6 Electrical installation

Installation manual

14

EA23DA6V(7)+9W

Daikin Altherma 3 H F

4P556073-1A – 2021.09

NOTICE

Do  NOT  cut  or  remove  the  backup  heater  power  supply
cable.

6.3.5

To connect the shut-off valve

1

Connect the valve control cable to the appropriate terminals as
shown in the illustration below.

NOTICE

Wiring  is  different  for  a  NC  (normally  closed)  valve  and  a
NO (normally open) valve.

X1M

X2M

X1M

X2M

NO

M2S

NC

M2S

21 28

21 29

2

Fix the cable with cable ties to the cable tie mountings.

6.3.6

To connect the electricity meters

INFORMATION

In case of an electricity meter with transistor output, check
the  polarity.  The  positive  polarity  MUST  be  connected  to
X5M/6  and  X5M/4;  the  negative  polarity  to  X5M/5  and
X5M/3.

1

Connect the electricity meters cable to the appropriate terminals
as shown in the illustration below.

X1M

X2M

X5M

S3S S2S

3456

2

Fix the cable with cable ties to the cable tie mountings.

6.3.7

To connect the domestic hot water pump

1

Connect the domestic hot water pump cable to the appropriate
terminals as shown in the illustration below.

X1M

X2M

X5M

1~

M

M2P

1 2

2

Fix the cable with cable ties to the cable tie mountings.

6.3.8

To connect the alarm output

1

Connect the alarm output cable to the appropriate terminals as
shown in the illustration below.

X2M

X5M

X1M

A5P

A4P

YC
Y1

Y2
Y3

Y4

X1M

Y1

YC

7 9

a

b

a

Installation of EKRP1HBAA is required.

b

Prewiring between X2M/7+9 and Q1L (= thermal
protector backup heater). Do NOT change.

2

Fix the cable with cable ties to the cable tie mountings.

6.3.9

To connect the space cooling/heating ON/
OFF output

INFORMATION

Cooling  is  only  applicable  in  case  a  conversion  kit
(EKHVCONV*) is installed.

1

Connect the space cooling/heating ON/OFF output cable to the
appropriate terminals as shown in the illustration below.

X2M

X5M

X1M

A5P

A4P

YC
Y1

Y2
Y3

Y4

X2 X1

X2M

X1M

X4 X3

a

b

Y2

YC

7 9

a

Installation of EKRP1HBAA is required.

b

Prewiring between X2M/7+9 and Q1L (= thermal
protector backup heater). Do NOT change.

2

Fix the cable with cable ties to the cable tie mountings.

6.3.10

To connect the changeover to external
heat source

1

Connect  the  changeover  to  external  heat  source  cable  to  the
appropriate terminals as shown in the illustration below.

Содержание Altherma 3 H F

Страница 1: ...Installation manual Daikin Altherma 3 H F English Installation manual Daikin Altherma 3 H F EAVZ16S18DA6V 7 EAVZ16S23DA6V 7 EAVZ16S18DA9W EAVZ16S23DA9W...

Страница 2: ...souladu s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na i...

Страница 3: ...ge 17 7 2 2 Configuration wizard Time and date 17 7 2 3 Configuration wizard System 17 7 2 4 Configuration wizard Backup heater 18 7 2 5 Configuration wizard Main zone 19 7 2 6 Configuration wizard Ad...

Страница 4: ...iping installation 48 WARNING Field piping method MUST be in accordance with the instructions from this manual See 5 Piping installation 48 WARNING Ethylene glycol is toxic WARNING Due to the presence...

Страница 5: ...heater 4 1 1 Installation site requirements of the indoor unit The indoor unit is designed for indoor installation only and for the following ambient temperatures Space heating operation 5 30 C Space...

Страница 6: ...ng cases 4 2 2 To lower the switch box on the indoor unit 46 4 3 2 To connect the drain hose to the drain 47 When you need access to the high voltage switch box 2 T25 5 If you need access to the high...

Страница 7: ...hose to the drain See 4 3 2 To connect the drain hose to the drain 47 3 Slide the indoor unit into position 4 Adjust the height of the leveling feet to compensate for floor irregularities The maximum...

Страница 8: ...ntrolled valves it is important that the minimum flow rate is guaranteed even if all valves are closed In case the minimum flow rate cannot be reached a flow error 7H will be generated no heating or o...

Страница 9: ...en All automatic air purge valves MUST remain open after commissioning 5 2 4 To protect the water circuit against freezing About freeze protection Frost can damage the system To prevent the hydraulic...

Страница 10: ...e maximum allowed water volume Adding glycol to the water circuit reduces the maximum allowed water volume of the system For more information see the installer reference guide topic To check the water...

Страница 11: ...mA b Field supplied components 11 Shut off valve 2 100 mA b 12 Electricity meter 2 per meter b 13 Domestic hot water pump 2 b 14 Alarm output 2 b 15 Changeover to external heat source control 2 b Item...

Страница 12: ...ables 6 3 3 To connect the main power supply 1 Connect the main power supply In case of normal kWh rate power supply X1M X2M X5M A5P X11YB X1A 1 2 3 1 2 3 a X11Y X11YA 1 2 3 a Interconnection cable ma...

Страница 13: ...l Technical Standard setting the limits for voltage changes voltage fluctuations and flicker in public low voltage supply systems for equipment with rated current 75 A provided that the system impedan...

Страница 14: ...to the appropriate terminals as shown in the illustration below X1M X2M X5M 1 M M2P 1 2 2 Fix the cable with cable ties to the cable tie mountings 6 3 8 To connect the alarm output 1 Connect the alar...

Страница 15: ...is too high the contact will open and the user interface will show a 8H 02 error ONLY the main pump will stop Additional zone 3 Connect the safety thermostat normally closed cable to the appropriate...

Страница 16: ...access the installer settings using two different methods However NOT all settings are accessible via both methods If so the corresponding table columns in this chapter are set to N A not applicable...

Страница 17: ...r interface For units with a built in backup heater the type of heater can be viewed but not changed Code Description 9 3 1 E 03 3 6V 4 9W Domestic hot water The following setting determines if the sy...

Страница 18: ...European electricity grids If the backup heater is available the voltage configuration and capacity must be set on the user interface The capacities for the different steps of the backup heater must...

Страница 19: ...55 C Variable 1 Fancoil unit Maximum 55 C Variable 2 Radiator Maximum 65 C Fixed 8 C NOTICE Average emitter temperature Leaving water temperature Delta T 2 This means that for a same leaving water te...

Страница 20: ...the scheduled heat up cycles reheat operation is allowed 2 Schedule only The domestic hot water tank can ONLY be heated according to a schedule See the operation manual for more details Comfort setpoi...

Страница 21: ...curves 422 7 3 2 2 points curve Define the weather dependent curve with these two setpoints Setpoint X1 Y2 Setpoint X2 Y1 Example Y1 Y2 X1 X2 a Item Description a Selected weather dependent zone Main...

Страница 22: ...g Go to setpoint mode Set the setpoint mode to 3 4 Additional zone Setpoint mode WD heating fixed cooling OR Weather dependent Additional zone Cooling 3 4 Additional zone Setpoint mode Weather depende...

Страница 23: ...at indoor unit b External room thermostat at main zone c External room thermostat at additional zone NOTICE If an external room thermostat is used the external room thermostat will control the room f...

Страница 24: ...2 Capacity step 1 Equilibrium Equilibrium temperature Operation 9 6 Balancing Space heating priority Priority temperature Offset BSH setpoint Minimum running timer Anti recycle timer Maximum running t...

Страница 25: ...oltage on the identification label of the unit There are NO loose connections or damaged electrical components in the switch box There are NO damaged components or squeezed pipes on the inside of the...

Страница 26: ...correct operation of the unit can be checked by monitoring its leaving water temperature heating cooling mode and tank temperature domestic hot water mode To monitor the temperatures 1 In the menu go...

Страница 27: ...result in cracking of the screed NOTICE For the underfloor heating screed dryout to be able to start make sure the following settings are met 4 00 1 C 02 0 D 01 0 4 08 0 4 01 1 9 Hand over to the user...

Страница 28: ...rew connection 1 p Water filter main mixed zone b1 Space heating main mixed zone Water IN screw connection 1 q Loose nut 1 b2 Space heating main mixed zone Water OUT screw connection 1 B1L Flow sensor...

Страница 29: ...n OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box English Translation Position in switch box Positi...

Страница 30: ...ad Maximum load Normally closed Normally closed Normally open Normally open Safety thermostat Safety thermostat English Translation Safety thermostat contact 16 V DC detection voltage supplied by PCB...

Страница 31: ...uded signal A13P P1 P2 LAN adapter A14P P1 P2 user interface communication 2 core communication 2 core 4 core 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H...

Страница 32: ...4P556073 1A 2021 09 Copyright 2018 Daikin 4P556073 1 A 0000000 Verantwortung f r Energie und Umwelt...

Отзывы: