Preparation and Setup

The blower direction is through top  

 A 

 of the hood. 

However, the blower can be rotated to vent through the  

rear

 

 B 

 of the hood. 

When planning new ductwork, always find the shortest, 

most direct route to the outside. 

Duct Length Calculation Table

The maximum straight duct length for the hood is deter-

mined by the type of duct used. See the chart below.

Duct Size

Maximum Duct Run

8-inch Round

60 feet

10-inch Round

50 feet

3 1/4-in x 10-in Rectangular

50 feet

For each elbow and transition added, “equivalent lengths” 

must be subtracted from your total maximum duct run 

length to compensate for wind resistance.
To determine your maximum length: 
1.  Start with the total max. length of your duct run, then 
2.  Subtract all of the ductwork equivalent lengths (see  

chart below).

Ductwork Equivalent Lengths

Piece

Subtract

Piece

Subtract

8-inch 

90° Elbow

7 feet

10-inch 90° Elbow

5 feet

8-inch 

45° Elbow

3 feet

10-inch 45° Elbow

2 feet

3-in x 10-inch

to Round 90°

 Transition

25 feet

3¼ in x 10 in to 8 

in / 10 in Round 

Transition

4 feet

Roof Cap

*

Wall Cap with 

Damper

*

* The equivalent lengths of roof and wall caps vary with 

model and configuration.

A

B

Planning the Ductwork

 WARNING

•  To prevent combustion by-products, smoke or odors 

from entering the home and to improve efficiency, tape 

all duct joints securely.

•  Range hoods may interrupt the proper flow of smoke 

and combustion gases from furnaces, gas water heat-

ers, and fireplaces. To avoid drawing lethal gases into 

the home, follow the manufacturer’s recommendation 

for these devices and consult NFPA and ASHRAE rec-

ommendations.

•  Failure to install a remote blower or proper ductwork 

may result in a backdraft and/or insufficient venting of 

smoke and fumes.

• 

DO NOT

 install an additional in-line or external blower 

to increase the length of the duct run. Even small dif-

ferences between blower air flow rates can greatly 

reduce the air draw by the hood.

 CAUTION

To reduce the risk of fire and to properly exhaust air, be 

sure to duct air outside the house or building. Do not vent 

exhaust air into spaces within walls or ceilings or into 

attics, crawl spaces or garages.

•  Local building codes may require the use of makeup air 

systems with ventilation systems that move air greater 

than the specified movement rate (CFM). The specified 

rate varies based on locale. Consult a qualified HVAC 

specialist when designing the system for the require-

ments in your area and to assure optimal performance.

•  All ductwork materials (including screws and foil tape) 

must be purchased separately by the customer.

•  Make sure ductwork does not interfere with floor joists  

or wall studs.

•  On dual exhaust models, the two 8-inch exhausts may 

be merged into one 10-inch duct using Dacor transition 

kit AHT10. See page 19 for details.

•  Fasten all joints with sheet metal screws and seal with 

certified duct tape or foil tape.

Vent Direction Options

 WARNING

During duct installation, make sure there are no 

obstructions that keep the damper flaps on the top of the 

hood from opening.

Содержание RNHP36 Renaissance

Страница 1: ...oods Models RNHP30 RNHP36 and RNHP48 Part No 109172 Rev A APPROVED FOR USE WITH ALL DACOR RANGES AND COOKTOPS TESTED IN ACCORDANCE WITH THE LATEST EDITION OF ANSI UL 507 STANDARD FOR ELECTRIC FANS AND...

Страница 2: ...nstructions completely and carefully before you begin the installation process Leave these installation instructions with the consumer Write the Data Plate Information in the Use and Care Manual befor...

Страница 3: ...amage personal injury or death WARNING WARNING TO REDUCE THE RISK OF FIRE ELECTRIC SHOCK OR INJURY TO PERSONS OBSERVE THE FOLLOWING a Use this unit only in the manner intended by the manufacturer If y...

Страница 4: ...appliance only as instructed in the Use and Care Manual Use only the cleaners specified Do not tamper with the controls Never allow the filters to become blocked or clogged Do not allow foreign object...

Страница 5: ...s Model Number RNHP48 RNHP36 RNHP30 Lights 4 3 2 Filters 4 3 2 Blowers 2 1 1 Exhaust Vents 2 1 1 Blower Rating 1200 CFM 600 CFM 600 CFM Product Specifications Model Weight RNHP3012 51 lbs 23 kg RNHP30...

Страница 6: ...holes 7 8 in dia 5 1 cm C A Dual Exhaust Models Standard 8 inch duct Single Exhaust Models Standard 8 inch duct Bottom of hood C Electrical access holes 7 8 in 5 1 cm diameter 19 3 4 in 50 2 cm Conne...

Страница 7: ...3018 29 7 8 75 9 cm 24 61 cm 18 45 7 cm 11 7 8 30 2 cm RNHP3618 35 7 8 91 1 cm RNHP4818 47 7 8 121 6 cm Top Access Holes A B C RNHP48 1 1 2 3 81 cm 5 12 7 cm 3 7 62 cm RNHP36 1 1 2 3 81 cm 4 1 2 11 43...

Страница 8: ...s and hardware are within reach before beginning the installation pictures vary by model Blower Rotation optional Phillips screwdriver 5 16 Nut driver Hood Model RNHP48 RNHP36 RNHP30 LED Lights 4 3 2...

Страница 9: ...electrician Do not ground the appliance or appliance wiring to a gas pipeline or to the neutral white power supply wire Do not install a fuse in the neutral or ground circuit Connect the hood directl...

Страница 10: ...ations for the cooktop or range E 30 min 76 2 cm Electrical access From cooking surface top rear E Minimum Width of E Upper Cabinet Cutout Appliance Width Models E RNHP3012 RNHP3018 30 inches 76 2 cm...

Страница 11: ...s water heat ers and fireplaces To avoid drawing lethal gases into the home follow the manufacturer s recommendation for these devices and consult NFPA and ASHRAE rec ommendations Failure to install a...

Страница 12: ...etup Ductwork Tips Wherever possible reduce the number of transitions turns and sharp angles Two staggered 45 angles are better than one sharp 90 angle Keep turns as far away from the hood exhaust as...

Страница 13: ...les in the back and top of the hood Holding Brackets Enlarged for Detail Support Block Model Weight RNHP3012 51 lbs 23 kg RNHP3018 RNHP3612 53 lbs 24 kg RNHP3618 57 lbs 26 kg RNHP4812 70 lbs 32 kg RNH...

Страница 14: ...or example if it is a top vent installa tion set the hood with the vents on top 2 Measure the distance from the edge of the hood to the center of the exhaust port 3 Transfer that measurement to the wa...

Страница 15: ...with the horizontal centerline Make sure the anchors and or screws being used are strong enough to support the hood Make sure drywall installations are properly reinforced 5 Mark the two holes in the...

Страница 16: ...ar Exhaust WARNING Do not install the range hood unless the electrical service provided meets the range hood specifications Observe all governing codes and ordinances during installation Contact your...

Страница 17: ...allation Instructions Removing the Blower s 4 Tip the hood up so that it lays on its back You are now facing inside the hood 5 Find the end of the cable assembly plugged into the bottom left of the bl...

Страница 18: ...ear Exhaust 9 Unscrew and remove the L bracket that is in the default top venting orientation 10 Turn and align the L bracket so the hole is in back of the hood allowing a rear venting configuration c...

Страница 19: ...1 Roll the hood on its top so the tip of the blower can extend beyond the exit vent 12 Insert the blower into the exit vent with this specific placement When standing at the back of the hood and looki...

Страница 20: ...1 Remove the plastic coating and confirm that the inside lip is beveled If this is true proceed If not flip the frame 2 Align the screw lock washer and knob with the filter Make sure the knob is on th...

Страница 21: ...TANT Rear vent 12 inch tall hood configurations keep one of the long edges straight 12 inch tall hoods are models 3012 3612 4812 Bending the Flange for Top Vent Configuration None Rear Only Rear Vent...

Страница 22: ...3018 3618 4818 18 inch height requirement 1 Drill holes for screws in the flanges Make sure the holes pierce the rear of the hood see right 2 Center the AHT10 transition kit over the duct collars 3 Fa...

Страница 23: ...ts final position 4 Mark the spot by drawing in a mounting hole in the back of the hood see figure Hanging and Mounting Slots This is where a screw will hold the hood to the wall stud or concrete anch...

Страница 24: ...ted circuit See Wire Diagrams Control Panel Wire Diagram Hardwiring the Hood WARNING To avoid electric shock or fire hazard prior to connecting the electrical wiring to the hood make sure that power t...

Страница 25: ...n cup to the lens of a dimmable light bulb Both are supplied parts Make sure the bulb faces are clean so the suction cup can stick 2 Insert the bulb into one of the light fixtures 3 Screw it into plac...

Страница 26: ...on at low speed 9 Slowly touch and release the FAN button three times Verify that with each touch the number of lights rises and that the fan speed increases 10 Press the FAN button again to turn the...

Страница 27: ...rding to the instructions on page 13 and 21 Is the ductwork completely installed Are all joints attached with sheet metal screws and wrapped with foil tape See page 19 Is the range hood wired and grou...

Страница 28: ...0 9 8 7 6 5 4 3 2 1 HOOD LIGHT 75W HOOD LIGHT 75W CLEAN FILTER LED INDICATOR RESISTOR 620 1 4W 2 3 4 FAN SPEED LED INDICATOR RESISTOR 3 6K 1 4W 3 4 FAN SW 4 3 4 3 LIGHT SW TIMER SW CAUTION DISCONNECT...

Страница 29: ...6 5 4 3 2 1 HOOD LIGHT 75W HOOD LIGHT 75W HOOD LIGHT 75W CLEAN FILTER LED INDICATOR RESISTOR 620 1 4W 2 3 4 FAN SPEED LED INDICATOR RESISTOR 3 6K 1 4W 3 4 FAN SW 4 3 4 3 LIGHT SW TIMER SW CAUTION DIS...

Страница 30: ...1 10 9 8 7 6 5 4 3 2 1 HOOD LIGHT 75W HOOD LIGHT 75W HOOD LIGHT 75W CLEAN FILTER LED INDICATOR RESISTOR 620 1 4W 2 3 4 FAN SPEED LED INDICATOR RESISTOR 3 6K 1 4W 3 4 FAN SW 4 3 4 3 LIGHT SW TIMER SW W...

Страница 31: ...29 Notes...

Страница 32: ......

Страница 33: ...Dacor 14425 Clark Avenue City of Industry CA 91745 Phone 800 793 0093 Fax 626 403 3130 www dacor com...

Отзывы: