Installation and operation manual
6
FWEC3
Advanced plus electronic controller
FC66002765
DIGITAL 1 OUTPUT
P09
P10 = 0 (NO CONTACT)
P10 = 1 (NC CONTACT)
OPEN
CONTACT
CLOSED
CONTACT
OPEN
CONTACT
CLOSED
CONTACT
0
NOT USED
--
--
--
--
1
OPERATING MODE
SUMMER
WINTER
WINTER
SUMMER
2
UNIT IN COOLING OR
HEATING MODE
NO
YES
YES
NO
3
UNIT IN COOLING MODE
NO
YES
YES
NO
4
UNIT IN HEATING MODE
NO
YES
YES
NO
5
CONTROLLER STATUS
OFF
ON
ON
OFF
6
ALARM TRIGGERED
NO
YES
YES
NO
7
EXTERNAL
DEHUMIDIFICATION CALL
NO
YES
YES
NO
8
EXTERNAL
HUMIDIFICATION CALL
NO
YES
YES
NO
9
HIGH ROOM
TEMPERATURE
NO
YES
YES
NO
10
LOW ROOM
TEMPERATURE
NO
YES
YES
NO
11
NOT USED
--
--
--
--
12
LOW WATER
TEMPERATURE
YES
NO
NO
YES
DIGITAL 2 OUTPUT
P11
P12 = 0 (NO CONTACT)
P12 = 1 (NC CONTACT)
OPEN
CONTACT
CLOSED
CONTACT
OPEN
CONTACT
CLOSED
CONTACT
0
--
--
--
--
1
OPERATING MODE
SUMMER
WINTER
WINTER
SUMMER
2
UNIT IN COOLING OR
HEATING MODE
NO
YES
YES
NO
3
UNIT IN COOLING MODE
NO
YES
YES
NO
4
UNIT IN HEATING MODE
NO
YES
YES
NO
5
CONTROLLER STATUS
OFF
ON
ON
OFF
6
ALARM TRIGGERED
NO
YES
YES
NO
7
EXTERNAL
DEHUMIDIFICATION CALL
NO
YES
YES
NO
8
EXTERNAL
HUMIDIFICATION CALL
NO
YES
YES
NO
9
HIGH ROOM
TEMPERATURE
NO
YES
YES
NO
10
LOW ROOM
TEMPERATURE
NO
YES
YES
NO
11
WATER CIRCUIT
ENABLED FOR COOLING
YES
NO
NO
YES
12
WATER CIRCUIT
ENABLED FOR HEATING
YES
NO
NO
YES
CONFIGURATION OF DIGITAL OUTPUTS
(PARAMETERS
P09,P10,P11,P12
)
P09,P11
= 8
The contact is used to switch ON/OFF any external device
for humidifying the air (heating mode only). The ON/OFF
logic is based on a reading of the humidity in the room and
the SETPOINT selected with parameter P13. It follows the
diagram shown:
P09,P11
= 9
The status of the contact indicates whether the air tempe-
rature is too high compared to the temperature SETPOINT
(only in the “summer” mode); the ON/OFF logic is thus tied
to the value of the temperature SETPOINT, according to the
following step:
P09,P11
= 10
The status of the contact indicates whether the air temperature
is too low compared to the temperature SETPOINT (only in the
“winter” mode); the ON/OFF logic is thus tied to the value of
the temperature SETPOINT, according to the following step:
P09,P11
= 11
The digital output is not governed by the controller; the contact
is always open.
P09,P11
= 12
The contact status indicates that water temperature is low.
The activation/deactivation logic follows the step:
The two tables below provide a detailed explanation of the
meaning of the contact associated with each digital output:
Air humidity
Air temperature
Air temperature
Water temperature
Содержание Advanced plus
Страница 2: ...1 2 5 3 4 ...
Страница 3: ...10 8 11 9 6 7 ...
Страница 4: ...NOTES ...
Страница 21: ......
Страница 39: ......
Страница 57: ......
Страница 75: ......
Страница 93: ......
Страница 111: ......
Страница 129: ......
Страница 147: ......
Страница 165: ......
Страница 183: ......
Страница 185: ...NOTES FC66002554L 1 ...
Страница 186: ......
Страница 187: ...FC66002678 4 UT6600887L 5 ...
Страница 188: ...UT6600888L 6 UT6600889L 7 ...
Страница 189: ......
Страница 190: ......
Страница 191: ...U T 6 6 0 0 1 4 1 6 ...
Страница 192: ...Zandvoordestraat 300 B 8400 Oostende Belgium FC66002765 Stampato su carta riciclata Printed on recycled paper ...