22
Operating
Pr
ocedure
Handling
1·6
2·4
2·4
3·5
Data display
Operation mode
display
Operation mode
indicator
Factory setting
(With non-standard models, the settings
may be different from the above.)
Example) Capacity direct designation
(Capacity setting: 100%)
17
17
Cooling liquid in the tank at constant capacity (%)
With the above operation setting, the OILCON unit executes cooling operation according to the specified command value (%).
Therefore, tank liquid temperature control is disabled.
The capacity setting range is 0 to 100%.
∗
The capacity (%) is an approximate index.
∗
When the capacity is set to “0”%, the compressor stops. (The pump and fan are running.)
∗
Even if the capacity command value is the same, the actual cooling capacity varies depending on the room temperature and the tank liquid
temperature.
Operation mode: 9
Cooling the liquid in the tank
at constant capacity (%)
Setting procedure
• Go to the operation setting mode with the key.
See “
Mode changing operation
” on page .
• The “SETTING” lamp on the operation mode indicator lights.
∗
The number on the operation mode display blinks.
1. Select the operation setting mode.
When the number on the operation mode display is blinking,
change the number to “9” with the or key.
2. Change the operation mode.
After the number is registered, the number on the data display blinks.
∗
“9” on the operation mode display remains lit.
3. After changing the number, press the key
to register it.
After the temperature setting is registered, the number on the
operation mode display blinks.
∗
The number on the data display remains lit.
5. After changing the set value, press the key
to register it.
When the number on the data display is blinking, change the set
value to a desired capacity with the or key.
4. Change the set value.
• Press the key three times, to return to the normal mode.
See “
Mode changing operation
” on page .
• The “NORMAL” lamp on the operation mode indicator lights.
6. Return to the normal mode.
PIM00132A_EN.fm 22 ページ 2007年9月20日 木曜日 午後3時4分