SiBE12-519
Outdoor Unit
Removal Procedure
197
1.6
Removal of the
Four Way Valve
Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power
supplies before disassembling work.
Step
Procedure
Points
1. Remove the peripheries.
Remove the followings
so as not to be burned
by a gas brazing
machine.
Four way valve coil
Electronic
expansion valve coil
Putty
1
Loosen the screw and
remove the four way
valve coil.
2
Remove the sheet of
putty.
3
Before working,
make sure that the
refrigerant is empty
in the circuit.
Heat up four brazed
parts of the four way
valve and disconnect in
(a)(b)(c)(d) order. (See
the next page also.)
Provide a protective sheet or
a steel plate so that the
brazing flame cannot
influence peripheries.
4
Withdraw the piping
side by pliers.
Be careful so as not to break
pipes by pressing it
excessively by pliers when
withdrawing it.
Содержание 2MKS40DVMB
Страница 10: ...SiBE12 519 List of Functions 1 Part 1 List of Functions 1 Cooling Only 2 2 Heat Pump 4 ...
Страница 15: ...Heat Pump SiBE12 519 6 List of Functions ...
Страница 29: ...Heat Pump SiBE12 519 20 Specifications ...
Страница 89: ...Instruction SiBE12 519 80 System Configuration FDK X S25 35C Names of parts Indoor Unit 3 6 8 9 10 7 1 4 5 2 ...
Страница 135: ...Instruction SiBE12 519 126 System Configuration ...
Страница 211: ...Outdoor Unit SiBE12 519 202 Removal Procedure ...
Страница 212: ...SiBE12 519 Others 203 Part 8 Others 1 Others 204 1 1 Test Run from the Remote Controller 204 1 2 Jumper Settings 205 ...
Страница 223: ...Wiring Diagrams SiBE12 519 214 Appendix ...