SiBE12-519
Service Check Function
Service Diagnosis
131
3.
Service Check Function
In the
ARC433A
series remote controller, the temperature display sections on the main unit
indicate corresponding codes.
Check Method 1
1. When the timer cancel button is held down for 5 seconds, a “00” indication flashes on the
temperature display section.
2. Press the timer cancel button repeatedly until a continuous beep is produced.
The code indication changes in the sequence shown below, and notifies with a long beep.
<In case of ARC433A50, 43>
Note:
1. A short beep and two consecutive beeps indicate non-corresponding codes.
2. To cancel the code display, hold the timer cancel button down for 5 seconds. The code
display also cancels itself if the button is not pressed for 1 minute.
No.
Code
No.
Code
No.
Code
1
00
12
C7
23
H0
2
U4
13
H8
24
E1
3
F3
14
J3
25
P4
4
E6
15
A3
26
L3
5
L5
16
A1
27
L4
6
A6
17
C4
28
H6
7
E5
18
C5
29
H7
8
F6
19
H9
30
U2
9
C9
20
J6
31
UH
10
U0
21
UA
32
EA
11
E7
22
A5
33
AH
(R4271)
TEMP
ON/OFF
POWERFUL
MODE
FAN
SWING
SILENT
SENSOR
ECONO
COMFORT
TIMER
ON
CANCEL
OFF
<
ARC433A50, 43
>
TIMER CANCEL button
It cancels the timer setting.
No.
Code
No.
Code
No.
Code
1
00
12
F6
23
A1
2
U4
13
C7
24
E1
3
L5
14
A3
25
UA
4
E6
15
H8
26
UH
5
H6
16
H9
27
P4
6
H0
17
C9
28
L3
7
A6
18
C4
29
L4
8
E7
19
C5
30
H7
9
U0
20
J3
31
U2
10
F3
21
J6
32
EA
11
A5
22
E5
33
AH
Содержание 2MKS40DVMB
Страница 10: ...SiBE12 519 List of Functions 1 Part 1 List of Functions 1 Cooling Only 2 2 Heat Pump 4 ...
Страница 15: ...Heat Pump SiBE12 519 6 List of Functions ...
Страница 29: ...Heat Pump SiBE12 519 20 Specifications ...
Страница 89: ...Instruction SiBE12 519 80 System Configuration FDK X S25 35C Names of parts Indoor Unit 3 6 8 9 10 7 1 4 5 2 ...
Страница 135: ...Instruction SiBE12 519 126 System Configuration ...
Страница 211: ...Outdoor Unit SiBE12 519 202 Removal Procedure ...
Страница 212: ...SiBE12 519 Others 203 Part 8 Others 1 Others 204 1 1 Test Run from the Remote Controller 204 1 2 Jumper Settings 205 ...
Страница 223: ...Wiring Diagrams SiBE12 519 214 Appendix ...