Test Motion:  

In the Main Menu, the Test Motion Screen allows the door to be 

operated with the buttons.  This is used when no other controls are connected and it 
is necessary to calibrate the door.  In some cases, it may be easier to run the door 
from the Master Controller Test Motion feature even if other controls are connected. 

Open and Close Speeds:

The user can set the speeds for both opening and 

closing with the Open Speed and Close Speed settings.

Acceleration/Deceleration: 

The user can program the rates at which the door 

accelerates and decelerates, this is configurable separately for each direction.

Custom Software: 

Custom system software features may be added upon request.

Motion Detection: 

Motion sensors may be provided to open or retract the door, 

including safety sensors to monitor for a person or object blocking the door path.

Fire Alarm interface: 

External inputs can be configured to receive input from any low 

voltage source for remote control, such as a fire alarm contact closure.

PiNG Proximity Sensor Option: 

 The Ping Sensor is a small device offered by Dado 

Door that allows for door control when a person gets within a predefined distance 
from the Pin sensor.  The sensor is setup to detect a person( ie hand, foot, etc) within 
a number of inches.  The Ping Setting allows for calibrating the distance for two 
devices.  P1 and P2.  Once the setting is adjusted, any object that comes within that 
distance will trigger the door to open. 

Deadband

   The Deadband value is based on 1" = 500.  This setting in the menu 

determines how precise the door should attempt to hold a position.  In some cases, 
this setting may be increase to reduce some oscillation or 'pulsing' motion when the 
door is supposed to be stopped.  The default setting is 10, which means that the 
door will park typically within 10/500 of an inch precision(.02").  For an exaggerated 
example, if the Deadband is set to 250, the final position of the door could be within 
1/2" of the actual position programmed in the controller.  

7

Содержание Door Master Controller

Страница 1: ...Manual Copyright 2013 All rights reserved No unauthorized duplication distribution or online posting without prior written consent from Dado Door LLC Dado Door LLC and the Dado Logo are registered tr...

Страница 2: ...Motor Driver Fault Error Troubleshooting 20 Advanced Motor Driver Fault Error Troubleshooting Cont d 21 Initial Calibration and Setup 22 Initial Calibration and Setup cont d 23 Error Messages 24 Error...

Страница 3: ...roller contains a simple and easy to follow menu directory of settings When changing a setting they are stored permanently This manual will cover all aspects of the menu It is advised that the install...

Страница 4: ...E fully open quickly turn off the power If the door begins the homing process towards the CLOSED position then the belt has been installed in reverse It is advised that when powering the system up for...

Страница 5: ...formation needed to set up the parameters Buttons Explained Move up or down the Main Menu Add or subtract from a number or select Yes No fields CURSOR Cycle the cursor through a menu item with more th...

Страница 6: ...gs Factory settings Do not change 4 BYPASS MODE If required at power ON the user can immediately PRESS and HOLD down the Setup Mode Button until the Main Menu appears this will bypass the diagnositcs...

Страница 7: ...erial communication Port 8 RS485 interface duplicate for daisy chain Motor 3 Phase Power Leads Connection to the Brushless DC motor power using 26VDC is made with a 3 condutor 18G specially prepared c...

Страница 8: ...y the port that will be used as a Locking Touch Screen inside the room Port A it typically the outside Touch Screen Auto Home Upon each power up the system automatically moves towards a Home switch wh...

Страница 9: ...configured to receive input from any low voltage source for remote control such as a fire alarm contact closure PiNG Proximity Sensor Option The Ping Sensor is a small device offered by Dado Door that...

Страница 10: ...system against overload due to an obstruction during the Homing phase The parameters may need to be adjusted to account for the weight speed and friction of each door by the user at the time of insta...

Страница 11: ...ng thus a higher Trip Level will be required to avoid false trips Each time the speed is adjusted in the menu the Trip Levels will need to be adjusted as well for optimal retraction If you have set th...

Страница 12: ...where the motor door are in a highly precision manner The Set Close Position value shown in the display will equate to approximately 1 500 As an example if the value says 5000 then calculate 5000 500...

Страница 13: ...ressure on the door during the closing motion Above a certain pressure on the door the door will auto retract Closing Trip Level In some cases during the last couple of inches of travel closing as the...

Страница 14: ...mber means the factor will be larger and will take longer to slow the door to a stop To cause the door to take longer to accelerate to full speed choose a higher accel factor Shorter values produce a...

Страница 15: ...opposite direction while the arrows are pressed Due to the fact that there are numerous ways a system can be set up these arrows may not always reflect the direction that the door is actually moving i...

Страница 16: ...ned on the offset value is used for the fully open position The value in the menu is approximately 1 500 So for example to create a 1 2 offset put the offset value at 250 The door should move as the s...

Страница 17: ...controller The Destination number will always be 0 by default System Input Configuration The system controller has a number of options for controlling the door On the top of the enclosure are the con...

Страница 18: ...attached to the motor that allows the system to know very precisely where the motor and door are at all times If the encoder has been damaged or the cable that connects the system controller to the m...

Страница 19: ...Fault LED on the motor driver board is lit right away then there is a problem 1 The Motor Logic cable is not plugged in from the Master Controller to the motor 2 On the motor there is a set of five w...

Страница 20: ...any wires out of a pair Each end of the CAT5 cable should be identical colors not mirrored colors When the connection problem is resolved on power up the motor driver board will only have the Green PW...

Отзывы: