Overview
The MicroTech® III controller’s state-of-the-art design not
only permits the chiller to run more efficiently, but also can
simplify troubleshooting if a system failure occurs. Every
MicroTech IIII controller is programmed and tested prior to
shipment to facilitate start-up.
The controller menu structure is separated into three distinct
categories that provide the operator or service technician with
a full description of :
1
current unit status
2
control parameters
3
alarms. Security protection prevents unauthorized
changing of the setpoints and control parameters.
MicroTech III control continuously performs self-diagnostic
checks, monitoring system temperatures, pressures and
protection devices, and will automatically shut down a
compressor or the entire unit should a fault occur. The cause
of the shutdown will be retained in memory and can be easily
displayed in plain English for operator review. The MicroTech
III chiller controller will also retain and display the date/time
the fault occurred. In addition to displaying alarm diagnostics,
the MicroTech III chiller controller also provides the operator
with a warning of limit (pre-alarm) conditions.
Controller Inputs and Outputs
Main Controller
Table 21: Analog Inputs
Table 22: Analog Outputs
Table 23: Digital Inputs
Table 24: Digital Outputs
#
Description
Type
Expected Range
AI1
Evaporator EWT
NTC 10k
340 to 300k
Ω
AI2
Evaporator LWT
NTC 10k
340 to 300k
Ω
AI3
Outside Ambient
Temperature
NTC 10k
340 to 300k
Ω
X1
Demand Limit
4-20 mA
1 to 23 mA
X4
LWT Reset
4-20 mA
1 to 23 mA
#
Description
Output Type
Range
X5
Circuit 1 Fan VFD Speed
Voltage
0 to 10 volts
X6
Circuit 2 Fan VFD Speed
Voltage
0 to 10 volts
Description
Signal Off
Signal On
DI1 External Alarm/Event
External Fault
No External Fault
DI2 Evaporator Flow Switch
No Flow
Flow
DI3
Double Set Point/ Mode
Switch
See sections on Unit Mode Selection and LWT
Target
DI4 Remote Switch
Remote Disable
Remote Enable
DI5 Unit Switch
Unit Disable
Unit Enable
Description
Output Off
Output On
DO1
Evaporator Water Pump 1
Pump Off
Pump On
DO2
Alarm Indicator
Alarm Not Active
Alarm Active
DO3
Circuit 1 Fan Output 1
Fan(s) Off
Fan(s) On
DO4
Circuit 1 Fan Output 2
Fan(s) Off
Fan(s) On
DO5
Circuit 1 Fan Output 3
Fan(s) Off
Fan(s) On
DO6
Circuit 1 Fan Output 4
Fan(s) Off
Fan(s) On
DO7
Circuit 2 Fan Output 1
Fan(s) Off
Fan(s) On
DO8
Circuit 2 Fan Output 2
Fan(s) Off
Fan(s) On
DO9
Circuit 2 Fan Output 3
Fan(s) Off
Fan(s) On
DO10
Circuit 2 Fan Output 4
Fan(s) Off
Fan(s) On