Installation and operation manual
15
FWEC3
Advanced plus electronic controller
FC66002765
DESCRIPTION OF READ/WRITE REGISTERS [R/W]
■
“Digital 1”
Register
:
H
Bit 15
Bit 14
Bit 13
Bit 12
Bit 11
Bit 10
Bit 9
Bit 8
En.Vel
En.Min/
Max
En.Set
En.MinT En.ECO
En.RE
En.S/W
En.On/
Off
L
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
-
-
Lock
MinT
Eco
RE
S/W
On/Off
-
On/Off
: On/Off via supervision system
-
S/W
: selection of operating mode via supervision system
(0: Cooling, 1: Heating); N.B.: if the unit con
fi
guration
(parameter
P00
) provides for summer/winter changeover
based on water or air temperature, the resulting mode
selection will override the command from the supervision
system (which is thus substantially ignored))
-
RE
: selection of Electrical heater via supervision system
-
Eco
: Economy mode ON via supervision system
-
MinT
.: enabling of Minimum Temperature control via
supervision system; N.B.: actual activation remains at
the local discretion of each fan-coil unit based on the air
temperature probe reading
-
Lock
: keypad lock (0: unlocked, 1: locked)
-
En.On/Off
: enabling of On/Off control via supervision
system
-
En.S/W
: enabling of mode control via supervision system
-
En.RE
: enabling of selection of electrical heater function
via supervision system
-
En.ECO
: enabling of economy mode activation via super-
vision system
-
En.MinT
: enabling of selection of Minimum Temperature
logic via supervision system
-
En.Set
: enabling of forced override of setpoint via super-
vision system
-
En.Min/Max
: enabling of setpoint thresholds via supervi-
sion system
-
En.Vel
: enabling of selection of fan speed via supervision
system
■
“
Scheduling
” register: ON/OFF time programming via
supervision system
- 0: scheduling disabled
- 1: scheduling enabled for ON/OFF
- 2: scheduling enabled with SETPOINT
■
“
Cooling - Setpoint
” Register: setpoint imposed by su-
pervision system for the Cooling mode
■
“
Heating - Setpoint
” Register: setpoint imposed by su-
pervision system for the Heating mode
■
“
Minimum Setpoint – Cool.
” Register: lower limit for
setpoint in cooling mode
■
“
Maximum Setpoint – Cool.
” Register: upper limit for
setpoint in cooling mode
■
“
Minimum Setpoint – Heat.
” Register: lower limit for
setpoint in heating mode
■
“
Maximum Setpoint – Heat.
” Register: upper limit for
setpoint in heating mode
■
“
Speed
” Register: selection of fan speed via supervision
system; in the case of modulating fan control, it expresses
the percentage of speed used in the manual mode
■
“
Economy Correction
” Register: correction of setpoint in
the case of economy mode imposed by supervisor (this
correction is an amount subtracted from or added to the
setpoint, based on the operating mode)
■
“
Modulating fan mode
” Register: selection of the mode in
the case of modulating fan control: 0 = fan OFF; 1=manually
forced fan operation ; 2=automatic fan operation
DESCRIPTION OF READ-ONLY REGISTERS [R]
■
“Status”
Register
H
Bit 15
Bit 14
Bit 13
Bit 12
Bit 11
Bit 10
Bit 9
Bit 8
DOUT2 DOUT1
P04
Deum
P07
P06
DI2
DI1
L
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Vh
Vc
Alarm
MinT
Eco
P01
S/W
On/Off
-
On/Off
: unit status (0: Off, 1=On)
-
S/W
: operation mode (0: S=cooling, 1:W=heating);
-
P01
: “on unit/wall-mounted” parameter
-
Eco
: Economy logic active
-
Min.T
: Minimum Temperature logic selected
-
Alarm
: general alarm indication (activated when any of
the managed alarms is triggered)
-
Vc
status of digital output Vc
-
Vh
: status of digital output Vh
-
DI1
: logical value of dig. input 1 (the physical status of the
input depends on the associated logic)
-
DI2
: logical value of dig. input 2 (the physical status of the
input depends on the associated logic)
-
P07
: “DIN 2 Logic” parameter
-
P06
: “DIN 1 Logic” parameter
-
Dehum
: dehumidi
fi
cation ON (0:no, 1:yes)
-
P04
: “water probe present” parameter
-
DOUT1
: Digital Input 1 status
-
DOUT2
: Digital Input 2 status
■
“Speed”
Register
:
current operating speed of the indoor
unit
- 0: fan off
- 1: extra-low speed
- 2: low speed
- 3: medium speed
- 4: high speed
■
“
Air Temperature
” register: room temperature read by
the controller and shown on the display (N.B.: this tem-
perature corresponds to the reading of the remote probe
if the controller is located on the unit, or the reading of the
internal probe in the case of a wall-mounted controller and
remote probe disconnected)
■
“
Humidity
” Register: room humidity read by the control-
ler via the probe associated with the temperature probe
used
■
“
Water Temperature
” register: value read by the water
probe (SW)
■
“
P00
” Register: “Controller con
fi
guration” parameter
■
“
T. Active setpoint
” Register: setpoint used for temperature
control
■
“
T. User setpoint
” Register: setpoint programmed by the
user (it may differ from the active setpoint due to correc-
tions based on economy logics,…or use of the setpoint
imposed by the supervision software)
■
“
LCD version
” Register: de
fi
nes the controller type and
software version installed (0xHHSS: HH: ASCII character,
SS:sw version)
■
“
P09
” Register: “Digital output 1 Con
fi
guration” parameter
■
“
P10
” Register: “Digital output 1 Logic” parameter
■
“
P11
” Register: “Digital output 2 Con
fi
guration” parameter
■
“
P12
” Register: “Digital output 1 Logic” parameter
■
“
P14
” Register: “Con
fi
guration of analog outputs” parameter
■
“
Analog output 1
” register: value of analogue output 1
expressed as a % of the full scale 0-10V
■
“
Analog output 2
” register: value of analogue output 1
expressed as a % of the full scale 0-10V
Содержание Advanced plus
Страница 2: ...1 2 5 3 4 ...
Страница 3: ...10 8 11 9 6 7 ...
Страница 4: ...NOTES ...
Страница 21: ......
Страница 39: ......
Страница 57: ......
Страница 75: ......
Страница 93: ......
Страница 111: ......
Страница 129: ......
Страница 147: ......
Страница 165: ......
Страница 183: ......
Страница 185: ...NOTES FC66002554L 1 ...
Страница 186: ......
Страница 187: ...FC66002678 4 UT6600887L 5 ...
Страница 188: ...UT6600888L 6 UT6600889L 7 ...
Страница 189: ......
Страница 190: ......
Страница 191: ...U T 6 6 0 0 1 4 1 6 ...
Страница 192: ...Zandvoordestraat 300 B 8400 Oostende Belgium FC66002765 Stampato su carta riciclata Printed on recycled paper ...