SiBE12-519
Control Specification
Function and Control
59
3.6
Freeze-up Protection Control
Outline
During cooling operation, the signals being sent from the indoor unit allow the operating
frequency limitation and then prevent freezing of the indoor heat exchanger. (The signal from
the indoor unit must be divided into the zones as the followings.
Detail
Conditions for Start Controlling
Judge the controlling start with the indoor heat exchanger temperature after 2 sec from
operation start and after 30 sec from changing number of operation room.
Control in Each Zone
3.7
Heating Peak-cut Control
Outline
Heat Pump Only
During heating operation, the signals being sent from the indoor unit allow the operating
frequency limitation and prevent abnormal high pressure. (The signal from the indoor unit must
be divided as follows.)
Detail
Conditions for Start Controlling
Judge the controlling start with the indoor heat exchanger temperature after 2 min from
operation start and
sec from changing number of operation room.
Control in Each Zone
The maximum value of heat exchange intermediate temperature of each indoor unit controls the
following (excluding stopped rooms).
(R4561)
Return from stop
Reset zone
Heat exchanger
thermistor temperature
Up zone
Keep zone
Drooping zone
Stop zone
0˚C
3˚C
5˚C
7˚C
13˚C
When increase
30
When decrease
2
Содержание 2MKS40DVMB
Страница 10: ...SiBE12 519 List of Functions 1 Part 1 List of Functions 1 Cooling Only 2 2 Heat Pump 4 ...
Страница 15: ...Heat Pump SiBE12 519 6 List of Functions ...
Страница 29: ...Heat Pump SiBE12 519 20 Specifications ...
Страница 89: ...Instruction SiBE12 519 80 System Configuration FDK X S25 35C Names of parts Indoor Unit 3 6 8 9 10 7 1 4 5 2 ...
Страница 135: ...Instruction SiBE12 519 126 System Configuration ...
Страница 211: ...Outdoor Unit SiBE12 519 202 Removal Procedure ...
Страница 212: ...SiBE12 519 Others 203 Part 8 Others 1 Others 204 1 1 Test Run from the Remote Controller 204 1 2 Jumper Settings 205 ...
Страница 223: ...Wiring Diagrams SiBE12 519 214 Appendix ...