Function of Main Structural Parts
SiBE12-519
52
Function and Control
2.2.2 Cooling Only Model
A Outdoor Heat
Exchanger
Thermistor
(DCB)
1. The outdoor heat exchanger thermistor is used for controlling target discharge temperature.
The system sets a target discharge temperature according to the outdoor and indoor heat
exchanger temperature, and controls the electronic expansion valve opening so that the
target discharge temperature can be obtained.
2. The outdoor heat exchanger thermistor is used for detecting disconnection of the discharge
thermistor when cooling.
When the discharge pipe temperature becomes lower than the outdoor heat exchanger
temperature, the discharge pipe thermistor is judged as disconnected.
3. The outdoor heat exchanger thermistor is used for high pressure protection during cooling
operation.
B Discharge
Pipe Thermistor
(DOT)
1. The discharge pipe thermistor is used for controlling temperature of the discharge pipe.
If the temperature of discharge pipe (used in place of the inner temperature of the
compressor) rises abnormally, the operating frequency drops or the operation halts.
2. The discharge pipe thermistor is used for detecting disconnection of the discharge
thermistor.
C Gas Pipe
Thermistor
(DGN)
1. In cooling, the gas pipe thermistors are used for gas pipe isothermal control.
The system controls electronic expansion valve opening so that gas pipe temperature in
each room becomes equal.
D
Indoor Heat
Exchanger
Thermistor
(DCN)
1. The indoor heat exchanger thermistor is used for controlling target discharge temperature.
The system sets a target discharge pipe temperature according to the outdoor and indoor
heat exchanger temperature, and controls the electronic expansion valve opening so that
the target discharge temperature can be obtained.
2. The indoor heat exchanger thermistors are used to prevent freezing.
During the cooling operation, if the temperature drops abnormally, the operating frequency
becomes lower, then the operation halts.
3. The indoor heat exchanger thermistor is used for anti-icing control.
During the cooling operation, if the heat exchanger temperature in the room where operation
is halted becomes -1°C, or if the room temperature - heat exchanger in the room where
operation is halted becomes
≥
10°C, it is assumed as icing.
EV
B
EV
A
Compressor
Expansion valve
A
B
C
D
(R4688)
Содержание 2MKS40DVMB
Страница 10: ...SiBE12 519 List of Functions 1 Part 1 List of Functions 1 Cooling Only 2 2 Heat Pump 4 ...
Страница 15: ...Heat Pump SiBE12 519 6 List of Functions ...
Страница 29: ...Heat Pump SiBE12 519 20 Specifications ...
Страница 89: ...Instruction SiBE12 519 80 System Configuration FDK X S25 35C Names of parts Indoor Unit 3 6 8 9 10 7 1 4 5 2 ...
Страница 135: ...Instruction SiBE12 519 126 System Configuration ...
Страница 211: ...Outdoor Unit SiBE12 519 202 Removal Procedure ...
Страница 212: ...SiBE12 519 Others 203 Part 8 Others 1 Others 204 1 1 Test Run from the Remote Controller 204 1 2 Jumper Settings 205 ...
Страница 223: ...Wiring Diagrams SiBE12 519 214 Appendix ...