20
IOM 1206-1
Field Wiring Diagram
Field Wiring Diagram
Figure 14: Typical Field Wiring Diagram
(Single-point connection)
NO
COM
BELL
LESS
EVAPORATOR
ONLY
N
24 VAC
N
24 VAC
LIQUID LINE #2
SOLENOID
24VAC 1.5 AMP MAX
LIQUID LINE #1
SOLENOID
24VAC 1.5 AMP MAX
4-20MA FOR
DEMAND LIMIT
(BY OTHERS)
4-20MA FOR
EVAP. WATER RESET
(BY OTHERS)
CHW FLOW SWITCH
-MANDATORY-
(BY OTHERS)
NOR. OPEN PUMP
AUX. CONTACTS
(OPTIONAL)
ICE MODE
SWITCH
(BY OTHERS)
TIME
CLOCK
OFF
MANUAL
ON
AUTO
585
IF REMOTE STOP
CONTROL IS USED
REMOVE LEAD 585
FROM TERM
TB2-52 TO TB2-72
TIME
CLOCK
OFF
MANUAL
ON
AUTO
CHW2
PUMP NO.2 RELAY
(BY OTHERS)
120VAC @ 1.0AMP MAX
93A
TB2
92
TB2
93A
TB2
91
TB2
71
TB2
70
TB2
69
TB2
68
TB2
61
TB2
TB1 22
TB1
1A
TO
COMPRESSOR(S)
AND FAN MOTORS
ALARM BELL
RELAY
120
VAC
FU5
T1
FU6
CONTROL CIRCUIT
FUSE
SEE NOTE 1
FU4
REMOTE
STOP SWITCH
(BY OTHERS)
TB2
TB2
43
83
ALARM BELL
OPTION
N
N
120 VAC
120 VAC
120 VAC
(FACTORY WIRING)
TB1
TB1
TB1
TB1
TB1
TB1
TB2
TB2
TB2
TB2
TB2
ALARM BELL
RELAY
44
54
52
34
P2+
CHW1
PUMP NO.1 RELAY
(BY OTHERS)
120VAC @ 1.0AMP MAX
35
74
72
32A
31
33
ALARM
BELL OPTION
3 PHASE
POWER
SOURCE
DISCONNECT SWITCH
OR
POWER BLOCK
DISCONNECT
(BY OTHERS)
1
2
TB2
TB2
45
67
EXTERNAL
ALARM/
EVENT
DISCONNECT
(BY OTHERS)
N
120 VAC
FIELD
SUPPLIED
OPTION
FU
15A for 1.5 KVA
30A for 3.0KVA
(BY OTHERS)
Notes:
1.) IF FIELD SUPPLIED, CONTROL
POWER USER MUST REMOVE
FU6, AND WIRE NUMBERS 299, 301A
INSIDE CONTROL PANEL
FIELD WIRING DIAGRAM
WITH MICROTECH CONTROLLER
301A
301
299
ABR
ABR
SV1
SV2
_
+
_
+
GND
(317)
T3
T2
T1
L3
L2
L1
PANEL