYSTEM COMMISSIONING CHECKLIST C...

Страница 43: ...ng co uk It is recommended that your heating system is serviced regularly and that the appropriate Service Interval Record is completed Service Provider SERVICE RECORD SERVICE 01 AND Where Possible AN...

Страница 44: ...88454708 4P353067 1K 2020 10 Copyright 2013 Daikin Verantwortung f r Energie und Umwelt...

Отзывы: