Taking out of operation
Installation and maintenance instructions
55
Daikin Altherma EHS(X/H)(B)-D
Heat pump (indoor unit) with integrated heat accumulator
008.1444099_01 – 11/2018 – EN
Fig. 9-3
Completing the combined filling and draining filling con-
nection
Fig. 9-4
Screwing the combined filling and draining filling connec-
tion into the filling and draining connection
4
Open the combined filling and draining valve on the
combined
filling and draining filling connection
and drain the water con-
tent of the storage tank.
Only with
solar system:
1
Adjust the valve insert on the connection bracket so that the path
to the blind plug is blocked off (
Fig. 9-6
).
2
Place a suitable collecting tray and remove the blind plug from
the connection bracket (
Fig. 9-6
).
Fig. 9-5
Shut off the valve insert, remove the blind plug from the
connection bracket
3
Insert the
combined filling and draining filling connection
in
the connection bracket and secure with the holding clamp
(
Fig. 9-6
).
Fig. 9-6
Installing the combined filling and draining filling connec-
tion in the connection bracket
4
Open the combined filling and draining valve on the
combined
filling and draining filling connection
.
5
Adjust the valve insert on the connection bracket so that the path
to the drain hose is open (see also
Fig. 9-5
) and drain the water
content of the storage tank.
9.1.2
Draining the heating circuit and hot water
circuit
1
Connect the drain hose to the KFE cock of the indoor unit.
2
Open the KFE cock on the indoor unit.
3
Drain the heating and hot water circuits.
4
Disconnect the heating flow and return and the cold water feed
and hot water discharge from the indoor unit.
5
Connect the discharge hose on the heating inflow and return
flow as well as the cold water inflow and hot water outflow so
that the hose opening is at ground level.
6
Allow the individual heat exchangers to run empty one after the
other according to the siphon lifting principle.
9.2
Final shutdown and disposal
CAUTION
Refrigerant leaking from the system causes long-term
damage to the environment.
Mixing different kinds of refrigerant can result in hazardous
toxic gases being released. Mixing with oils can lead to the
soil being contaminated in case of leaking refrigerant.
▪ Never allow refrigerant to escape into the atmosphere -
always extract and recycle with a suitable recycling
device.
▪ Always recycle refrigerant, thus keeping it separated
from oils and other additives.
▪ Only keep each type of refrigerant separate in suitable
pressure vessels.
▪ Dispose of refrigerants, oils and additives properly and
in accordance with the applicable national regulations of
the country it is being used in.
For final shutdown of the indoor unit
1
taken out of service (see
Chap. 9.1
),
2
disconnected from all electrical, oil and water connections,