FWEC3
Advanced plus electronic controller
FC66002765
HEATING WITH 3-SPEED CONFIGURATIONS
HEATING WITH 4-SPEED CONFIGURATIONS
2. WATER CONTROL
The checking of water temperature to enable valve opening
is a function that concerns only con
fi
gurations with 3-way
valves and electrical heater. In such con
fi
gurations the water
temperature will be checked in the following cases:
■
Heating with heat element: operation of the electrical heater
will force the fan to switch on; it is therefore necessary to
prevent excessively cold water from passing through the
unit.
■
Post-ventilation due to switching off of the electrical hea-
ter: this function will be maintained until the set time has
elapsed, even if the operating mode is changed. During
post-ventilation the water temperature enabling signal will
coincide with the one seen for fan operation.
DISPLAY
The active valve indication on the display will be shown by
the symbol
ELECTRICAL HEATER
The electrical electrical heater is a device used to provide
support where necessary in the heating mode.
SELECTION
If provided for in the con
fi
guration, the electrical heater can be
selected in the heating mode by pressing the Sel
key
ACTIVATION
If use of the electrical heater is selected by the user, it will be
activated on a call from the thermostat based on the room
temperature
N.B.
: switching it on will force the fan on as well
■
Extra low speed
■
Minimum
Speed
■
Medium
Speed
■
Maximum Speed
N.B.
: in the case of modulating fans, the four symbols mentio-
ned above indicate the interval (extra-low, low, medium
and high) in which the operating speed falls.
N.B.
: if the active speed is different from the one selected by
the user (in the case of a forced override), pressing the
button Fan
once will cause the latter to be displa-
yed; pressing again will change this setting.
VALVE
The controller can manage 2- or 3-way valves of the ON/OFF
type (i.e. completely open or completely closed) or modulating
valves (the degree of valve opening may range between 0%
and 100%). As in the case of fans, parameter
P14
(con
fi
guration
of analog outputs) must be carefully set based on the type of
valves actually present in the unit, so that the controller will
implement the correct control logic.
1. AIR CONTROL
A. OPENING
The valve opening is controlled according to the operating
setpoint and air temperature setpoint
B. MODULATING VALVE
The valve opening is controlled according to the operating
setpoint and air temperature setpoint The regulation logic for
opening conforms to the diagrams below.
COOLING
AIR TEMP.
AIR TEMP.
HEATING
AMBIENT TEMP.
COOLING
OPENING (%)
OPENING (%)
AMBIENT
TEMP.
AMBIENT
TEMP.
OPENING (%)
WATER
TEMP.
AIR TEMP.
Содержание Advanced plus
Страница 2: ...1 2 5 3 4 ...
Страница 3: ...10 8 11 9 6 7 ...
Страница 4: ...NOTES ...
Страница 21: ......
Страница 39: ......
Страница 57: ......
Страница 75: ......
Страница 93: ......
Страница 111: ......
Страница 129: ......
Страница 147: ......
Страница 165: ......
Страница 183: ......
Страница 185: ...NOTES FC66002554L 1 ...
Страница 186: ......
Страница 187: ...FC66002678 4 UT6600887L 5 ...
Страница 188: ...UT6600888L 6 UT6600889L 7 ...
Страница 189: ......
Страница 190: ......
Страница 191: ...U T 6 6 0 0 1 4 1 6 ...
Страница 192: ...Zandvoordestraat 300 B 8400 Oostende Belgium FC66002765 Stampato su carta riciclata Printed on recycled paper ...