Outdoor Unit
Removal Procedure
201
Step
Procedure
Points
Before working,
make sure that the
refrigerant is empty
in the circuit.
Be sure to apply
nitrogen
replacement when
heating up the
brazed part.
Warning
Since it may happen that
refrigeration oil in the
compressor will catch fire,
prepare wet cloth so as to
extinguish fire immediately.
Warning
Ventilate when refrigerant leaks
during the work.
(If refrigerant contacts fire, it will
cause to arise toxic gas.)
Caution
Be careful about the pipes
which were heated up by a gas
brazing machine, so as not to
get burnt your hands.
3
Heat up the brazed part
of the discharge side
and disconnect.
4
Heat up the brazed part
of the suction side and
disconnect.
5
Lift the compressor up
and remove it.