13.4  oF/ot: Blockage due to current overload in the output stages with temperature of the stages higher 

than 45°C

The letters “oF” and “ot” are shown alternately on the display, indicating that a current higher than the safety 
threshold has been detected in the output stages and that the temperature of the stages is higher than 45°C.  
This means that it might be possible to restart the electropump once the stages have cooled down. The 
operating principle of this protection is as follows: since single-stage pumps are characterised by a high 
starting current, to make it possible to protect the stages both at starting and during normal operation, 2 
different protection thresholds have been introduced.
Moreover, the protection threshold for starting decreases as the temperature of the output stages  increases, so 
that it will be easier to have a blockage for current overload when trying to start a single-phase pump when 
the stages are too warm. 

13.5  SC : Blockage due to direct short circuit between the phases of the output terminal 

The ACTIVE DRIVER is equipped with protection against the direct short circuit which may occur 
between the phases U, V, W of the “PUMP” output terminal. When this block status is indicated, you 
are advised to eliminate the short circuit and to check the wiring carefully to ensure it is unbroken and 
the installation in general. Once these checks have been made you can try to reset operation by 
simultaneously pressing the  

+

and –  keys; 

anyway, this will have no effect until 10 seconds have 

passed from the moment in which the short circuit occurred.

Whenever a short circuit occurs, an event counter is increased and saved in the permanent memory  
(EEPROM).

AFTER THE HUNDREDTH SHORT CIRCUIT THE MACHINE BLOCKS PERMANENTLY 
AND IT WILL NO LONGER BE POSSIBLE TO UNBLOCK IT! 

13.6  MANUAL RESET of error condition 

In error status the operator can reset the error by forcing a new attempt, pressing the  

+

 and 

 keys 

simultaneously. 

13.7  Self-reset of error conditions 

For some malfunctions and block conditions, the system makes attempts at automatic reset of the 
electropump. 
The following table shows the sequences of the operations performed by the ACTIVE DRIVER for the 
different types of blockage. 

Automatic resets of error conditions 

Display indication

Description 

Sequence of automatic reset 

bL 

Blockage due to water lack 

- An attempt every 10 minutes for a total of 6 attempts 
- An attempt every 1 hour for a total of 24 attempts 
- An attempt every 24 hours for a total of 30 attempts 

bP

Blockage due to fault of the 
pressure sensor

- Reset 10 seconds after correct conditions return

LP

Blockage due to low supply 
voltage

- Reset when voltage returns to a value in the range 

220V - 20% + 10% 

HP

Blockage due to high 
voltage

- Reset when the internal voltage returns in acceptable   

conditions

Ot

Blockage due to overheating 
of the power stages 

- Reset when the temperature of the power stages falls 

below 70°C again 

OC

Blockage due to current 
overload 

- An attempt every 10 minutes for a total of 6 attempts 

oF

Blockage due to current 
overload in the output 
stages 

- An attempt every 10 minutes for a total of 6 attempts 

oF/ot

Blockage due to current 
overload in the output 
stages with temperature of 
the stages higher than 45°C

- An attempt every 10 minutes or when the temperature 
has fallen by 10°C. The counting of the attempts is 
shared with that of the blockage oF.

Содержание ACTIVE DRIVER M/M 1.1

Страница 1: ...ifications KONFORMIT TSERKL RUNG Die Firma DAB PUMPS s p a Via M Polo 14 Mestrino PD ITALIEN erkl rt eigenverantwortlich dass die vorstehend beschriebenen Produkte den folgenden Richtlinien entspreche...

Страница 2: ...SENIE O ZHODE Spolo nos DAB PUMPS s p a Via M Polo 14 Mestrino PD Taliansko vyhlasuje na vlastn v hradn zodpovednos e v robky uveden v d al om texte zodpovedaj Smernici Elektromagnetick kompatibilita...

Страница 3: ...nd SET and keys for 5 seconds 46 8 6 1 tb Setting the reaction time of the water lack blockage 46 8 6 2 GP Setting the gain of the proportional coefficient of the PI 46 8 6 3 GI Setting the gain of th...

Страница 4: ...ircuit between the phases of the output terminal 52 13 6 Manual reset of error conditions 52 13 7 Self reset of error conditions 52 14 INDICATIONS ON THE DISPLAY 53 INDEX OF TABLES Page Table 4 Techni...

Страница 5: ...Manufacturer declines all responsibility for possible errors in this instructions manual if due to misprints or errors in copying The Manufacturer reserves the right to make any modifications to produ...

Страница 6: ...rth terminal 5 2 Check that all the connecting cables are in excellent conditions with the external sheathing unbroken 5 3 The motor of the installed electropump must comply with the data in the table...

Страница 7: ...is operative it is absolutely necessary to protect it suitably against frost and to leave it constantly fed If it is disconnected from the power supply the anti frost function is no longer active If t...

Страница 8: ...excluding A D M M 1 1 and A D M T 1 0 250 Vac 6 A max resistive load 3 A max inductive load J14 o2 Pump operating connection terminal excluding A D M M 1 1 and A D M T 1 0 250 Vac 6 A max resistive l...

Страница 9: ...regulating pressure becomes P1 switch over active setpoint SP or P1 Example Use IN 3 When IN 3 is activated the pump is blocked and the signal F3 is given ex IN 3 could be connected to a safety pressu...

Страница 10: ...a plate of the electropump motor If the set parameter is lower than the correct one during operation the error message oC will appear as soon as the set current has been exceeded for a certain time If...

Страница 11: ...ng status 8 5 1 rC Setting the rated current of the electropump excluding A D M M 1 1 This parameter must be set the same as the current on the motor data plate Amps in the configuration in which it i...

Страница 12: ...CTIVE DRIVER on each of the two machines 8 5 7 Eb Enable booster pre set value 2 excluding A D M M 1 1 When two ACTIVE DRIVER units are interconnected with each other in the case where only one ACTIVE...

Страница 13: ...with Fn whenever a new Fn is set 8 6 6 Ft Setting the low flow rate threshold The ACTIVE DRIVER system possesses a flow sensor Whenever the electropump is switched off a new zero is acquired The ACTI...

Страница 14: ...ump has to be started for the time St The pre set value is 45 Hz and it may be varied between Fn and Fn 50 using the and keys If a FL higher than Fn 50 has been set SF will be limited to the value of...

Страница 15: ...le no 14 page 53 Access keys SET and for 2 seconds From normal operating status pressing the key SET and enters the MONITOR function where the following values are displayed NB to scroll through the v...

Страница 16: ...nks quickly When the electropump is OFF the display blinks slowly In manual mode pressing the SET key takes you out of the menu but if the electropump has been started pressing the key stops only the...

Страница 17: ...ion Description bL Blockage due to water lack bP Blockage due to absence of pressure sensor LP Blockage due to low supply voltage HP Blockage due to high rectified voltage ot Blockage due to overheati...

Страница 18: ...enever a short circuit occurs an event counter is increased and saved in the permanent memory EEPROM AFTER THE HUNDREDTH SHORT CIRCUIT THE MACHINE BLOCKS PERMANENTLY AND IT WILL NO LONGER BE POSSIBLE...

Страница 19: ...flow rate threshold 15 15 15 15 15 CM Exchange method on sets of 2 electropumps 01 01 01 01 AE Setting the enabling of the anti block anti frost function 01 01 01 01 01 SF Setting the starting freque...

Страница 20: ...e sensor LP Blockage due to low supply voltage HP Blockage due to high supply voltage ot Blockage due to overheating of the power stages oC Blockage due to current overload in the electropump motor oF...

Страница 21: ...6 Ad A D M M 1 1 136 8 5 7 Eb booster 2 A D M M 1 1 136 8 6 MODE SET 5 136 8 6 1 tb 136 8 6 2 GP PI 136 8 6 3 GI PI 137 8 6 4 FS 137 8 6 5 FL 137 8 6 6 Ft 137 8 6 7 CM 1 A D M M 1 1 137 8 6 8 AE 137...

Страница 22: ...2 140 11 RESET MODE SET 140 12 SET 140 13 140 13 1 bL 141 13 2 bP 141 13 3 LP A D M M 1 1 A D M T 1 0 142 13 4 oF ot 45 C 142 13 5 SC 142 13 6 reset 142 13 7 142 14 143 4 130 8 1 131 8 2 134 8 6 12 IN...

Страница 23: ...9 1 2 2 1 IEC 60634 2 2 CEI 64 2 2 3 ACTIVE DRIVER 2 4 IEC 536 1 NEC U V W Active Driver M M 1 1 R S EN 60204 9 2 5 4 3 ACTIVE DRIVER ACTIVE DRIVER M T 230V ACTIVE DRIVER M M 230V ACTIVE DRIVER T T 40...

Страница 24: ...r 16 bar 16 bar 16 bar 16 bar 1 6 bar 1 9 bar 1 15 bar 1 15 bar 1 15 bar x x 22x28x18 cm 22x28x18 cm 22x28x18 cm 22x28x18 cm 22x28x18 cm 1 1 1 1 1 1 1 1 1 1 IP 55 IP 55 IP 55 IP 55 IP 55 A D M M A D M...

Страница 25: ...RIVER ACTIVE DRIVER 7 2 ACTIVE DRIVER 7 3 ACTIVE DRIVER 7 4 ACTIVE DRIVER 0 C ACTIVE DRIVER ACTIVE DRIVER 8 ACTIVE DRIVER ACTIVE DRIVER inverter M M 1 1 M T 1 0 ACTIVE DRIVER 3 2 1 2 3 2 ACTIVE DRIVER...

Страница 26: ...I3 I2 A D M M 1 1 A D M T 1 0 6 IN 1 i1 A D M M 1 1 A D M T 1 0 J22 7 0V DC GND A D M M 1 1 A D M T 1 0 o1 A D M M 1 1 A D M T 1 0 250 Vac 6 A 3 A J14 o2 A D M M 1 1 A D M T 1 0 250 Vac 6 A 3 A J9 1...

Страница 27: ...N 1 F1 IN 1 IN 2 IN 2 P1 set point SP P1 IN 3 IN 3 F3 IN 3 Max 48V Max 50Vrms Max 48V Max 50Vrms Max 48V Max 50Vrms 1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7 AC DC 1 2 3 4 5 6 7 AC DC 1...

Страница 28: ...MODE SET SET 6 6 SET SET 8 3 ACTIVE DRIVER 14 143 ACTIVE DRIVER ZF EC ACTIVE DRIVER Hz 8 3 1 rC MODE SET rC oC SET Fn ACTIVE DRIVER EC 8 3 2 Fn rC MODE Fn Fn MODE SET ACTIVE DRIVER 8 3 3 Fn MODE rt AC...

Страница 29: ...M 1 1 1 9 bar A D M T 1 0 1 15 bar SET ACTIVE DRIVER RP bar SP 8 5 14 143 MODE SET 5 SET MODE SET rC MODE set 8 5 1 rC A D M M 1 1 Ampere 230V A D M T 400V A D T T 8 5 2 rt A D M M 1 1 0 1 Fr MODE GO...

Страница 30: ...der ACTIVE DRIVER Ad Ad ACTIVE DRIVER Go Sb Ad ACTIVE DRIVER ACTIVE DRIVER SP setpoint rP Eb booster CM M dP P1 set point P1 2 ACTIVE DRIVER 8 5 7 Eb booster 2 A D M M 1 1 ACTIVE DRIVER ACTIVE DRIVER...

Страница 31: ...Ft ACTIVE DRIVER ACTIVE DRIVER 0 ZF Ft 8 6 7 CM 1 A D M M 1 1 ACTIVE DRIVER CM 0 ACTIVE DRIVER leader ACTIVE DRIVER booster Eb 2 Eb 1 23 leader leader booster Eb 2 leader ACTIVE DRIVER booster leader...

Страница 32: ...11 St St SF PI St 1 St 0 3 8 6 12 IN1 IN2 IN3 i1 i2 i3 A D M M 1 1 A D M T 1 0 IN1 IN2 IN3 i1 i2 i3 i1 i2 i3 0 1 3 2 3 i3 3 4 5 IN1 IN2 IN3 0 1 2 3 4 5 F1 i1 F1 IN1 Set point P1 IN1 set point P1 i2 F2...

Страница 33: ...t point SP P1 1 9 bar 8 6 14 O1 1 A D M M 1 1 A D M T 1 0 O2 2 A D M M 1 1 A D M T 1 0 OUT1 OUT2 0 1 2 3 o1 o2 9 9 1 14 143 MODE MODE Fr Hz UP bar C1 A A D M M 1 1 A D M T 1 0 UE 9 2 SET 2 SET MONITOR...

Страница 34: ...FS UP bar C1 A rt UF ZF MODE MODE 2 SET SET SET SET 10 1 rt SET 2 10 2 MODE FP SET SET SET 11 RESET 14 143 MODE SET 4 MODE SET 12 14 143 SET 2 14 143 SET EE ACTIVE DRIVER ACTIVE DRIVER RC 0 EC MODE S...

Страница 35: ...141 bL oC oF SC FS FS 20 Fr Lt LC Lb bL bP LP HP ot ob oC oF oF ot 45 C SC EC rC Fn E0 E7 0 7 F1 1 F3 3 13 1 bL setpoint bL 2 3 13 2 bP ACTIVE DRIVER bP 10...

Страница 36: ...A D M T 1 0 180V ACTIVE DRIVER 200V 13 4 oF ot 45 C oF ot 45 C 2 13 5 SC ACTIVE DRIVER U V W PUMP 10 EEPROM 13 6 RESET 13 7 ACTIVE DRIVER bL 10 6 1 24 24 30 bP 10 LP 220V 20 10 HP Ot 70 C OC 10 6 oF 1...

Страница 37: ...ar 0 5 bar Ad Eb booster 02 02 02 02 MODE SET 5 tb s 10 s 10 s 10 s 10 s 10 s GP PI 1 0 1 0 1 0 1 0 1 0 GI PI 1 0 1 0 1 0 1 0 1 0 FS Hz 50 50 50 50 50 FL Hz 0 0 0 0 0 Ft 15 15 15 15 15 CM 2 01 01 01 0...

Страница 38: ...144 14 Reset MODE SET A D M M 1 1 A D M T 1 0 A D M T 2 2 A D T T 3 0 A D T T 5 5 ZF ZF SET 2 EE EEprom bL bP LP HP ot oC oF oF ot 45 C SC EC rC Fn E0 E7 0 7 F1 1 F3 3...

Отзывы: