5 Piping installation

Installation manual

9

EA23DA6V(7)+9W
Daikin Altherma 3 H F
4P556073-1A – 2021.09

NOTICE

Overpressure bypass valve

 (delivered as accessory). We

recommend to install the overpressure bypass valve in the
space heating water circuit.

▪ Mind  the  minimum  water  volume  when  choosing  the

installation  location  of  the  overpressure  bypass  valve
(at  the  indoor  unit,  or  at  the  collector).  See 

"5.1.1  To

check the water volume and flow rate"

 [

4

 8].

▪ Mind  the  minimum  flow  rate  when  adjusting  the

overpressure  bypass  valve  setting.  See 

"5.1.1  To

check  the  water  volume  and  flow  rate"

  [

4

  8]  and

"8.2.1 To check the minimum flow rate"

 [

4

 25].

NOTICE

If you install this unit as a single-zone application, then:

Setup.

  Install  a  bypass  between  the  space  heating  water

inlet  and  outlet  of  the  additional  zone  (=direct  zone).  Do
NOT interrupt the water flow by closing the shut-off valves.

a

a

 Bypass

Configuration.

  Set  field  setting  [7-02]=0  (

Number  of

zones

 = 

Single zone

).

NOTICE

Install air purge valves at all local high points.

NOTICE

A  pressure  relief  valve  (field  supply)  with  an  opening
pressure  of  maximum  10  bar  (=1  MPa)  must  be  installed
on the domestic cold water inlet connection in accordance
with the applicable legislation.

5.2.2

To connect the recirculation piping

Prerequisite: 

Only required if you need recirculation in your system.

1

Remove  the  top  panel  from  the  unit,  see 

"4.2.1  To  open  the

indoor unit"

 [

4

 5].

2

Cut out the rubber grommet on top of the unit, and remove the
stop. The recirculation connector is placed below the hole.

3

Route the recirculation piping through the grommet and connect
it to the recirculation connector.

4

Reattach the top panel.

5.2.3

To fill the water circuit

To  fill  the  water  circuit,  use  a  field  supply  filling  kit.  Make  sure  you
comply with the applicable legislation.

NOTICE

Make sure both air purge valves (one on the magnetic filter
and one on the backup heater) are open.

All  automatic  air  purge  valves  MUST  remain  open  after
commissioning.

5.2.4

To protect the water circuit against
freezing

About freeze protection

Frost can damage the system. To prevent the hydraulic components
from  freezing,  the  software  is  equipped  with  special  frost  protection
functions such as water pipe freeze prevention and drain prevention
(see the installer reference guide) that include the activation of pump
in case of low temperatures.

However,  in  case  of  a  power  failure,  these  functions  cannot
guarantee protection.

Do one of the following to protect the water circuit against freezing:

▪ Add  glycol  to  the  water.  Glycol  lowers  the  freezing  point  of  the

water.

▪ Install freeze protection valves. Freeze protection valves drain the

water  from  the  system  before  it  can  freeze.  Insulate  the  freeze
protection valves in a similar way as the water piping, but do NOT
insulate the inlet and outlet (release) of these valves.

NOTICE

If  you  add  glycol  to  the  water,  do  NOT  install  freeze
protection  valves. 

Possible  consequence: 

Glycol  leaking

out of the freeze protection valves.

Freeze protection by glycol

About freeze protection by glycol

Adding glycol to the water lowers the freezing point of water.

WARNING

Ethylene glycol is toxic.

WARNING

Due  to  the  presence  of  glycol,  corrosion  of  the  system  is
possible.  Uninhibited  glycol  will  turn  acidic  under  the
influence  of  oxygen.  This  process  is  accelerated  by  the
presence  of  copper  and  high  temperatures.  The  acidic
uninhibited  glycol  attacks  metal  surfaces  and  forms
galvanic  corrosion  cells  that  cause  severe  damage  to  the
system. Therefore it is important that:

▪ the water treatment is correctly executed by a qualified

water specialist,

▪ a  glycol  with  corrosion  inhibitors  is  selected  to

counteract acids formed by the oxidation of glycols,

▪ no  automotive  glycol  is  used  because  their  corrosion

inhibitors  have  a  limited  lifetime  and  contain  silicates
which can foul or plug the system,

▪ galvanized pipes are NOT used in glycol systems since

the  presence  may  lead  to  the  precipitation  of  certain
components in the glycol's corrosion inhibitor.

Содержание Altherma 3 H F

Страница 1: ...Installation manual Daikin Altherma 3 H F English Installation manual Daikin Altherma 3 H F EAVZ16S18DA6V 7 EAVZ16S23DA6V 7 EAVZ16S18DA9W EAVZ16S23DA9W...

Страница 2: ...souladu s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na i...

Страница 3: ...ge 17 7 2 2 Configuration wizard Time and date 17 7 2 3 Configuration wizard System 17 7 2 4 Configuration wizard Backup heater 18 7 2 5 Configuration wizard Main zone 19 7 2 6 Configuration wizard Ad...

Страница 4: ...iping installation 48 WARNING Field piping method MUST be in accordance with the instructions from this manual See 5 Piping installation 48 WARNING Ethylene glycol is toxic WARNING Due to the presence...

Страница 5: ...heater 4 1 1 Installation site requirements of the indoor unit The indoor unit is designed for indoor installation only and for the following ambient temperatures Space heating operation 5 30 C Space...

Страница 6: ...ng cases 4 2 2 To lower the switch box on the indoor unit 46 4 3 2 To connect the drain hose to the drain 47 When you need access to the high voltage switch box 2 T25 5 If you need access to the high...

Страница 7: ...hose to the drain See 4 3 2 To connect the drain hose to the drain 47 3 Slide the indoor unit into position 4 Adjust the height of the leveling feet to compensate for floor irregularities The maximum...

Страница 8: ...ntrolled valves it is important that the minimum flow rate is guaranteed even if all valves are closed In case the minimum flow rate cannot be reached a flow error 7H will be generated no heating or o...

Страница 9: ...en All automatic air purge valves MUST remain open after commissioning 5 2 4 To protect the water circuit against freezing About freeze protection Frost can damage the system To prevent the hydraulic...

Страница 10: ...e maximum allowed water volume Adding glycol to the water circuit reduces the maximum allowed water volume of the system For more information see the installer reference guide topic To check the water...

Страница 11: ...mA b Field supplied components 11 Shut off valve 2 100 mA b 12 Electricity meter 2 per meter b 13 Domestic hot water pump 2 b 14 Alarm output 2 b 15 Changeover to external heat source control 2 b Item...

Страница 12: ...ables 6 3 3 To connect the main power supply 1 Connect the main power supply In case of normal kWh rate power supply X1M X2M X5M A5P X11YB X1A 1 2 3 1 2 3 a X11Y X11YA 1 2 3 a Interconnection cable ma...

Страница 13: ...l Technical Standard setting the limits for voltage changes voltage fluctuations and flicker in public low voltage supply systems for equipment with rated current 75 A provided that the system impedan...

Страница 14: ...to the appropriate terminals as shown in the illustration below X1M X2M X5M 1 M M2P 1 2 2 Fix the cable with cable ties to the cable tie mountings 6 3 8 To connect the alarm output 1 Connect the alar...

Страница 15: ...is too high the contact will open and the user interface will show a 8H 02 error ONLY the main pump will stop Additional zone 3 Connect the safety thermostat normally closed cable to the appropriate...

Страница 16: ...access the installer settings using two different methods However NOT all settings are accessible via both methods If so the corresponding table columns in this chapter are set to N A not applicable...

Страница 17: ...r interface For units with a built in backup heater the type of heater can be viewed but not changed Code Description 9 3 1 E 03 3 6V 4 9W Domestic hot water The following setting determines if the sy...

Страница 18: ...European electricity grids If the backup heater is available the voltage configuration and capacity must be set on the user interface The capacities for the different steps of the backup heater must...

Страница 19: ...55 C Variable 1 Fancoil unit Maximum 55 C Variable 2 Radiator Maximum 65 C Fixed 8 C NOTICE Average emitter temperature Leaving water temperature Delta T 2 This means that for a same leaving water te...

Страница 20: ...the scheduled heat up cycles reheat operation is allowed 2 Schedule only The domestic hot water tank can ONLY be heated according to a schedule See the operation manual for more details Comfort setpoi...

Страница 21: ...curves 422 7 3 2 2 points curve Define the weather dependent curve with these two setpoints Setpoint X1 Y2 Setpoint X2 Y1 Example Y1 Y2 X1 X2 a Item Description a Selected weather dependent zone Main...

Страница 22: ...g Go to setpoint mode Set the setpoint mode to 3 4 Additional zone Setpoint mode WD heating fixed cooling OR Weather dependent Additional zone Cooling 3 4 Additional zone Setpoint mode Weather depende...

Страница 23: ...at indoor unit b External room thermostat at main zone c External room thermostat at additional zone NOTICE If an external room thermostat is used the external room thermostat will control the room f...

Страница 24: ...2 Capacity step 1 Equilibrium Equilibrium temperature Operation 9 6 Balancing Space heating priority Priority temperature Offset BSH setpoint Minimum running timer Anti recycle timer Maximum running t...

Страница 25: ...oltage on the identification label of the unit There are NO loose connections or damaged electrical components in the switch box There are NO damaged components or squeezed pipes on the inside of the...

Страница 26: ...correct operation of the unit can be checked by monitoring its leaving water temperature heating cooling mode and tank temperature domestic hot water mode To monitor the temperatures 1 In the menu go...

Страница 27: ...result in cracking of the screed NOTICE For the underfloor heating screed dryout to be able to start make sure the following settings are met 4 00 1 C 02 0 D 01 0 4 08 0 4 01 1 9 Hand over to the user...

Страница 28: ...rew connection 1 p Water filter main mixed zone b1 Space heating main mixed zone Water IN screw connection 1 q Loose nut 1 b2 Space heating main mixed zone Water OUT screw connection 1 B1L Flow sensor...

Страница 29: ...n OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box English Translation Position in switch box Positi...

Страница 30: ...ad Maximum load Normally closed Normally closed Normally open Normally open Safety thermostat Safety thermostat English Translation Safety thermostat contact 16 V DC detection voltage supplied by PCB...

Страница 31: ...uded signal A13P P1 P2 LAN adapter A14P P1 P2 user interface communication 2 core communication 2 core 4 core 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H...

Страница 32: ...4P556073 1A 2021 09 Copyright 2018 Daikin 4P556073 1 A 0000000 Verantwortung f r Energie und Umwelt...

Отзывы: