User’s Manual
44
Submenu
Setting
●
Key
: The key type zone is used as an auxiliary command to arm/disarm
one or more areas.
●
SIREN FAULT
: The siren fault zone is uses to receive abnormal output
signals from the siren, and it is active for 24 hours a day.
TERMINATION
Each wired zone can be connected according to seven different criteria:
●
N.O.
,
N.C
: Select
N.O
or
N.C
depends on the output type of detectors. For
example, if the output of detector is set to
N.O.
, then you should select
N.O
.
●
1EOL, 2EOL, 3EOL. For definition, see "1.3 Technical Specifications".
●
INERTIAL
: If
INERTIAL
is selected, the level of sensitivity must be set. The
range is 20 ms–5020 ms, and the detector type can be
N.O.
or
N.C
.
●
IMPULSE
: If
IMPULSE
is selected, the times of impulse triggered and
impulse time must be set. The times range is 2–15. For example, if you set
range to be 5, the triggered time is set to be 000.01, this setting means
the alarm is triggered for 5 times within 1 second. The detector type can
be
N.O.
or
N.C
.
AREA
Each wired zone can be assigned to one or more areas (1 to 8). The areas can
be assigned in individual or combined mode, In the case of multiple areas,
the zone is linked to them in
OR
mode or arms when one of them is armed
and disarms when all of them are disarmed.
To assign or remove areas from the keypad, press the corresponding key (1 to
8) and then press
. The number of the assigned area appears on the
programming line to confirm that the selection was successful. The number
of the assigned area disappears from the programming line to confirm that
the deselection was successful.
BYPASS
Each wired zone can be programmed so that it is excludable by the user or
not.
●
NO
: Establishes that the wired zone cannot be bypass by the user.
●
TEMPORARY
: Establishes that the wired zone can be bypass but, when
the area to which it belongs is disarmed, it is automatically re-included.
●
PERMANENT
: Establishes that the wired zone can be bypass and does
not re-arm automatically. Re-inclusion must be performed manually as
described in the
ZOME MANAGER
of user menu.
PARTITION1
Each individual wired zone can be assigned for partition 1 type arming. If this
option is set to
YES
, the wired zone will be involved in the partition 1 arming
of the areas which it belongs to.
PARTITON2
Each individual wired zone can be assigned for partition 2 type arming. If this
option is set to
YES
, the wired zone will be involved in the partition 1 arming
of the areas which it belongs to.
Содержание DHI-ARC3008C
Страница 1: ...Alarm Controller User s Manual ZHEJIANG DAHUA VISION TECHNOLOGY CO LTD V2 0 1...
Страница 25: ...User s Manual 14 2 4 Wiring Figure 2 6 Wiring Figure 2 7 Wiring of detectors...
Страница 31: ...User s Manual 20 4 3 Wiring Figure 4 3 keypad connection...
Страница 41: ...User s Manual 30 5 2 Wiring Figure 5 2 Wiring of detectors...
Страница 45: ...User s Manual 34 Figure 6 2 Remove plugs Step 2 Attach the thermal pad to the 4G module...
Страница 137: ...User s Manual...