background image

7 Configuration

Installation manual

19

EA23DA6V(7)+9W
Daikin Altherma 3 H F
4P556073-1A – 2021.09

INFORMATION

Only for systems with integrated domestic hot water tank: If
the  storage  temperature  setpoint  is  higher  than  50°C,
Daikin  recommends  NOT  to  disable  the  backup  heater
second  step  because  it  will  have  a  big  impact  on  the
required time for the unit to heat up the domestic hot water
tank.

Capacity step 1

#

Code

Description

[9.3.4]

[6‑03]

▪ The  capacity  of  the  first  step  of  the

backup heater at nominal voltage.

Additional capacity step 2

#

Code

Description

[9.3.5]

[6‑04]

▪ The  capacity  difference  between  the

second  and  first  step  of  the  backup
heater  at  nominal  voltage.  Nominal
value  depends  on  backup  heater
configuration.

7.2.5

Configuration wizard: Main zone

The most important settings for the main leaving water zone can be
set here.

Emitter type

Depending on the system water volume and the heater emitter type
of the main zone, the heat up or cooling down of the main zone can
take  longer.  This  setting  can  compensate  for  a  slow  or  a  quick
heating/cooling  system  during  the  heat  up/cool  down  cycle  (cooling
only with EKHVCONV2 installed).

The  target  delta  T  for  the  main  zone  will  depend  on  this  setting.
Target delta T control is only possible in case only 1 zone is active.
Pump control will be different when both zones are active.

In room thermostat control, this setting will influence:

▪ the  maximum  modulation  of  the  desired  leaving  water

temperature.

▪ the  possibility  for  usage  of  the  automatic  cooling/heating

changeover  based  on  the  indoor  ambient  temperature  (only  with
EKHVCONV2 installed).

Therefore it is important to set this correctly and in accordance with
your system layout.

#

Code

Description

[2.7]

[2‑0C]

▪ 0: 

Underfloor heating

▪ 1: 

Fancoil unit

▪ 2: 

Radiator

The setting of the emitter type has an influence on the space heating
setpoint range and the target delta T in heating as follows:

Description

Space heating

setpoint range

Target delta T in

heating

0: 

Underfloor

heating

Maximum 55°C

Variable

1: 

Fancoil unit

Maximum 55°C

Variable

2: 

Radiator

Maximum 65°C

Fixed 8°C

NOTICE

Average 

emitter 

temperature

 

Leaving 

water

temperature – (Delta T)/2

This  means  that  for  a  same  leaving  water  temperature
setpoint,  the  average  emitter  temperature  of  radiators  is
lower  than  that  of  underfloor  heating  because  of  a  bigger
delta T.

Example radiators: 40–8/2=

36°C

Example underfloor heating: 40–5/2=

37.5°C

To compensate, you can:

▪ Increase 

the 

weather-dependent 

curve 

desired

temperatures [2.5].

▪ Enable  leaving  water  temperature  modulation  and

increase the maximum modulation [2.C].

Control

Define how the operation of the unit is controlled.

Control

In this control...

Leaving water

Unit operation is decided based on the leaving
water temperature regardless the actual room
temperature and/or heating or cooling demand
of the room.

External room
thermostat

Unit operation is decided by the external
thermostat or equivalent (e.g. heat pump
convector).

Room thermostat

Unit operation is decided based on the ambient
temperature of the user interface used as a
room thermostat.

#

Code

Description

[2.9]

[C‑07]

▪ 0: 

Leaving water

▪ 1: 

External room thermostat

▪ 2: 

Room thermostat

Setpoint mode

Define the setpoint mode:

Fixed

: the desired leaving water temperature does not depend on

the outdoor ambient temperature.

▪ In 

WD heating, fixed cooling

 mode, the desired leaving water

temperature:

▪ depends on the outdoor ambient temperature for heating

▪ does  NOT  depend  on  the  outdoor  ambient  temperature  for

cooling

▪ In 

Weather 

dependent

  mode,  the  desired  leaving  water

temperature depends on the outdoor ambient temperature.

#

Code

Description

[2.4]

N/A

Setpoint mode

▪ 0: 

Fixed

▪ 1: 

WD  heating,  fixed  cooling

(only with EKHVCONV* installed)

▪ 2: 

Weather dependent

When  weather  dependent  operation  is  active,  low  outdoor
temperatures  will  result  in  warmer  water  and  vice  versa.  During
weather  dependent  operation,  the  user  can  shift  the  water
temperature up or down by a maximum of 10°C.

Schedule

Indicates  if  the  desired  leaving  water  temperature  is  according  to  a
schedule. Influence of the LWT setpoint mode [2.4] is as follows:

▪ In 

Fixed

  LWT  setpoint  mode,  the  scheduled  actions  consist  of

desired leaving water temperatures, either preset or custom.

Содержание Altherma 3 H F

Страница 1: ...Installation manual Daikin Altherma 3 H F English Installation manual Daikin Altherma 3 H F EAVZ16S18DA6V 7 EAVZ16S23DA6V 7 EAVZ16S18DA9W EAVZ16S23DA9W...

Страница 2: ...souladu s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na i...

Страница 3: ...ge 17 7 2 2 Configuration wizard Time and date 17 7 2 3 Configuration wizard System 17 7 2 4 Configuration wizard Backup heater 18 7 2 5 Configuration wizard Main zone 19 7 2 6 Configuration wizard Ad...

Страница 4: ...iping installation 48 WARNING Field piping method MUST be in accordance with the instructions from this manual See 5 Piping installation 48 WARNING Ethylene glycol is toxic WARNING Due to the presence...

Страница 5: ...heater 4 1 1 Installation site requirements of the indoor unit The indoor unit is designed for indoor installation only and for the following ambient temperatures Space heating operation 5 30 C Space...

Страница 6: ...ng cases 4 2 2 To lower the switch box on the indoor unit 46 4 3 2 To connect the drain hose to the drain 47 When you need access to the high voltage switch box 2 T25 5 If you need access to the high...

Страница 7: ...hose to the drain See 4 3 2 To connect the drain hose to the drain 47 3 Slide the indoor unit into position 4 Adjust the height of the leveling feet to compensate for floor irregularities The maximum...

Страница 8: ...ntrolled valves it is important that the minimum flow rate is guaranteed even if all valves are closed In case the minimum flow rate cannot be reached a flow error 7H will be generated no heating or o...

Страница 9: ...en All automatic air purge valves MUST remain open after commissioning 5 2 4 To protect the water circuit against freezing About freeze protection Frost can damage the system To prevent the hydraulic...

Страница 10: ...e maximum allowed water volume Adding glycol to the water circuit reduces the maximum allowed water volume of the system For more information see the installer reference guide topic To check the water...

Страница 11: ...mA b Field supplied components 11 Shut off valve 2 100 mA b 12 Electricity meter 2 per meter b 13 Domestic hot water pump 2 b 14 Alarm output 2 b 15 Changeover to external heat source control 2 b Item...

Страница 12: ...ables 6 3 3 To connect the main power supply 1 Connect the main power supply In case of normal kWh rate power supply X1M X2M X5M A5P X11YB X1A 1 2 3 1 2 3 a X11Y X11YA 1 2 3 a Interconnection cable ma...

Страница 13: ...l Technical Standard setting the limits for voltage changes voltage fluctuations and flicker in public low voltage supply systems for equipment with rated current 75 A provided that the system impedan...

Страница 14: ...to the appropriate terminals as shown in the illustration below X1M X2M X5M 1 M M2P 1 2 2 Fix the cable with cable ties to the cable tie mountings 6 3 8 To connect the alarm output 1 Connect the alar...

Страница 15: ...is too high the contact will open and the user interface will show a 8H 02 error ONLY the main pump will stop Additional zone 3 Connect the safety thermostat normally closed cable to the appropriate...

Страница 16: ...access the installer settings using two different methods However NOT all settings are accessible via both methods If so the corresponding table columns in this chapter are set to N A not applicable...

Страница 17: ...r interface For units with a built in backup heater the type of heater can be viewed but not changed Code Description 9 3 1 E 03 3 6V 4 9W Domestic hot water The following setting determines if the sy...

Страница 18: ...European electricity grids If the backup heater is available the voltage configuration and capacity must be set on the user interface The capacities for the different steps of the backup heater must...

Страница 19: ...55 C Variable 1 Fancoil unit Maximum 55 C Variable 2 Radiator Maximum 65 C Fixed 8 C NOTICE Average emitter temperature Leaving water temperature Delta T 2 This means that for a same leaving water te...

Страница 20: ...the scheduled heat up cycles reheat operation is allowed 2 Schedule only The domestic hot water tank can ONLY be heated according to a schedule See the operation manual for more details Comfort setpoi...

Страница 21: ...curves 422 7 3 2 2 points curve Define the weather dependent curve with these two setpoints Setpoint X1 Y2 Setpoint X2 Y1 Example Y1 Y2 X1 X2 a Item Description a Selected weather dependent zone Main...

Страница 22: ...g Go to setpoint mode Set the setpoint mode to 3 4 Additional zone Setpoint mode WD heating fixed cooling OR Weather dependent Additional zone Cooling 3 4 Additional zone Setpoint mode Weather depende...

Страница 23: ...at indoor unit b External room thermostat at main zone c External room thermostat at additional zone NOTICE If an external room thermostat is used the external room thermostat will control the room f...

Страница 24: ...2 Capacity step 1 Equilibrium Equilibrium temperature Operation 9 6 Balancing Space heating priority Priority temperature Offset BSH setpoint Minimum running timer Anti recycle timer Maximum running t...

Страница 25: ...oltage on the identification label of the unit There are NO loose connections or damaged electrical components in the switch box There are NO damaged components or squeezed pipes on the inside of the...

Страница 26: ...correct operation of the unit can be checked by monitoring its leaving water temperature heating cooling mode and tank temperature domestic hot water mode To monitor the temperatures 1 In the menu go...

Страница 27: ...result in cracking of the screed NOTICE For the underfloor heating screed dryout to be able to start make sure the following settings are met 4 00 1 C 02 0 D 01 0 4 08 0 4 01 1 9 Hand over to the user...

Страница 28: ...rew connection 1 p Water filter main mixed zone b1 Space heating main mixed zone Water IN screw connection 1 q Loose nut 1 b2 Space heating main mixed zone Water OUT screw connection 1 B1L Flow sensor...

Страница 29: ...n OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box English Translation Position in switch box Positi...

Страница 30: ...ad Maximum load Normally closed Normally closed Normally open Normally open Safety thermostat Safety thermostat English Translation Safety thermostat contact 16 V DC detection voltage supplied by PCB...

Страница 31: ...uded signal A13P P1 P2 LAN adapter A14P P1 P2 user interface communication 2 core communication 2 core 4 core 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H...

Страница 32: ...4P556073 1A 2021 09 Copyright 2018 Daikin 4P556073 1 A 0000000 Verantwortung f r Energie und Umwelt...

Отзывы: